Plan Review Details - Permit 01021024
Plan Review Stops For Permit 01021024
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-08-01 Cont ID  
Sent By hpiskura Date 2001-08-01 Time 13:55 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-08-01 00:00:00PROVISO:IMPACT FEES MUST BE PAID TO
 THE COUNTY

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-06-18 Cont ID  
Sent By hpiskura Date 2001-06-18 Time 09:23 Rev Time 0.00
Received By hpiskura Date 2001-06-13 Time 10:25 Sent To  
Notes
2001-06-18 00:00:00SHEET H8.4SMOKE CONTROL SEQUENCEDOES
 NOT APPEAR TO ADDRESS THE REQUIEMENTS
 OF SBC 414.8 FOR OTHER OCCUPIED SPACES
 SUCH AS THE VARIOUS GALLERIES ON ALL
 THREE FLOORS.
  
 WILL THE ATRIUM BEUNDER POSITIVE OR
 NEGATIVE PRESSURE DURING SMOKE REMOVAL
 OPERATIONS?HAS THE EFFECT ON
 OPERATION OF THE TWO STAIR SHAFT DOORS
 BEEN ANALYZED UNDERBOTH
 +/- PRESSURES.
  
  
  
 PROVIDE ACCEPTANCE REPPORTS AND TEST
 DATA FOR THE DOORS WINDOWS AND ROOF
 COVERINGS.INCLUDE METHOD OF HURRICANE
 MISSILEIMPACT RESISTANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-03-19 Cont ID  
Sent By hpiskura Date 2001-03-19 Time 09:19 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-03-19 00:00:00A COMPLETE PLAN PREVIEW FOR CODE
 COMPLIANCE WAS NOT POSSIBLE SINCE THE
 PLANS AND SPECIFICATIONS AND PROVIDED
 ARE INCOMPLETE.
  
 THE CODE PLAN SHEET CD1.1 APPEARS TO USE
 THE NOMINAL WIDTHS OF THE EGRESS DOORS
 AND OPENINGS.SBC 1003.2 REQUIRES THE
 CLEAR WIDTH TO BE USED.
  
 SHEET A1.2.WHERE WILL THE NEW STAIR #
 4 DISCHARGE?
  
 THE OVAL STAIR REQUIRES AN ENCLOSURE
 SINCE IT PENETRATES MORE THAN 2
 STORIES.SEE SBC 705.2.2.H3 IMPLIES
 AN ATRIUM.IF SO PROVIDE ALL
 INFORMATION AND CALCULATIONS AT TIME OF
 PERMIT.SEE SBC 414.1.
  
 SHEET A1.4.THE ROOF AND OVERFLOW
 DRAINS MUSTBE SIZED TO THE 1994
 STANDARD PLUMBING CODE.
  
 SHEET A2.1A.DETAILS FOR THE ATTACHMENT
 OF THE WOOD CEILING WILL BE NECESSARY.
  
 A3.1.SPECIFIC CONNECTION DETAILS WILL
 BE REQUIRED FOR THE CAST STONE AND THE
 "COMPONENT" PANELS.
  
 THIS IS A THRESHOLD BUILDING AND WILL
 REQUIRE A THRESHOLD INSPECTOR AND
 INSPECTION PLAN.SEE FS 553.71.
  
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY.CALL 561-233-5025 FOR MORE
 INFORMATION.
  
 PRODUCT APPROVALS AND TEST REPORTS ARE
 REQUIRED FOR THE WINDOWS, ROOF
 COVERINGS AND THE HURRICANE MISSILE
 IMPACT PROTECTION SYSTEM.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2002-10-08 Cont ID  
Sent By btrobaug Date 2002-11-01 Time 14:20 Rev Time 0.30
Received By btrobaug Date 2002-10-08 Time 15:52 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2002-06-20 Cont ID  
Sent By dpalmer Date 2002-06-20 Time 15:27 Rev Time 0.00
Received By dpalmer Date 2002-06-20 Time 06:50 Sent To  
Notes
2002-06-20 00:00:00REV OK, SOME SHEETS SUBMITTED DID NOT
 HAVE ANY REV NOTED.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2002-04-16 Cont ID  
Sent By dpalmer Date 2002-04-16 Time 06:46 Rev Time 0.00
Received By dpalmer Date 2002-04-16 Time 06:45 Sent To  
Notes
2002-04-16 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT EACH PAGE IS
 NOTED THAT THERE ARE MISC ELECTRICAL
 REVISIONS? PLEASE NOTE THAT THERE ARE
 NO CLOUDS AND/OR TRIANGLES TO SHOW
 CHANGES. PLEASE LABEL REVISIONS BY
 CLOUDS AND/TRIANGLES.
 PLEASE NOTE THAT BY OVER LOOKING
 SERVICE RISER THERE ARE SOME CHANGES
 MADE DO NOT SEEM TO CORRELATE
 WITH ORIG REVIEW COMMENTS AND OR PLANS??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2001-09-18 Cont ID  
Sent By dpalmer Date 2001-09-18 Time 19:48 Rev Time 0.00
Received By dpalmer Date 2001-09-18 Time 19:48 Sent To  
Notes
2001-09-18 00:00:00************ PLEASE NOTE***************
  
 1)NOTE: PLEASE NOTE THAT REVISION FOR
 SKETCHES PRI-E1 AND PRI-E2 ARE OK.
  
 2)NOTE: PLEASE NOTE THAT AS PER THE
 WEITZ CO. REQUEST, SECURITY PLANS WERE
 NOT ORIGINALLY SIGNED AND SEALED AND
 WERE ASKED TO BE REMOVED FROM MAIN PLANS
 AND TO BE SUBMITTED UNDER SEPARATE
 PERMIT IN ORDER TO ISSUE MAIN.
  
 PLEASE SUBMIT PLANS FOR LOW VOLTAGE
 PERMIT AND SUBMIT NEW PERMIT APPLICATION
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE NAY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-08-21 Cont ID  
Sent By dpalmer Date 2001-08-21 Time 09:43 Rev Time 0.00
Received By dpalmer Date 2001-08-21 Time 09:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-08-10 Cont ID  
Sent By dpalmer Date 2001-08-10 Time 13:14 Rev Time 0.00
Received By dpalmer Date 2001-08-10 Time 13:14 Sent To  
Notes
2001-08-10 00:00:00************UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT LETTER FROM
 ENGINEER MENTIONS NEW PLANS FOR E4-1
 WAS SUBMITTED?? WENT THROUGH ALL PLANS
 W/ CONTRACTOR OUT FRONT AND NOTHING?
 PLEASE ALSO NOTE THAT LV/SEC PLANS WERE
 NOT SIGNED AND SEALED? PER FS/FAC .
 BOTH PER PREVIOUS COMMENTS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-06-08 Cont ID  
Sent By dpalmer Date 2001-06-08 Time 07:30 Rev Time 0.00
Received By dpalmer Date 2001-06-07 Time 21:05 Sent To  
Notes
2001-06-08 00:00:00**************** UNSAT ***************
  
 1)NOTE:PLEASE NOTE IN REFERENCE TO
 THE SHUNT TRIP BEING SHOWN FOR MAIN
 BUILDING POWER SHUT OFF.
 PLEASE SEE 230-72,230-76,230-79
 THE GROUPING OF DISCONNECTING SERVICES
 NEEDS TO BE IN SAME AREAS.
  
 2)NOTE: PLEASE SEE E4-1 DISTRIBUTION
 LOAD SUNMMARY IS BLANK? PLEASE CLARIFY.
  
 3)NOTE: PLEASE NOTE THAT UNDER F.S.
 AND'F.A.C 471.025 AND 481.221, ALL
 PLANSDONE BY ARCHS/ENGINEERS NEED TO BE
 SIGNED, SEALED AND DATED.
  
 3)NOTE: PLEASE NOTE THAT PLANS ARE IN
 VERY GOOD SHAPE. IT HAS BEEN ACCEPTED TH
 AT A SHUNT MEANS FOR"SHUTTING DOWN"
 EMERGENCY GENERATORS IS OK AS LONG A
 MANUAL MEANS OF DISCONNECT IS ALSO
 THERE ON THE EQUIPMENT. 230-76 AND -79.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-07 Cont ID  
Sent By dpalmer Date 2001-03-07 Time 18:47 Rev Time 3.00
Received By dpalmer Date 2001-03-07 Time 18:47 Sent To  
Notes
2001-03-07 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE TO
 BESIGNED AND SEALED PER F.A.C 471.025/
 61G15-23.002. BY AN ENGINEER.
  
 2)NOTE: PLEASE SEE 230-95 FOR GFI
 PROTECTION OF SERVICE.
  
 3)NOTE: PLEASE CLARIFY MEANS OF
 DISCONNECT FOR GENERATOR, GROUPED WITH
 MAIN PER 230-72 AND REQ`MENTS FOR DISC
 PER 230-76 AND 230-79.
  
 4)NOTE: PLEASE SHOW ALL CONDUIT/WIRE
 SIZES ON LINE DIAGRAM.
  
