2001-03-06 00:00:00 | *************** UNSAT **************** |
| |
| 1)NOTE: PLEASE NOTE, SPACE MUST HAVE |
| A 2 (TWO) HOUR FIRE WALL ALL THE TO |
| ROOFLINE IF SPACE IS GOING TO BE A |
| SEPARATE SERVICE. 230-2. IF THE SERVICE |
| SHOWN IS THE SAME SERVICE FEEDING THE |
| SAME BLDG THEN THIS WOULD BE OK? PLEASE |
| CLARIFY. |
| |
| 2)NOTE: PLEASE NOTE, THAT PER F.A.C. |
| 553-79 6A 277/480V SERVICES MUST BE |
| SIGNED AND SEALED BY AN P.E. |
| |
| 3)NOTE: PLEASE NOTE THAT ALL CONTINUOUS |
| LOADS ARE TO FIG AND SHOWN AT 125% |
| PER 215-2,3 |
| |
| 4)NOTE: PLEASE PROVIDE CLARIFICATION ON |
| THE INSTALLATION OF TRANSFORMER PER |
| 450-13B. |
| |
| 5) PLEASE CLARIFY EQUIPMENT GROUNDING |
| METHOD BETWEEN FIRST MEANS OF |
| DISCONNECTAND PANEL(S). EQUIPMENT |
| GROUNDING |
| CONDUCTORS ARE TO BE SIZED BY 250-122. |
| ETC. ALL LOCATION |
| |
| 6)NOTE: PLEASE CLARIFY GROUND FOR |
| TRANSFORMER. |
| |
| 7)NOTE: PLEASE CLARIFY LOAD SHOWN FOR |
| PANEL "H" LOADS SHOWN ARE 1500W AND |
| 15000W FOR TRANSFORMER, THEN JUMPS TO |
| 90,000W IN LOAD CALC.??? |
| |
| |
| 8)NOTE: MEANS OF DISCONNECT CANNOT BE |
| IN ANOTHER PERSONS TENANT SPACE! PLEASE |
| CLARIFY THIS AS EXISTING BLGS ELEC ROOM. |
| |
| |
| |
| PLEASE SUBMIT ALL THE ABOVE INFOAMTION |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |