Plan Review Details - Permit 01030216
Plan Review Stops For Permit 01030216
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-03-07 Cont ID  
Sent By jwitmer Date 2001-03-07 Time 13:54 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-07 00:00:00PROVISO: SBC 803.3 (TABLE)
 THE INTERIOR FINISH CLASSIFICATION FOR
 SPRINKLERED BUILDINGS, BUSSSINESS
 OCCUPANCY IS"C".

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-04-10 Cont ID  
Sent By dpalmer Date 2001-04-10 Time 14:18 Rev Time 0.00
Received By dpalmer Date 2001-04-10 Time 14:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-06 Cont ID  
Sent By dpalmer Date 2001-03-06 Time 21:46 Rev Time 0.00
Received By dpalmer Date 2001-03-06 Time 21:46 Sent To  
Notes
2001-03-06 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE, SPACE MUST HAVE
 A 2 (TWO) HOUR FIRE WALL ALL THE TO
 ROOFLINE IF SPACE IS GOING TO BE A
 SEPARATE SERVICE. 230-2. IF THE SERVICE
 SHOWN IS THE SAME SERVICE FEEDING THE
 SAME BLDG THEN THIS WOULD BE OK? PLEASE
 CLARIFY.
  
 2)NOTE: PLEASE NOTE, THAT PER F.A.C.
 553-79 6A 277/480V SERVICES MUST BE
 SIGNED AND SEALED BY AN P.E.
  
 3)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS ARE TO FIG AND SHOWN AT 125%
 PER 215-2,3
  
 4)NOTE: PLEASE PROVIDE CLARIFICATION ON
 THE INSTALLATION OF TRANSFORMER PER
 450-13B.
  
 5) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF
 DISCONNECTAND PANEL(S). EQUIPMENT
 GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
 ETC. ALL LOCATION
  
 6)NOTE: PLEASE CLARIFY GROUND FOR
 TRANSFORMER.
  
 7)NOTE: PLEASE CLARIFY LOAD SHOWN FOR
 PANEL "H" LOADS SHOWN ARE 1500W AND
 15000W FOR TRANSFORMER, THEN JUMPS TO
 90,000W IN LOAD CALC.???
  
  
 8)NOTE: MEANS OF DISCONNECT CANNOT BE
 IN ANOTHER PERSONS TENANT SPACE! PLEASE
 CLARIFY THIS AS EXISTING BLGS ELEC ROOM.
  
  
  
 PLEASE SUBMIT ALL THE ABOVE INFOAMTION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-03-08 Cont ID  
Sent By mcarsill Date 2001-03-08 Time 15:00 Rev Time 0.00
Received By mcarsill Date 2001-03-08 Time 15:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-04-11 Cont ID  
Sent By pkrauss Date 2001-04-10 Time 16:45 Rev Time 0.30
Received By pkrauss Date 2001-04-11 Time 12:08 Sent To  
Notes
2001-04-10 00:00:00******************PROVISO***************
  
 PRIOR TO CONNECTING TO ANY EXISTING
 DUCTWORK CALL FOR AN INSPECTION.
  
 SUBMIT DETAILS WITH MECHANICAL PERMIT
 APPLICATION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-03-22 Cont ID  
Sent By ndenmark Date 2001-03-22 Time 14:05 Rev Time 0.25
Received By ndenmark Date 2001-03-22 Time 14:05 Sent To  
Notes
2001-03-22 00:00:00DENIED
 PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-03-29 Cont ID  
Sent By lsmith Date 2001-03-29 Time 14:23 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***