 5)NOTE: PLEASE SUBMIT COMPLETE PANEL
 SCHEDULES AND PLANS FOR SERVICE.
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 7)NOTE: PLEASE SUBMIT COMPLETED LOAD
 CALCULATIONS ECT EQUIPMENT LOADS ETC
 ETC ETC,,,,
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2001-07-17 Cont ID  
Sent By mamini Date 2001-07-17 Time 14:07 Rev Time 1.00
Received By mamini Date 2001-07-17 Time 14:06 Sent To  
Notes
2001-07-17 00:00:00PASSED :
 1. APPROVED, SEE PERMIT # 01040393
  
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2001-05-18 Cont ID  
Sent By mamini Date 2001-05-18 Time 09:15 Rev Time 3.00
Received By mamini Date 2001-05-18 Time 08:46 Sent To  
Notes
2001-05-18 00:00:00FAILED:
 1. PLEASE REFER TO PREVIOUS REVIEW
 COMMENTS DATED 03-05-01
 2. POLLUTION PREVENTION NOTE DETAILS
 SHOULD BE ADDED TO PLANS.PLANS SHOULD
 INCLUDE PROTECTION OF ALL EXISTING CATCH
 BASIN AND PREVENTION OF TRACKING
 CONSTRUCTION DEBRIES AND DUST INTO THE
 PUBLIC R.O.W DURING CONSTRUCTION.THIS
 PLANS SHOULD BE KEPT ON SITE DURING
 CONSTRUCTION.
 3. ALL BROKEN SIDEWALK, CURBS(& GUTTERS)
 ALONG THE THE PROPERTY ALL SIDES SHOULD
 BE REPLACED.
 4. ALL DRIVEWAY THAT WILL NOT BE USED
 MUST BE REMOVED AND REPLACED WITH
 REGULAR CURBS (& GUTTERS).

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-03-05 Cont ID  
Sent By mamini Date 2001-03-05 Time 16:12 Rev Time 2.00
Received By mamini Date 2001-03-05 Time 08:16 Sent To  
Notes
2001-03-02 00:00:00FAILED:
 1. ANY WORK PERFORMED IN CITY R.O.W AN
 "APPLICATION FOR CONSTRUCTION WITHIN
 PUBLIC RIGHT-OF-WAY" MUST BE SUBMITTED
 TO CITY ENGINEER'S OFFICE.ALSO SUBMIT
 SHOP DRAWING ON ALL MATERIALS TO PUBLIC
 UTILITIES ENGINEERING SERVICES
 DEPARTMENT 1000 45TH STREET WPB, FL
 33407
 2. ALL DRIVEWAY APPROACHES MUST BE
 CONSTRUCTED PER CITY OF WEST PALM BEACH
 STANDARD.SEE ATTACHED
 3. INLET AT 2ND DRIVEWAY GOING NORTH
 MAY REQUIRE ADJUSMENT(TOP ELEVATION),
 PLEASE VERIFY.
 4. PLEASE RELOCATE THE EXISTING LIGHT
 POLE AT DRIVEWAY ENTERING THE DROP-OFF
 5. PLEASE SHOW THE LOCATION OF CLEAN
 OUTS FOR SANITARY SEWER LATERAL, ON
 PROPERTY.
 6. PROVIDE CALCULATION FOR PERVIOUS AND
 IMPERVIUS AREA CALCULATIONS ON A 8 1/2 X
 11 SHEET SIGNED AND SEALED BY THE DESIGN
 ENGINEER DUE TO THE CHANGES.PLEASE
 INCLUDE NAME OF THE PROPERTY, ADDRESS,
 PROPERTY CONTROL NUMBER.THIS CAN BE
 DONE WITH PERMIT APPLICATION.
 7. PLEASE SHOW THE NEW LOCATION OF
 DUMPSTER.PLEASE NOTE THAT THE NEW
 LOCATION SHOULD BE ACCESSIBLE AND SHOULD
 BE CONSTRUCTED PER CITY OF WEST PALM
 BEACH STANDARD. SEE ATTACHED STANDARD
 8. NOTE # 5 ON SHEET C-2 SHOWS S-III
 ASPHALTIC CONCRETE, DETAILS SHOWS S-I,
 PLEASE VERIFY
 9. DETAILS ON SHEET C-2 FOR PERFORATED
 PIPE TRENCH SHOWS 24" COVER, IT SHOULD
 36" FOR UNDER TRAFFIC, PLEASE VERIFY.
 10. NOTE TO LANDSCAPE ARCHITECT, PLEASE
 COMPLY WITH VISIBILITY TRIANGLE AT
 CORNER OF DIXIE AND CRANEST WAY AND
 PROVIDE 8' SIGHT LINE
 11. NOTE TO LANDSCAPE ARCHITECT, PLEASE
 PROVIDE LANDSCAPING IN FRONT OF NEW
 BACKFLOW PREVENTERS.
 IF ANY QUSETION PLEASE CONTACT 659-8096
 EXT. 8492

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status F Date 2002-09-26 Cont ID  
Sent By mcarsill Date 2002-09-26 Time 17:00 Rev Time 0.00
Received By mcarsill Date 2002-09-26 Time 17:00 Sent To  
Notes
2002-09-26 00:00:00PLEASE ARRANGE A MEETING WITH THIS
 OFFICE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status F Date 2002-05-02 Cont ID  
Sent By mcarsill Date 2002-05-02 Time 14:35 Rev Time 0.00
Received By mcarsill Date 2002-05-02 Time 14:35 Sent To  
Notes
2002-05-02 00:00:00PLEASE IDENTIFY CHANGES BY EITHER
 CLOUDS OR TRIANGLES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2001-09-12 Cont ID  
Sent By mcarsill Date 2001-09-12 Time 11:58 Rev Time 0.00
Received By mcarsill Date 2001-09-12 Time 11:58 Sent To  
Notes
2001-09-12 00:00:001) SECURITY FEAUTURES WHEN INSTALLED
 ARE TO MEET THE REQUIREMENTS OF
 " SPECIAL LOCKING ARRANGEMENTS" PER
 THE LIFE SAFETY CODE, 1985 EDITION,
 SECTION 5-2.1.6. THIS CODE REQUIRES
 THE UNLOCKING OF DOORS "UPON ACTUATION
 OF AN APPROVED SUPERVISED AUTOMATIC
 FIRE DETECTION SYSTEM OR APPROVED
 SUPERVISED AUTOMATIC FIRE SPRINKLER
 SYSTEM
 UNLOCK UPON LOSS OF POWER CONTROLLING
 THE LOCK OR LOCKING MECHANISM AND
 INITIATE AN IRREVERSIBLE PROCESS WHICH
 WILL RELEASE THE LOCK WITHIN 15
 SECONDS WHENEVER A FORCE OF NOT MORE
 THAN 15 LBS. IS CONTINOUSLY APPLIED.
 OPERATION OF THE DOOR SHALL ACTIVATE A
 SIGNAL IN THE VICINITY OF THE DOOR".
 ALSO A "SIGN SHALL BE PROVIDED ON THE
 DOOR ADJACENT TO THE RELEASE DEVICE
 WHICH READS PUSH UNTIL ALARM SOUNDS.
 DOOR CAN BE OPENED IN 15 SECONDS".
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-08-17 Cont ID  
Sent By mcarsill Date 2001-08-17 Time 12:39 Rev Time 0.00
Received By mcarsill Date 2001-08-17 Time 12:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-08-09 Cont ID  
Sent By mcarsill Date 2001-08-09 Time 13:46 Rev Time 0.00
Received By mcarsill Date 2001-08-09 Time 13:46 Sent To  
Notes
2001-08-09 00:00:00CALLED AND SPOKE TO ARCHITECT ON 8/9/01
 WRITTEN PLAN REVIEW COMMENTS ARE TO
 BE SUBMITTED.
  
 MIKE CARSILLO
 659-8096, EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-05-16 Cont ID  
Sent By mcarsill Date 2001-05-16 Time 10:16 Rev Time 0.00
Received By mcarsill Date 2001-05-16 Time 10:16 Sent To  
Notes
2001-05-16 00:00:00MANY OF THE PREVIOUS PLAN REVIEW
 COMMENTS MADE ON 3/01/01 HAVE NOT
 BEEN ADDRESSED. PLEASE PROVIDE WRITTEN
 COMMENTS TO THIS OFFICE ADDRESSING ALL
 PREVIOUS PLAN REVIEW COMMENTS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-03-01 Cont ID  
Sent By mcarsill Date 2001-03-01 Time 11:36 Rev Time 0.00
Received By mcarsill Date 2001-03-01 Time 11:36 Sent To  
Notes
2001-03-01 00:00:001) PLEASE INDICATE PROPOSED FIRE RESCUE
 INGRESS AND EGRESS POINTS TO THE NEW
 ADDITION.
 2) PLEASE LOCATE EXISTING FIRE HYDRANT
 LOCATIONS FOR MUSEUM.
 3) PLEASE PROVIDE MORE DETAILS ON GATES
 LOCATED NEAR SOUTH DIXIE FOR DROP OFF
 LANE.
 4) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 5) MAXIMUM TRAVEL DISTANCE NOTE ON CD1.1
 IS INCORRECT. MAXIMUM TRAVEL DISTANCE
 IN SPRINKLERED BUILDINGS OF THIS TYPE IS
 200 FEET.
 6) PLEASE FURTHER CLARIFY CD1.1. EXIT
 SIGNS AND DOORS MUST BE SHOWN. PLAN WAS
 DIFFICULT TO FOLLOW.
 7) PLEASE ADVISE HOW DEMOLITION WILL
 OCCUR WHEN THE MUSEUM IS OPEN.
 8) PLEASE PROVIDE PRODUCT APPROVAL FOR
 ONE HOUR FIRE RATED GLAZING IN CORRIDOR
 101.
 9) PLEASE INDICATE HOW ILLUMINATED
 EXIT SIGNS WILL BE INSTALLED IN OFFICES
 230 DUE TO HEADROOM ISSUES.
 10) PLEASE PROVIDE MORE DETAILS ON
 EMERGENCY GENERATOR 227.
 11) PLEASE ADVISE WHAT THE OPEN SHAFT
 SPACE IS FOR ON PAGE A2.2.
 12) PLEASE INDICATE COMPLIANCE WITH
 ATRIUM REQUIREMENTS IN THE LIFE SAFETY
 CODE. THE DESIGN OF THE ATRIUM IS TO BE
 DONE BY A LICENSED ENGINEER AND THE
 PLANS ARE TO BE SIGNED AND SEALED.
 PLEASE PROVIDE TESTING REQUIREMENTS AND
 EQUIPMENT THAT WILL BE NEEDED TO TEST
 THE ATRIUM SMOKE EXHAUST SYSTEM. PLEASE
 INDICATE WHAT THE FIREFIGHTERS ATRIUM
 OVERRIDE PANEL WILL LOOK LIKE. ALSO
 PLEASE INDICATE THE NUMBER OF REQUIRED
 AIR CHANGES THAT ARE REQUIRED.
 13) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION.
 14) ELEVATORS TO COMPLY WITH ANSI A17.1.
 PHASE ONE AND PHASE TWO ELEVATOR RECALL
 WILL BE REQUIRED.
 15) ALL STAIRS TO COMPLY WITH NEW STAIRS
 NFPA 101, THE LIFE SAFETY CODE, 1985
 EDITION.
 16) PLEASE INDICATE WHAT THE RAISED
 PLATFORM ON THE NORTH INTERIOR
 ELEVATION WILL BE USED FOR.
 17) NATURAL GAS INSTALLATION TO COMPLY
 WITH NFPA 54.
 18) FIRE SPRINKLER DRAWINGS NOT SIGNED
 AND SEALED. NO HYDRAULIC CALCULATIONS
 PROVIDED WITH PLANS. PLEASE PROVIDE
 MORE DETAILS ON PRE-ACTION SPRINKLER
 SYSTEM.
 19) PLEASE PROVIDE MORE DETAILS FOR THE
 TEMPORARY RELOCATION OF THE FIRE PUMP
 AND FIRE MAIN. IF APPROVED BY THIS
 OFFICE, WHEN DOES THIS ACTIVITY OCCUR.
 20) THE CHILLER ROOM IS TO BE EQUIPPED
 WITH APPROPRIATE SIGNAGE, ALARMS, AND
 HAVE SELF-CONTAINED BREATHING APPARATUS
 SINCE REFRIGERATOR LEAK DETECTION IS
 NOTED ON THE PLANS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-01 Cont ID  
Sent By btrobaug Date 2002-11-01 Time 14:19 Rev Time 0.00
Received By btrobaug Date 2002-11-01 Time 14:19 Sent To E
Notes
2002-11-01 00:00:00TO DVP./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2002-06-13 Cont ID  
Sent By pkrauss Date 2002-06-13 Time 15:43 Rev Time 2.00
Received By pkrauss Date 2002-06-13 Time 15:31 Sent To  
Notes
2002-06-13 00:00:00DUCT REVISIONS

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2002-04-16 Cont ID  
Sent By pkrauss Date 2002-04-08 Time 16:55 Rev Time 0.45
Received By pkrauss Date 2002-04-08 Time 15:32 Sent To  
Notes
2002-04-08 00:00:00 
  
 PLEASEDESIGNATE REIVISIONS TO HELP
 EXPEDITE PLAN REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-09-25 Cont ID  
Sent By pkrauss Date 2001-09-25 Time 10:02 Rev Time 0.45
Received By pkrauss Date 2001-09-25 Time 10:02 Sent To  
Notes
2001-09-25 00:00:00PROVISO ON PLAN.PHK

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-08-08 Cont ID  
Sent By pkrauss Date 2001-08-08 Time 10:59 Rev Time 3.00
Received By pkrauss Date 2001-08-08 Time 09:00 Sent To  
Notes
2001-08-08 00:00:00******************PROVISO***************
  
  
 REVISIONS FOR "CHILLER ROOM" WERE NOT A
 PART OF THIS REVIEW.ALL CHILLER ROOM
 REVISIONS NEED TO BE SUBMITTED WITH
 PERMIT NUMBER 01040393.
  
 NOTE:CONDENSATE SHALL BE INDICATED ON
 PLANS AND SHALL COMPLY WITH THE
 AMENDED 1994 SPC 804.3.RTU 1
 ON PLAN SHEET H1.2A,SHALL NOT
 "SPILL ON ROOF".FAN COIL UNITS
 SHALL NOT GO INTO "SANITARY
 PIPING".PLEASE SUBMIT
 CONDENSATE FOR REVIEW.
  
 **** CONDENSATE NEEDS TO BE ADDRESSED
 PRIOR TO MECHANICAL PERMIT BEING
 ISSUED.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-06-06 Cont ID  
Sent By pkrauss Date 2001-06-06 Time 10:08 Rev Time 3.00
Received By pkrauss Date 2001-06-06 Time 08:57 Sent To  
Notes
2001-06-06 00:00:00*******************DENIED***************
  
 1.PLEASE PROVIDE O. A. CALCULATIONS
 AS PER ASHRAE 62-89.
  
 2.PROVIDE AIR BALANCE SCHEDULE FOR
 COMPLIANCE WITH 1997 SMC 501.2.
  
 3.PROVIDE INFORMATION SHOWING
 COMPLIANCE WITH 1997 SMC CHAPTER
 11, LEVEL 1 MACHINE ROOM, I.E.
 SIGNAGE, LOCATION OF HORN & STROBES
 (OUTSIDE & INSIDE ROOM), LOCATION
 OF REFRIGERANT SENSORS & BREATHING
 APPARATUS.
  
 4.DRAWING H1.3 "REFER TO MATCH LINE
 H1.4A", NO SUCH DRAWING WITH THIS
 SET OF PLANS.
  
 5.DUCT SMOKE DETECTORS NEED TO BE
 INDICATED ON PLAN.
  
 6.ADDITIONAL MECH PERMIT & PLANS
 REQUIRED FOR FUEL (PIPING & TANK).
  
 7.ADDITIONAL MECH PERMIT & PLANS
 REQUIRED FOR KITCHEN HOOD &
 DUCTWORK.
  
 NOTE:PRIOR TO CONNECTING TO ANY
 EXISTING DUCTWORK, CALL FOR AN
 INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-03-22 Cont ID  
Sent By pkrauss Date 2001-03-22 Time 10:29 Rev Time 3.00
Received By pkrauss Date 2001-03-21 Time 12:47 Sent To  
Notes
2001-03-22 00:00:00******************DENIED****************
  
 1.PROVIDE OUTSIDE AIR SCHEDULE PER
 ASHRAE 62-89.
 2.PROVIDE AIR BALANCE SHOWING COMPLIANCE
 WITH 1997 SMC 501.2.
  
 3.SPECIFIC LOCATION AND INSTALLATION
 DETAILS ARE REQUIRED FOR FIRE AND OR
 SMOKE DAMPERS AS PER 1997 SMC 610.6.
 ALSO ACCESS TO MAINTAIN AND RESETTING
 OF FIRE DAMPER,1997 SMC 610.5.
  
 4.PROVIDE ELEVATION AND SHAFT DETAIL FOR
 DUCTS PENETRATING FLOORS, 1997 SMC
 610.4.
  
 5.CLARIFY THE FOLLOWING EXHAUST FANS &
 DUCTWORK FOR:
  
 ROOM 304 - 3RD FLOOR MENS RESTROOM
 ROOM 205 - 2ND FLOOR CUST.
 ROOM 204 - 2ND FLOOR MENS RESTROOM
 ROOM 208 - 2ND FLOOR WOMENS RESTROOM
  
 6.CLARIFY FUNCTION OF AHU 5, PLANS
 INDICATE SERVICING KITCHEN AND WOMENS
 RESTROOM (RM. 119), WHEREAS THE AHU
 SCHEDULE INDICATES AHU 5 SERVES
 CLASSROOMS.
  
 7.PROVIDE CFM INFORMATION FOR 3RD FLOOR.
  
 8.PROVIDE DETAIL OF 2ND FLOOR MECHANICAL
 ROOM - PLAN ELEVATION, CLEARANCE FOR
 SERVICEABILITY AS PER 1997 SMC 304.2.3
 ALSO, PROVIDE LOCATION OF AHU 7.
 SCHEDULE INDICATES IT IS LOCATED IN
 MECHANICAL ROOM, 2ND FLOOR.
  
 9.AHU 6 SERVES CAFE, IS THIS AN EXISTING
 SPACE? PLEASE PROVIDE MORE INFORMATION
  
 10.PROVIDE MORE INFORMATION OF KITCHEN
 HOOD - MAKE UP AIR AND EXHAUST TO
 SHOW COMPLIANCE WITH 1997 SMC 504.
  
  
  
  
 11.DRAWING H-7 SHOWS GREASE DUCT
 PENETRATING THE WALL BETWEEN THE
 KITCHEN TO THE BOILER ROOM, IS THIS
 WALL RATED?
  
 12.PLEASE PROVIDE A CLEAR DETAIL OF ROOF
 TERMINATION OF BOTH FLUE AND EXHAUST
 OUTLET.
  
 13.PROVIDE INFORMATION SHOWING C
 COMPLIANCE WITH SMC CHAPTER 11,
 LEVEL 1 MACHINE ROOM, I.E. SIGNAGE,
 VENTILATION CALCULATIONS (EMERGENCY
 & NORMAL), LOCATION OF HORN & STROBES
 (OUTSIDE & INSIDE ROOM), LOCATION OF
 REFRIGERANT SENSORS AND BREATHING
 APPARATUS.

Review Stop P PLUMBING
Rev No 9 Status P Date 2002-10-29 Cont ID  
Sent By kstevens Date 2002-10-29 Time 14:05 Rev Time 1.50
Received By kstevens Date 2002-10-29 Time 14:05 Sent To  
Notes
2002-10-29 00:00:00REVISION OK - SHTS P1.2A, P4.1, P4.2,
 P4.4, & P4.5

Review Stop P PLUMBING
Rev No 8 Status P Date 2002-10-18 Cont ID  
Sent By kstevens Date 2002-10-18 Time 11:40 Rev Time 0.50
Received By kstevens Date 2002-10-18 Time 11:40 Sent To  
Notes
2002-10-18 00:00:00REVISION OK - REROUTE U/G RW LINES TO
 PLANTER DRAINS & POOL DRAIN.

Review Stop P PLUMBING
Rev No 7 Status P Date 2002-07-12 Cont ID  
Sent By btrobaug Date 2002-10-08 Time 16:11 Rev Time 0.00
Received By kstevens Date 2002-07-12 Time 17:39 Sent To  
Notes
2002-07-12 00:00:00REVISION OK - GAS RISER DIAGRAM

Review Stop P PLUMBING
Rev No 6 Status F Date 2002-07-08 Cont ID  
Sent By kstevens Date 2002-07-08 Time 12:27 Rev Time 0.00
Received By kstevens Date 2002-07-08 Time 12:27 Sent To  
Notes
2002-07-08 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SGC-97
  
 1) SHT P4.2 3" PLANTER DRAIN SHOWN ON
 FLAT DRAWING P1.0 MISSING FROM STORM
 RISER DIAGRAM.
 2) SHT P1.2A REVISION SHOWS NO PIPING TO
 ROOF DRAINS, 1 NEW 4" RD-A, 2" SCUPPER
 DRAINS COL. LINE X15, 3" & 4" SCUPPER
 DRAINS COL. LINE BELOW X26. PLEASE
 CLAIRFY. ARE ORIGINAL ROOF DRAINS STILL
 BEING USED? ARE SCUPPERS SECONDARY
 DRAINS? IF SO THEY CAN NOT TIE INTO
 PRIMARY DRAIN SYSTEM. NO SECONDARY DRAIN
 SHOWN FOR LOWER ROOF TO THE LEFT SIDE.
 3) PLEASE INDICATE WHERE ALL SECONDARY
 ROOF DRAINS DRAIN TO.
 4) SHT P4.1 GREASE INTERCEPTOR DETAIL,
 2 WAY CLEAN OUTS ARE REQUIRED FOR INLET
 & OUTLET SIDES OF GREASE INTERCEPTOR.
 5) SHT P4.2 RAINWATER RISER DIAGRAM, THE
 AREA IN QUESTION ON COMMENT #2, (SHT P1.
 2), IS NOT SHOWN ON RAINWATER RISER DIA-
 GRAM. PLEASE INDICATE WHERE THIS IS LO-
 CATED ON RISER DIAGRAM.
 6) SHT P4.4 FUNNEL FLOOR DRAINS ARE NOT
 APPROVED. ALL INDIRECT WASTE SHALL DRAIN
 INTO A FLOOR SINK. PLEASE DELETE AND
 SHOW FLOOR SINKS.
 7) SHT P4.5 SANT RISER DIAGRAM. PLEASE
 SHOW FIXTURE UNITS DRAINING IN SYSTEM.
 SHOW TOTAL AMOUNT AND SHOW DFU'S AS THEY
 ACCUMULATE IN SYSTEM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 5 Status F Date 2002-05-01 Cont ID  
Sent By kstevens Date 2002-05-01 Time 13:35 Rev Time 0.00
Received By kstevens Date 2002-05-01 Time 13:35 Sent To  
Notes
2002-05-01 00:00:00DENIED
  
 REVIEW NOTES: *****UNSET***********
  
 1) EACH SHEET NOTED THAT THERE ARE MISC.
 REVISIONS. THERE ARE NO CLOUDS OR TRI-
 ANGLES TO DENOTE WHERE CHANGES ARE LO-
 CATED. PLEASE LABLE REVISIONS WITH A
 CLOUD AND TRIANGLES DATEING CHANGES.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-11-16 Cont ID  
Sent By kstevens Date 2001-11-16 Time 20:42 Rev Time 0.50
Received By kstevens Date 2001-11-16 Time 20:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-08-21 Cont ID  
Sent By kstevens Date 2001-08-21 Time 09:51 Rev Time 0.00
Received By kstevens Date 2001-08-21 Time 09:51 Sent To  
Notes
2001-08-21 00:00:00PASSED PER PES
2001-07-27 00:00:00SEE ATTACHMENTS ON PLANS.PES

