Plan Review Details - Permit 01030013
Plan Review Stops For Permit 01030013
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-03-05 Cont ID  
Sent By dpalmer Date 2001-03-05 Time 21:07 Rev Time 0.00
Received By dpalmer Date 2001-03-05 Time 21:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-03-05 Cont ID  
Sent By jleech Date 2001-03-05 Time 08:17 Rev Time 0.00
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-03-29 Cont ID  
Sent By jleech Date 2001-03-29 Time 07:17 Rev Time 0.50
Received By jleech Date 2001-03-29 Time 07:17 Sent To  
Notes
2001-03-29 00:00:00PROVISO;
  
 REVISED PLUMBING RISER REQUIRED.
 A. WASTE AND VENT STACKS ARE
 CROSSED.
 B. MECHANICAL VENT MUST HAVE AN
 ACCESS PANAL. PANAL WOULD BE IN
 TUB WALL.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-03-05 Cont ID  
Sent By jleech Date 2001-03-05 Time 08:17 Rev Time 0.25
Received By jleech Date 2001-03-05 Time 08:17 Sent To  
Notes
2001-03-05 00:00:00SUBMIT SANITARY RISER DIAGRAM TO SHOW
 PLUMBER HOW DRAINAGE PIPING SHOULD BE
 INSTALLED.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-04-10 Cont ID  
Sent By hpiskura Date 2001-04-10 Time 11:04 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-04-03 Cont ID  
Sent By rmcdouga Date 2001-04-03 Time 11:01 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-04-03 00:00:00DENIED
  
 1) SITE SPECIFIC ENGINEERING MAKES
 REFERENCE TO CURRENT SBCCI BUILDING CODE
 THIS IS NOT ACCEPTABLE. THE PRODUCT MUST
 CONFORM TO THE 1997 STANDARD BUILDING
 CODE OR THE 1999 SOUTH FLORIDA BUILDING
 CODE (LISTED ON THE FORM). PLEASE
 CORRECT.
  
 2) THE DESIGN PROFESSIONAL OF RECORD
 THAT SIGNED AND SEALED THE PRODUCT
 APPROVAL (SITE SPECIFIC) DID NOT SIGN
 AND SEAL THE PLANS, WHICH ARE SIGNED AND
 SEALED BY AN INTERIOR DESIGNER. AN
 EXTERIOR DOOR IS NOT WITHIN THE SCOPE OF
 AN INTERIOR DESIGNER AND REQUIRES
 WINDLOAD CERTIFICATION BY AN ARCHITECT
 OR ENGINEER. PLEASE HAVE PLANS SIGNED,
 SEALED AND DATED BY APPROPRIATE DESIGN
 PROFESSIONAL WITH TITLE BLOCK.
  
 3) PRODUCT APPROVAL FOR DOORS INDICATES
 NO IMPACT RESISTIBILITY. STORM PANELS OR
 SMALL MISSLE IMPACT RESISTANT GLASS IS
 REQUIRED AT 30 FT. OR MORE ABOVE GRADE.
 PLEASE CLARIFY HOW COMPLIANCE WILL BE
 ACHIEVED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-03-08 Cont ID  
Sent By rmcdouga Date 2001-03-08 Time 11:20 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-03-08 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) DRAWINGS ARE REQUIRED TO BE SIGNED,
 SEALED AND DATED BY A DESIGN
 PROFESSIONAL. CITY AMENDMENTS 104.2.3
  
 4) PROVIDE DRAWINGS/DETAILS INDICATING
 THAT ADEQUATE FIRE SPRINKLER COVERAGE
 WILL BE MAINTAINED.
  
 5) PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR:
 - NEW EXTERIOR SLIDE DOOR UNITS
  
 6) GUARDRAILS ARE REQUIRED AT EXTERIOR
 OF NEW DOOR UNITS. 97 SBC 1014.1.2
  
 7) ALL PARTITIONS SHALL BE CONSTRUCTED
 OF NON-COMBUSTIBLE MATERIALS.97 SBC 609.
 2.1
  
 8) PROVIDE ENERGY CALCULATIONS AS
 REQUIRED BY 101.2.2 OF THE FLORIDA
 ENERGY CODE.
  
 9) PROVIDE WALL SECTION OF EXTERIOR WALL
 THAT IS BEING ENCLOSED INTO CONDITIONED
 SPACE. INDICATE INSULATION, FURRING,
 WALL COVERING, ETC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202