Plan Review Details - Permit 01030568
Plan Review Stops For Permit 01030568
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-07-06 Cont ID  
Sent By jwitmer Date 2001-07-06 Time 09:10 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-06 00:00:00REVISION:

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-04-27 Cont ID  
Sent By jwitmer Date 2001-04-27 Time 14:30 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-27 00:00:00PROVISO: CONTRACTOR TO PROVIDE PRODUCT
 APPROVAL FOR IMPACT RESISTANT GLAZING OR
 STORM SHUTTERS. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-03-20 Cont ID  
Sent By jwitmer Date 2001-03-20 Time 14:35 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-20 00:00:00BUILDING PLAN REVIEW
  
 1)- THE CITY IS CURRENTLY USING THE
 1997 SBC NOT 1999.
  
 2)- SBC 1606.4/ 1707.4.1 COUNTY AMEND-
 MENTS: GLAZED OPENINGS REQUIRE IMPACT
 RESISTANT GLAZING OR STORM SHUTTERS THAT
 HAVE APPROVAL. THE CITY ACCEPTS SBCCI
 OR DADE COUNTY PRODUCT APPROVALS.
  
 3)- ENERGY CALS (2) SETS
  
 4)- DOOR #4 SEE FL ACCESSIBILITY CODE
 MANEUVERING AT DOORS PUSH SIDE MINIMUM
 OF 12 INCHES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-07-12 Cont ID  
Sent By dpalmer Date 2001-07-12 Time 10:53 Rev Time 0.00
Received By dpalmer Date 2001-07-12 Time 10:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-07-05 Cont ID  
Sent By dpalmer Date 2001-07-05 Time 08:49 Rev Time 0.00
Received By dpalmer Date 2001-07-05 Time 08:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-04-26 Cont ID  
Sent By dpalmer Date 2001-04-26 Time 21:52 Rev Time 0.00
Received By dpalmer Date 2001-04-26 Time 21:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-27 Cont ID  
Sent By dpalmer Date 2001-03-27 Time 19:16 Rev Time 0.00
Received By dpalmer Date 2001-03-27 Time 19:16 Sent To  
Notes
2001-03-27 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE SHOW LOAD CALCULATION
 PERART 220.
 PLEASE SEE 220-12 FOR TRACK LIGHTING
 CALCULATION.
 PLEASE NOTE THAT ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125% 215-2.
  
 2)NOTE: PLEASE CLARIFY FEED GOING FROM
 METER TO DISCONNECT AND THEN ABACK TO
 METER AND THEN TO PANEL? METER CAN NOT
 BE USED AS A RACEWAY 373-8. TYPE-O?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-07-06 Cont ID  
Sent By mcarsill Date 2001-07-06 Time 13:06 Rev Time 0.00
Received By mcarsill Date 2001-07-06 Time 13:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-05-22 Cont ID  
Sent By mcarsill Date 2001-05-22 Time 15:20 Rev Time 0.00
Received By mcarsill Date 2001-05-22 Time 15:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-04-24 Cont ID  
Sent By mcarsill Date 2001-04-24 Time 14:41 Rev Time 0.00
Received By mcarsill Date 2001-04-24 Time 14:41 Sent To  
Notes
2001-04-24 00:00:001) NO CITY PLACE STAMP PRESENT ON PLANS.
 2) PLEASE INDICATE ON PLANS WHERE THE
 FIRE ALARM EQUIPMENT IS LOCATED WITHIN
 THOMAS KINKADE GALLERY.
 3) PLAN REVIEW COMMENT LETTER INDICATES
 THAT FIRE SPRINKLER CONTRACTOR WILL
 BE DOING FIRE ALARM WORK. A LICENSED
 FIRE ALARM CONTRACTOR IS RESPONSIBLE
 FOR FIRE ALARM WORK WITH A VALID
 PERMIT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-03-16 Cont ID  
Sent By mcarsill Date 2001-03-16 Time 08:46 Rev Time 0.00
Received By mcarsill Date 2001-03-16 Time 08:46 Sent To  
Notes
2001-03-16 00:00:001) CANVAS CANOPY TO BE FIRE RETARDANT.
 2) FIRE SPRINKLER HEADS SHOWN ON
 REFLECTED CEILING PLAN ARE TO BE DONE
 BY SEPARATE PLAN AND PERMIT.
 3) NO FIRE ALARM EQUIPMENT SHOWN ON
 DRAWINGS. THE GENERAL NOTES ON A-3
 INDICATES AND ADT FIRE ALARM SYSTEM.
 PLEASE CHECK CITY PLACE STANDARDS FOR
 FIRE ALARM EQUIPMENT AND SYSTEMS.
 4) WRONG TRAVEL DISTANCE NOTED ON PLANS.
 SHOULD READ 150 FEET INSTEAD OF 250
 FEET.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-07-03 Cont ID  
Sent By pkrauss Date 2001-07-03 Time 11:00 Rev Time 0.40
Received By pkrauss Date 2001-07-03 Time 11:00 Sent To  
Notes
2001-07-03 00:00:00REVISION APPROVED FOR MECHANICAL, HAVE
 NOT ENTERED APPROVAL ON MECH DUE TO A
 PROBLEM WITH MTRAC "CLOSING" AND C.O.
 ON THE PERMIT.
  
  
 ONLY INSPECTION DONE WAS A ROUGH...NO
 FINAL AS OF YET.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-04-27 Cont ID  
Sent By pkrauss Date 2001-04-27 Time 11:53 Rev Time 0.40
Received By pkrauss Date 2001-04-27 Time 11:53 Sent To  
Notes
2001-04-27 00:00:00*****************PROVISO****************
  
 CONDENSATE SHALL NOT GO TO SANITARY.
  
 MECHANICAL PERMIT REQUIRED PRIOR TO ANY
 WORK BEING PERFORMED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-03-20 Cont ID  
Sent By pkrauss Date 2001-03-20 Time 16:06 Rev Time 0.40
Received By pkrauss Date 2001-03-20 Time 15:26 Sent To  
Notes
2001-03-20 00:00:00******************DENIED****************
  
 PROVIDE OUTSIDE AIR CALCULATIONS AND AIR
 BALANCE SCHEDULE AS PER ASHRAE 62-89.
  
 DRAWING M1.1 DETAIL OF ROOF PLAN HVAC
 INDICATES THE STAND FOR ACCU-1 HAVING A
 MINIMUM HEIGHT OF 12" (NOTE 3), THIS
 SHOULD BE A MINIMUM OF 18" FROM THE
 ROOF SURFACE TO BOTTOM OF THE LOWEST
 SUPPORT ON THE STAND.AMENDED 1997 SMC
 304.2.5.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-07-02 Cont ID  
Sent By kstevens Date 2001-07-02 Time 16:08 Rev Time 0.25
Received By kstevens Date 2001-07-02 Time 16:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-05-23 Cont ID  
Sent By pschmitz Date 2001-05-23 Time 10:10 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-23 00:00:00PROVISO: TRAP PRIMER REQ.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-03-31 Cont ID  
Sent By jleech Date 2001-03-31 Time 12:54 Rev Time 1.00
Received By jleech Date 2001-03-31 Time 12:54 Sent To  
Notes
2001-03-31 00:00:00DENIED;
  
 1.HANDICAP BATHROOM SHALL HAVE AN
 UNOBSTRUCTED PATH FACBC PAGE 9.
  
 2.THE WATER CLOSET SHALL BE LOCATED IN
 THE CORNER DIAGONAL TO THE DOOR FACBC
 4.17.3 EXCEPTION (NEW CONSSTUCTION) 2.
  
  
 3.SHUTOFF VALVE REQUIRED FOR STORE'S
 WATER SUPPLY. SPC 610.1.
  
 4.FLOOR DRAIN IN BATHROOM REQUIRES A
 TRAP PRIMER. SPC. 409.4.1.1.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377