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-06-04 Cont ID  
Sent By pschmitz Date 2001-06-04 Time 14:16 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-06-04 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) PREVIOUS COMMENTS NOT ADDRESSED
 SHT A1.1, A1.8,DOOR SWINGS INTO CLEAR
 FLR SPACE OF LAV, RM # 305,SEC 4.17.5
 (2) SHT P1.0,P4.1 GREASE TRAP SIZE AND
 TYPE TO BE REVIEWED BY WPB,RSTP ENVIRO-
 MENTAL COMPLIANCE RODNEY COMPO 561-837-
 4074.WITH CUT SHTS FROM MFG.
 (3) SHT A6.13 ELEVATIONS,DIMENSIONS OF
 H/C PLUMBING FIXTURES INCLUDING URINALS,
 (4) SHT P1.1B CHILLER PLANT,REST RM #132
 SHOWER COMPARTMENT,TO COMPLY W/FACBC 97
 SEC 4.21, FIG. 35 A OR B.
 (5) SHT P3.1 PROVIDE A LIST OF KITCHEN
 EQUIPMENT FOR PLUMBING,GAS FIXTURES,
 SPC 94 SEC 104.3
 (6) SHT P4.1 DISHWASHER TO BY PASS G/W,
 CONNECT TO SANITARY SEWER, LOCAL ORD.
 #2938-96 WPB,RSTP.
 (7) SHT P4.1 PROVIDE A COMPLETE GAS
 ISOMETRIC,FROM THE METER TO THE FARTHEST
 POINT OF USE,INCLUDE BOILER & KITCHEN.
 SEE ATTACHED GAS PERMIT APPLICATION REQ-
 UIRMENTS,SGC 97 SEC 104.3 ADDRESS EACH
 OF NINE ITEMS.
 (8) SHT P4.2 SHOW CALCULATIONS FOR ROOF
 & SCUPPER DRAINS, INCLUDING VERTICAL
 WALLS,ALSO SECONDARY DRAINS FROM ABOVE
 DRAINING ON TO LOWER ROOFS.SPC 94
 SEC 1101.2,1108.3,1109.1
 (9) SHTP4.1 SPC 94 SEC 921.4 GEN. DESIGN
 HORIZONTAL WASTE & VENT SYSTEM, EACH F/S
 BRANCH TO CONNECT SEPERATELY TO MAIN
 VENTED LINE, MIN SIZE 3".
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096 X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-03-19 Cont ID  
Sent By jleech Date 2001-03-19 Time 16:05 Rev Time 3.00
Received By pschmitz Date 2001-03-19 Time 16:05 Sent To  
Notes
2001-03-19 00:00:00DENIED;
  
 1.A1.1 (119) WOMENS ROOM HANDICAP STALL.
 DOOR CANNOT SWING INTO CLEAR FLOOR
 SPACE OF LAV. ALSO ROOM (305)
  
 2.GREASE TRAP SIZE AND LOCATION TO BE
 APPROVED BY RODNEY COMPO OF THE UTILTY
 DEPARTMENT. 835-7423
  
 3.SHOW ARCHITECTURAL DRAWINGS OF
 HANDICAP STALLS AND HANDICAP URINALS
 SHOWING SIZES TO COMPLY WITH THE 97
 FACBC.
  
 4.RISER DIAGRAMS REQUIRED FOR WATER,
 SANITARY, RAIN WATER AND GAS.
  
 5.NEED ARCHITECTURAL DRAWING OF BOILERS.
 SHOW PIPE INSTALLATION.
  
 6.MORE INFOMATION REQUIRED FOR GAS;
 A.TYPE OF GAS.
 B.DELIVERY PRESSURE.
 C.TYPE OF PIPE AND HOW IT WILL BE
 INSTALLED.
 D.BTU LOAD FOR EACH APPLIANCE AND
 TOTAL BTU LOAD ON SYSTEM.
 E.DISTANCE TO MOST REMOTE OUTLET.
 F.CALCULATIONS FOR COMBUSTION AIR FOR
 BOILERS.
 G.SHOW GAS VENTS FOR BOILERS.
  
 7.SITE DRAWINGS DO NOT SHOW TIE IN FOR
 RAIN LEADERS.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-16 Cont ID  
Sent By sgraham Date 2001-05-16 Time 08:54 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-05-16 00:00:00ZONING REQUIREMENTS MUST BE APPROVED
 BEFORE SIGN OFF


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved