Plan Review Stops For Permit 01021024 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2001-08-01 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-08-01 |
Time |
13:55 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-08-01 00:00:00 | PROVISO:IMPACT FEES MUST BE PAID TO | | THE COUNTY |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2001-06-18 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-06-18 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2001-06-13 |
Time |
10:25 |
Sent To |
|
|
Notes |
2001-06-18 00:00:00 | SHEET H8.4SMOKE CONTROL SEQUENCEDOES | | NOT APPEAR TO ADDRESS THE REQUIEMENTS | | OF SBC 414.8 FOR OTHER OCCUPIED SPACES | | SUCH AS THE VARIOUS GALLERIES ON ALL | | THREE FLOORS. | | | | WILL THE ATRIUM BEUNDER POSITIVE OR | | NEGATIVE PRESSURE DURING SMOKE REMOVAL | | OPERATIONS?HAS THE EFFECT ON | | OPERATION OF THE TWO STAIR SHAFT DOORS | | BEEN ANALYZED UNDERBOTH | | +/- PRESSURES. | | | | | | | | PROVIDE ACCEPTANCE REPPORTS AND TEST | | DATA FOR THE DOORS WINDOWS AND ROOF | | COVERINGS.INCLUDE METHOD OF HURRICANE | | MISSILEIMPACT RESISTANCE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-03-19 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-03-19 |
Time |
09:19 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-03-19 00:00:00 | A COMPLETE PLAN PREVIEW FOR CODE | | COMPLIANCE WAS NOT POSSIBLE SINCE THE | | PLANS AND SPECIFICATIONS AND PROVIDED | | ARE INCOMPLETE. | | | | THE CODE PLAN SHEET CD1.1 APPEARS TO USE | | THE NOMINAL WIDTHS OF THE EGRESS DOORS | | AND OPENINGS.SBC 1003.2 REQUIRES THE | | CLEAR WIDTH TO BE USED. | | | | SHEET A1.2.WHERE WILL THE NEW STAIR # | | 4 DISCHARGE? | | | | THE OVAL STAIR REQUIRES AN ENCLOSURE | | SINCE IT PENETRATES MORE THAN 2 | | STORIES.SEE SBC 705.2.2.H3 IMPLIES | | AN ATRIUM.IF SO PROVIDE ALL | | INFORMATION AND CALCULATIONS AT TIME OF | | PERMIT.SEE SBC 414.1. | | | | SHEET A1.4.THE ROOF AND OVERFLOW | | DRAINS MUSTBE SIZED TO THE 1994 | | STANDARD PLUMBING CODE. | | | | SHEET A2.1A.DETAILS FOR THE ATTACHMENT | | OF THE WOOD CEILING WILL BE NECESSARY. | | | | A3.1.SPECIFIC CONNECTION DETAILS WILL | | BE REQUIRED FOR THE CAST STONE AND THE | | "COMPONENT" PANELS. | | | | THIS IS A THRESHOLD BUILDING AND WILL | | REQUIRE A THRESHOLD INSPECTOR AND | | INSPECTION PLAN.SEE FS 553.71. | | | | IMPACT FEES MUST BE PAID TO PALM BEACH | | COUNTY.CALL 561-233-5025 FOR MORE | | INFORMATION. | | | | PRODUCT APPROVALS AND TEST REPORTS ARE | | REQUIRED FOR THE WINDOWS, ROOF | | COVERINGS AND THE HURRICANE MISSILE | | IMPACT PROTECTION SYSTEM. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
8 |
Status |
P |
Date |
2002-10-08 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-11-01 |
Time |
14:20 |
Rev Time |
0.30 |
Received By |
btrobaug |
Date |
2002-10-08 |
Time |
15:52 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
P |
Date |
2002-06-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-06-20 |
Time |
15:27 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-06-20 |
Time |
06:50 |
Sent To |
|
|
Notes |
2002-06-20 00:00:00 | REV OK, SOME SHEETS SUBMITTED DID NOT | | HAVE ANY REV NOTED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
F |
Date |
2002-04-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-04-16 |
Time |
06:46 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-04-16 |
Time |
06:45 |
Sent To |
|
|
Notes |
2002-04-16 00:00:00 | **************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THAT EACH PAGE IS | | NOTED THAT THERE ARE MISC ELECTRICAL | | REVISIONS? PLEASE NOTE THAT THERE ARE | | NO CLOUDS AND/OR TRIANGLES TO SHOW | | CHANGES. PLEASE LABEL REVISIONS BY | | CLOUDS AND/TRIANGLES. | | PLEASE NOTE THAT BY OVER LOOKING | | SERVICE RISER THERE ARE SOME CHANGES | | MADE DO NOT SEEM TO CORRELATE | | WITH ORIG REVIEW COMMENTS AND OR PLANS?? | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
F |
Date |
2001-09-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-09-18 |
Time |
19:48 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-09-18 |
Time |
19:48 |
Sent To |
|
|
Notes |
2001-09-18 00:00:00 | ************ PLEASE NOTE*************** | | | | 1)NOTE: PLEASE NOTE THAT REVISION FOR | | SKETCHES PRI-E1 AND PRI-E2 ARE OK. | | | | 2)NOTE: PLEASE NOTE THAT AS PER THE | | WEITZ CO. REQUEST, SECURITY PLANS WERE | | NOT ORIGINALLY SIGNED AND SEALED AND | | WERE ASKED TO BE REMOVED FROM MAIN PLANS | | AND TO BE SUBMITTED UNDER SEPARATE | | PERMIT IN ORDER TO ISSUE MAIN. | | | | PLEASE SUBMIT PLANS FOR LOW VOLTAGE | | PERMIT AND SUBMIT NEW PERMIT APPLICATION | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | IF THERE ARE NAY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2001-08-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-08-21 |
Time |
09:43 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-08-21 |
Time |
09:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2001-08-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-08-10 |
Time |
13:14 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-08-10 |
Time |
13:14 |
Sent To |
|
|
Notes |
2001-08-10 00:00:00 | ************UNSAT *************** | | | | 1)NOTE: PLEASE NOTE THAT LETTER FROM | | ENGINEER MENTIONS NEW PLANS FOR E4-1 | | WAS SUBMITTED?? WENT THROUGH ALL PLANS | | W/ CONTRACTOR OUT FRONT AND NOTHING? | | PLEASE ALSO NOTE THAT LV/SEC PLANS WERE | | NOT SIGNED AND SEALED? PER FS/FAC . | | BOTH PER PREVIOUS COMMENTS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2001-06-08 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-06-08 |
Time |
07:30 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-06-07 |
Time |
21:05 |
Sent To |
|
|
Notes |
2001-06-08 00:00:00 | **************** UNSAT *************** | | | | 1)NOTE:PLEASE NOTE IN REFERENCE TO | | THE SHUNT TRIP BEING SHOWN FOR MAIN | | BUILDING POWER SHUT OFF. | | PLEASE SEE 230-72,230-76,230-79 | | THE GROUPING OF DISCONNECTING SERVICES | | NEEDS TO BE IN SAME AREAS. | | | | 2)NOTE: PLEASE SEE E4-1 DISTRIBUTION | | LOAD SUNMMARY IS BLANK? PLEASE CLARIFY. | | | | 3)NOTE: PLEASE NOTE THAT UNDER F.S. | | AND'F.A.C 471.025 AND 481.221, ALL | | PLANSDONE BY ARCHS/ENGINEERS NEED TO BE | | SIGNED, SEALED AND DATED. | | | | 3)NOTE: PLEASE NOTE THAT PLANS ARE IN | | VERY GOOD SHAPE. IT HAS BEEN ACCEPTED TH | | AT A SHUNT MEANS FOR"SHUTTING DOWN" | | EMERGENCY GENERATORS IS OK AS LONG A | | MANUAL MEANS OF DISCONNECT IS ALSO | | THERE ON THE EQUIPMENT. 230-76 AND -79. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-03-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-03-07 |
Time |
18:47 |
Rev Time |
3.00 |
Received By |
dpalmer |
Date |
2001-03-07 |
Time |
18:47 |
Sent To |
|
|
Notes |
2001-03-07 00:00:00 | *************** UNSAT ****************** | | | | 1)NOTE: PLEASE NOTE THAT PLANS ARE TO | | BESIGNED AND SEALED PER F.A.C 471.025/ | | 61G15-23.002. BY AN ENGINEER. | | | | 2)NOTE: PLEASE SEE 230-95 FOR GFI | | PROTECTION OF SERVICE. | | | | 3)NOTE: PLEASE CLARIFY MEANS OF | | DISCONNECT FOR GENERATOR, GROUPED WITH | | MAIN PER 230-72 AND REQ`MENTS FOR DISC | | PER 230-76 AND 230-79. | | | | 4)NOTE: PLEASE SHOW ALL CONDUIT/WIRE | | SIZES ON LINE DIAGRAM. | | | | 5)NOTE: PLEASE SUBMIT COMPLETE PANEL | | SCHEDULES AND PLANS FOR SERVICE. | | | | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 7)NOTE: PLEASE SUBMIT COMPLETED LOAD | | CALCULATIONS ECT EQUIPMENT LOADS ETC | | ETC ETC,,,, | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
3 |
Status |
P |
Date |
2001-07-17 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2001-07-17 |
Time |
14:07 |
Rev Time |
1.00 |
Received By |
mamini |
Date |
2001-07-17 |
Time |
14:06 |
Sent To |
|
|
Notes |
2001-07-17 00:00:00 | PASSED : | | 1. APPROVED, SEE PERMIT # 01040393 | | | | IF ANY QUESTION PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
F |
Date |
2001-05-18 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2001-05-18 |
Time |
09:15 |
Rev Time |
3.00 |
Received By |
mamini |
Date |
2001-05-18 |
Time |
08:46 |
Sent To |
|
|
Notes |
2001-05-18 00:00:00 | FAILED: | | 1. PLEASE REFER TO PREVIOUS REVIEW | | COMMENTS DATED 03-05-01 | | 2. POLLUTION PREVENTION NOTE DETAILS | | SHOULD BE ADDED TO PLANS.PLANS SHOULD | | INCLUDE PROTECTION OF ALL EXISTING CATCH | | BASIN AND PREVENTION OF TRACKING | | CONSTRUCTION DEBRIES AND DUST INTO THE | | PUBLIC R.O.W DURING CONSTRUCTION.THIS | | PLANS SHOULD BE KEPT ON SITE DURING | | CONSTRUCTION. | | 3. ALL BROKEN SIDEWALK, CURBS(& GUTTERS) | | ALONG THE THE PROPERTY ALL SIDES SHOULD | | BE REPLACED. | | 4. ALL DRIVEWAY THAT WILL NOT BE USED | | MUST BE REMOVED AND REPLACED WITH | | REGULAR CURBS (& GUTTERS). |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2001-03-05 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2001-03-05 |
Time |
16:12 |
Rev Time |
2.00 |
Received By |
mamini |
Date |
2001-03-05 |
Time |
08:16 |
Sent To |
|
|
Notes |
2001-03-02 00:00:00 | FAILED: | | 1. ANY WORK PERFORMED IN CITY R.O.W AN | | "APPLICATION FOR CONSTRUCTION WITHIN | | PUBLIC RIGHT-OF-WAY" MUST BE SUBMITTED | | TO CITY ENGINEER'S OFFICE.ALSO SUBMIT | | SHOP DRAWING ON ALL MATERIALS TO PUBLIC | | UTILITIES ENGINEERING SERVICES | | DEPARTMENT 1000 45TH STREET WPB, FL | | 33407 | | 2. ALL DRIVEWAY APPROACHES MUST BE | | CONSTRUCTED PER CITY OF WEST PALM BEACH | | STANDARD.SEE ATTACHED | | 3. INLET AT 2ND DRIVEWAY GOING NORTH | | MAY REQUIRE ADJUSMENT(TOP ELEVATION), | | PLEASE VERIFY. | | 4. PLEASE RELOCATE THE EXISTING LIGHT | | POLE AT DRIVEWAY ENTERING THE DROP-OFF | | 5. PLEASE SHOW THE LOCATION OF CLEAN | | OUTS FOR SANITARY SEWER LATERAL, ON | | PROPERTY. | | 6. PROVIDE CALCULATION FOR PERVIOUS AND | | IMPERVIUS AREA CALCULATIONS ON A 8 1/2 X | | 11 SHEET SIGNED AND SEALED BY THE DESIGN | | ENGINEER DUE TO THE CHANGES.PLEASE | | INCLUDE NAME OF THE PROPERTY, ADDRESS, | | PROPERTY CONTROL NUMBER.THIS CAN BE | | DONE WITH PERMIT APPLICATION. | | 7. PLEASE SHOW THE NEW LOCATION OF | | DUMPSTER.PLEASE NOTE THAT THE NEW | | LOCATION SHOULD BE ACCESSIBLE AND SHOULD | | BE CONSTRUCTED PER CITY OF WEST PALM | | BEACH STANDARD. SEE ATTACHED STANDARD | | 8. NOTE # 5 ON SHEET C-2 SHOWS S-III | | ASPHALTIC CONCRETE, DETAILS SHOWS S-I, | | PLEASE VERIFY | | 9. DETAILS ON SHEET C-2 FOR PERFORATED | | PIPE TRENCH SHOWS 24" COVER, IT SHOULD | | 36" FOR UNDER TRAFFIC, PLEASE VERIFY. | | 10. NOTE TO LANDSCAPE ARCHITECT, PLEASE | | COMPLY WITH VISIBILITY TRIANGLE AT | | CORNER OF DIXIE AND CRANEST WAY AND | | PROVIDE 8' SIGHT LINE | | 11. NOTE TO LANDSCAPE ARCHITECT, PLEASE | | PROVIDE LANDSCAPING IN FRONT OF NEW | | BACKFLOW PREVENTERS. | | IF ANY QUSETION PLEASE CONTACT 659-8096 | | EXT. 8492 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
7 |
Status |
F |
Date |
2002-09-26 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-09-26 |
Time |
17:00 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-09-26 |
Time |
17:00 |
Sent To |
|
|
Notes |
2002-09-26 00:00:00 | PLEASE ARRANGE A MEETING WITH THIS | | OFFICE. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
6 |
Status |
F |
Date |
2002-05-02 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-05-02 |
Time |
14:35 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-05-02 |
Time |
14:35 |
Sent To |
|
|
Notes |
2002-05-02 00:00:00 | PLEASE IDENTIFY CHANGES BY EITHER | | CLOUDS OR TRIANGLES. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
5 |
Status |
P |
Date |
2001-09-12 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-09-12 |
Time |
11:58 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-09-12 |
Time |
11:58 |
Sent To |
|
|
Notes |
2001-09-12 00:00:00 | 1) SECURITY FEAUTURES WHEN INSTALLED | | ARE TO MEET THE REQUIREMENTS OF | | " SPECIAL LOCKING ARRANGEMENTS" PER | | THE LIFE SAFETY CODE, 1985 EDITION, | | SECTION 5-2.1.6. THIS CODE REQUIRES | | THE UNLOCKING OF DOORS "UPON ACTUATION | | OF AN APPROVED SUPERVISED AUTOMATIC | | FIRE DETECTION SYSTEM OR APPROVED | | SUPERVISED AUTOMATIC FIRE SPRINKLER | | SYSTEM | | UNLOCK UPON LOSS OF POWER CONTROLLING | | THE LOCK OR LOCKING MECHANISM AND | | INITIATE AN IRREVERSIBLE PROCESS WHICH | | WILL RELEASE THE LOCK WITHIN 15 | | SECONDS WHENEVER A FORCE OF NOT MORE | | THAN 15 LBS. IS CONTINOUSLY APPLIED. | | OPERATION OF THE DOOR SHALL ACTIVATE A | | SIGNAL IN THE VICINITY OF THE DOOR". | | ALSO A "SIGN SHALL BE PROVIDED ON THE | | DOOR ADJACENT TO THE RELEASE DEVICE | | WHICH READS PUSH UNTIL ALARM SOUNDS. | | DOOR CAN BE OPENED IN 15 SECONDS". | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2001-08-17 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-08-17 |
Time |
12:39 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-08-17 |
Time |
12:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2001-08-09 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-08-09 |
Time |
13:46 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-08-09 |
Time |
13:46 |
Sent To |
|
|
Notes |
2001-08-09 00:00:00 | CALLED AND SPOKE TO ARCHITECT ON 8/9/01 | | WRITTEN PLAN REVIEW COMMENTS ARE TO | | BE SUBMITTED. | | | | MIKE CARSILLO | | 659-8096, EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2001-05-16 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-05-16 |
Time |
10:16 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-05-16 |
Time |
10:16 |
Sent To |
|
|
Notes |
2001-05-16 00:00:00 | MANY OF THE PREVIOUS PLAN REVIEW | | COMMENTS MADE ON 3/01/01 HAVE NOT | | BEEN ADDRESSED. PLEASE PROVIDE WRITTEN | | COMMENTS TO THIS OFFICE ADDRESSING ALL | | PREVIOUS PLAN REVIEW COMMENTS. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-03-01 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-03-01 |
Time |
11:36 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-03-01 |
Time |
11:36 |
Sent To |
|
|
Notes |
2001-03-01 00:00:00 | 1) PLEASE INDICATE PROPOSED FIRE RESCUE | | INGRESS AND EGRESS POINTS TO THE NEW | | ADDITION. | | 2) PLEASE LOCATE EXISTING FIRE HYDRANT | | LOCATIONS FOR MUSEUM. | | 3) PLEASE PROVIDE MORE DETAILS ON GATES | | LOCATED NEAR SOUTH DIXIE FOR DROP OFF | | LANE. | | 4) PROVISIONS ARE TO BE MADE FOR AT | | LEAST TWO HANDICAPPED PERSONS. | | 5) MAXIMUM TRAVEL DISTANCE NOTE ON CD1.1 | | IS INCORRECT. MAXIMUM TRAVEL DISTANCE | | IN SPRINKLERED BUILDINGS OF THIS TYPE IS | | 200 FEET. | | 6) PLEASE FURTHER CLARIFY CD1.1. EXIT | | SIGNS AND DOORS MUST BE SHOWN. PLAN WAS | | DIFFICULT TO FOLLOW. | | 7) PLEASE ADVISE HOW DEMOLITION WILL | | OCCUR WHEN THE MUSEUM IS OPEN. | | 8) PLEASE PROVIDE PRODUCT APPROVAL FOR | | ONE HOUR FIRE RATED GLAZING IN CORRIDOR | | 101. | | 9) PLEASE INDICATE HOW ILLUMINATED | | EXIT SIGNS WILL BE INSTALLED IN OFFICES | | 230 DUE TO HEADROOM ISSUES. | | 10) PLEASE PROVIDE MORE DETAILS ON | | EMERGENCY GENERATOR 227. | | 11) PLEASE ADVISE WHAT THE OPEN SHAFT | | SPACE IS FOR ON PAGE A2.2. | | 12) PLEASE INDICATE COMPLIANCE WITH | | ATRIUM REQUIREMENTS IN THE LIFE SAFETY | | CODE. THE DESIGN OF THE ATRIUM IS TO BE | | DONE BY A LICENSED ENGINEER AND THE | | PLANS ARE TO BE SIGNED AND SEALED. | | PLEASE PROVIDE TESTING REQUIREMENTS AND | | EQUIPMENT THAT WILL BE NEEDED TO TEST | | THE ATRIUM SMOKE EXHAUST SYSTEM. PLEASE | | INDICATE WHAT THE FIREFIGHTERS ATRIUM | | OVERRIDE PANEL WILL LOOK LIKE. ALSO | | PLEASE INDICATE THE NUMBER OF REQUIRED | | AIR CHANGES THAT ARE REQUIRED. | | 13) PLEASE PROVIDE INTERIOR FINISH | | CLASSIFICATION INFORMATION. | | 14) ELEVATORS TO COMPLY WITH ANSI A17.1. | | PHASE ONE AND PHASE TWO ELEVATOR RECALL | | WILL BE REQUIRED. | | 15) ALL STAIRS TO COMPLY WITH NEW STAIRS | | NFPA 101, THE LIFE SAFETY CODE, 1985 | | EDITION. | | 16) PLEASE INDICATE WHAT THE RAISED | | PLATFORM ON THE NORTH INTERIOR | | ELEVATION WILL BE USED FOR. | | 17) NATURAL GAS INSTALLATION TO COMPLY | | WITH NFPA 54. | | 18) FIRE SPRINKLER DRAWINGS NOT SIGNED | | AND SEALED. NO HYDRAULIC CALCULATIONS | | PROVIDED WITH PLANS. PLEASE PROVIDE | | MORE DETAILS ON PRE-ACTION SPRINKLER | | SYSTEM. | | 19) PLEASE PROVIDE MORE DETAILS FOR THE | | TEMPORARY RELOCATION OF THE FIRE PUMP | | AND FIRE MAIN. IF APPROVED BY THIS | | OFFICE, WHEN DOES THIS ACTIVITY OCCUR. | | 20) THE CHILLER ROOM IS TO BE EQUIPPED | | WITH APPROPRIATE SIGNAGE, ALARMS, AND | | HAVE SELF-CONTAINED BREATHING APPARATUS | | SINCE REFRIGERATOR LEAK DETECTION IS | | NOTED ON THE PLANS. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2002-11-01 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-11-01 |
Time |
14:19 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-11-01 |
Time |
14:19 |
Sent To |
E |
|
Notes |
2002-11-01 00:00:00 | TO DVP./WRT. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
P |
Date |
2002-06-13 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-06-13 |
Time |
15:43 |
Rev Time |
2.00 |
Received By |
pkrauss |
Date |
2002-06-13 |
Time |
15:31 |
Sent To |
|
|
Notes |
2002-06-13 00:00:00 | DUCT REVISIONS |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
F |
Date |
2002-04-16 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-04-08 |
Time |
16:55 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2002-04-08 |
Time |
15:32 |
Sent To |
|
|
Notes |
2002-04-08 00:00:00 | | | | | PLEASEDESIGNATE REIVISIONS TO HELP | | EXPEDITE PLAN REVIEW. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2001-09-25 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-09-25 |
Time |
10:02 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2001-09-25 |
Time |
10:02 |
Sent To |
|
|
Notes |
2001-09-25 00:00:00 | PROVISO ON PLAN.PHK |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2001-08-08 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-08-08 |
Time |
10:59 |
Rev Time |
3.00 |
Received By |
pkrauss |
Date |
2001-08-08 |
Time |
09:00 |
Sent To |
|
|
Notes |
2001-08-08 00:00:00 | ******************PROVISO*************** | | | | | | REVISIONS FOR "CHILLER ROOM" WERE NOT A | | PART OF THIS REVIEW.ALL CHILLER ROOM | | REVISIONS NEED TO BE SUBMITTED WITH | | PERMIT NUMBER 01040393. | | | | NOTE:CONDENSATE SHALL BE INDICATED ON | | PLANS AND SHALL COMPLY WITH THE | | AMENDED 1994 SPC 804.3.RTU 1 | | ON PLAN SHEET H1.2A,SHALL NOT | | "SPILL ON ROOF".FAN COIL UNITS | | SHALL NOT GO INTO "SANITARY | | PIPING".PLEASE SUBMIT | | CONDENSATE FOR REVIEW. | | | | **** CONDENSATE NEEDS TO BE ADDRESSED | | PRIOR TO MECHANICAL PERMIT BEING | | ISSUED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2001-06-06 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-06-06 |
Time |
10:08 |
Rev Time |
3.00 |
Received By |
pkrauss |
Date |
2001-06-06 |
Time |
08:57 |
Sent To |
|
|
Notes |
2001-06-06 00:00:00 | *******************DENIED*************** | | | | 1.PLEASE PROVIDE O. A. CALCULATIONS | | AS PER ASHRAE 62-89. | | | | 2.PROVIDE AIR BALANCE SCHEDULE FOR | | COMPLIANCE WITH 1997 SMC 501.2. | | | | 3.PROVIDE INFORMATION SHOWING | | COMPLIANCE WITH 1997 SMC CHAPTER | | 11, LEVEL 1 MACHINE ROOM, I.E. | | SIGNAGE, LOCATION OF HORN & STROBES | | (OUTSIDE & INSIDE ROOM), LOCATION | | OF REFRIGERANT SENSORS & BREATHING | | APPARATUS. | | | | 4.DRAWING H1.3 "REFER TO MATCH LINE | | H1.4A", NO SUCH DRAWING WITH THIS | | SET OF PLANS. | | | | 5.DUCT SMOKE DETECTORS NEED TO BE | | INDICATED ON PLAN. | | | | 6.ADDITIONAL MECH PERMIT & PLANS | | REQUIRED FOR FUEL (PIPING & TANK). | | | | 7.ADDITIONAL MECH PERMIT & PLANS | | REQUIRED FOR KITCHEN HOOD & | | DUCTWORK. | | | | NOTE:PRIOR TO CONNECTING TO ANY | | EXISTING DUCTWORK, CALL FOR AN | | INSPECTION. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2001-03-22 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-03-22 |
Time |
10:29 |
Rev Time |
3.00 |
Received By |
pkrauss |
Date |
2001-03-21 |
Time |
12:47 |
Sent To |
|
|
Notes |
2001-03-22 00:00:00 | ******************DENIED**************** | | | | 1.PROVIDE OUTSIDE AIR SCHEDULE PER | | ASHRAE 62-89. | | 2.PROVIDE AIR BALANCE SHOWING COMPLIANCE | | WITH 1997 SMC 501.2. | | | | 3.SPECIFIC LOCATION AND INSTALLATION | | DETAILS ARE REQUIRED FOR FIRE AND OR | | SMOKE DAMPERS AS PER 1997 SMC 610.6. | | ALSO ACCESS TO MAINTAIN AND RESETTING | | OF FIRE DAMPER,1997 SMC 610.5. | | | | 4.PROVIDE ELEVATION AND SHAFT DETAIL FOR | | DUCTS PENETRATING FLOORS, 1997 SMC | | 610.4. | | | | 5.CLARIFY THE FOLLOWING EXHAUST FANS & | | DUCTWORK FOR: | | | | ROOM 304 - 3RD FLOOR MENS RESTROOM | | ROOM 205 - 2ND FLOOR CUST. | | ROOM 204 - 2ND FLOOR MENS RESTROOM | | ROOM 208 - 2ND FLOOR WOMENS RESTROOM | | | | 6.CLARIFY FUNCTION OF AHU 5, PLANS | | INDICATE SERVICING KITCHEN AND WOMENS | | RESTROOM (RM. 119), WHEREAS THE AHU | | SCHEDULE INDICATES AHU 5 SERVES | | CLASSROOMS. | | | | 7.PROVIDE CFM INFORMATION FOR 3RD FLOOR. | | | | 8.PROVIDE DETAIL OF 2ND FLOOR MECHANICAL | | ROOM - PLAN ELEVATION, CLEARANCE FOR | | SERVICEABILITY AS PER 1997 SMC 304.2.3 | | ALSO, PROVIDE LOCATION OF AHU 7. | | SCHEDULE INDICATES IT IS LOCATED IN | | MECHANICAL ROOM, 2ND FLOOR. | | | | 9.AHU 6 SERVES CAFE, IS THIS AN EXISTING | | SPACE? PLEASE PROVIDE MORE INFORMATION | | | | 10.PROVIDE MORE INFORMATION OF KITCHEN | | HOOD - MAKE UP AIR AND EXHAUST TO | | SHOW COMPLIANCE WITH 1997 SMC 504. | | | | | | | | | | 11.DRAWING H-7 SHOWS GREASE DUCT | | PENETRATING THE WALL BETWEEN THE | | KITCHEN TO THE BOILER ROOM, IS THIS | | WALL RATED? | | | | 12.PLEASE PROVIDE A CLEAR DETAIL OF ROOF | | TERMINATION OF BOTH FLUE AND EXHAUST | | OUTLET. | | | | 13.PROVIDE INFORMATION SHOWING C | | COMPLIANCE WITH SMC CHAPTER 11, | | LEVEL 1 MACHINE ROOM, I.E. SIGNAGE, | | VENTILATION CALCULATIONS (EMERGENCY | | & NORMAL), LOCATION OF HORN & STROBES | | (OUTSIDE & INSIDE ROOM), LOCATION OF | | REFRIGERANT SENSORS AND BREATHING | | APPARATUS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
9 |
Status |
P |
Date |
2002-10-29 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-10-29 |
Time |
14:05 |
Rev Time |
1.50 |
Received By |
kstevens |
Date |
2002-10-29 |
Time |
14:05 |
Sent To |
|
|
Notes |
2002-10-29 00:00:00 | REVISION OK - SHTS P1.2A, P4.1, P4.2, | | P4.4, & P4.5 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
8 |
Status |
P |
Date |
2002-10-18 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-10-18 |
Time |
11:40 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2002-10-18 |
Time |
11:40 |
Sent To |
|
|
Notes |
2002-10-18 00:00:00 | REVISION OK - REROUTE U/G RW LINES TO | | PLANTER DRAINS & POOL DRAIN. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
7 |
Status |
P |
Date |
2002-07-12 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-10-08 |
Time |
16:11 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-07-12 |
Time |
17:39 |
Sent To |
|
|
Notes |
2002-07-12 00:00:00 | REVISION OK - GAS RISER DIAGRAM |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
F |
Date |
2002-07-08 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-07-08 |
Time |
12:27 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-07-08 |
Time |
12:27 |
Sent To |
|
|
Notes |
2002-07-08 00:00:00 | DENIED | | REFERENCE: SPC-94 - FACBC-97 - SGC-97 | | | | 1) SHT P4.2 3" PLANTER DRAIN SHOWN ON | | FLAT DRAWING P1.0 MISSING FROM STORM | | RISER DIAGRAM. | | 2) SHT P1.2A REVISION SHOWS NO PIPING TO | | ROOF DRAINS, 1 NEW 4" RD-A, 2" SCUPPER | | DRAINS COL. LINE X15, 3" & 4" SCUPPER | | DRAINS COL. LINE BELOW X26. PLEASE | | CLAIRFY. ARE ORIGINAL ROOF DRAINS STILL | | BEING USED? ARE SCUPPERS SECONDARY | | DRAINS? IF SO THEY CAN NOT TIE INTO | | PRIMARY DRAIN SYSTEM. NO SECONDARY DRAIN | | SHOWN FOR LOWER ROOF TO THE LEFT SIDE. | | 3) PLEASE INDICATE WHERE ALL SECONDARY | | ROOF DRAINS DRAIN TO. | | 4) SHT P4.1 GREASE INTERCEPTOR DETAIL, | | 2 WAY CLEAN OUTS ARE REQUIRED FOR INLET | | & OUTLET SIDES OF GREASE INTERCEPTOR. | | 5) SHT P4.2 RAINWATER RISER DIAGRAM, THE | | AREA IN QUESTION ON COMMENT #2, (SHT P1. | | 2), IS NOT SHOWN ON RAINWATER RISER DIA- | | GRAM. PLEASE INDICATE WHERE THIS IS LO- | | CATED ON RISER DIAGRAM. | | 6) SHT P4.4 FUNNEL FLOOR DRAINS ARE NOT | | APPROVED. ALL INDIRECT WASTE SHALL DRAIN | | INTO A FLOOR SINK. PLEASE DELETE AND | | SHOW FLOOR SINKS. | | 7) SHT P4.5 SANT RISER DIAGRAM. PLEASE | | SHOW FIXTURE UNITS DRAINING IN SYSTEM. | | SHOW TOTAL AMOUNT AND SHOW DFU'S AS THEY | | ACCUMULATE IN SYSTEM. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
F |
Date |
2002-05-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-05-01 |
Time |
13:35 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-05-01 |
Time |
13:35 |
Sent To |
|
|
Notes |
2002-05-01 00:00:00 | DENIED | | | | REVIEW NOTES: *****UNSET*********** | | | | 1) EACH SHEET NOTED THAT THERE ARE MISC. | | REVISIONS. THERE ARE NO CLOUDS OR TRI- | | ANGLES TO DENOTE WHERE CHANGES ARE LO- | | CATED. PLEASE LABLE REVISIONS WITH A | | CLOUD AND TRIANGLES DATEING CHANGES. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2001-11-16 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-11-16 |
Time |
20:42 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2001-11-16 |
Time |
20:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2001-08-21 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-08-21 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2001-08-21 |
Time |
09:51 |
Sent To |
|
|
Notes |
2001-08-21 00:00:00 | PASSED PER PES | 2001-07-27 00:00:00 | SEE ATTACHMENTS ON PLANS.PES |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2001-06-04 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-06-04 |
Time |
14:16 |
Rev Time |
3.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-06-04 00:00:00 | PLUMBING PLAN REVIEWDENIED | | (1) PREVIOUS COMMENTS NOT ADDRESSED | | SHT A1.1, A1.8,DOOR SWINGS INTO CLEAR | | FLR SPACE OF LAV, RM # 305,SEC 4.17.5 | | (2) SHT P1.0,P4.1 GREASE TRAP SIZE AND | | TYPE TO BE REVIEWED BY WPB,RSTP ENVIRO- | | MENTAL COMPLIANCE RODNEY COMPO 561-837- | | 4074.WITH CUT SHTS FROM MFG. | | (3) SHT A6.13 ELEVATIONS,DIMENSIONS OF | | H/C PLUMBING FIXTURES INCLUDING URINALS, | | (4) SHT P1.1B CHILLER PLANT,REST RM #132 | | SHOWER COMPARTMENT,TO COMPLY W/FACBC 97 | | SEC 4.21, FIG. 35 A OR B. | | (5) SHT P3.1 PROVIDE A LIST OF KITCHEN | | EQUIPMENT FOR PLUMBING,GAS FIXTURES, | | SPC 94 SEC 104.3 | | (6) SHT P4.1 DISHWASHER TO BY PASS G/W, | | CONNECT TO SANITARY SEWER, LOCAL ORD. | | #2938-96 WPB,RSTP. | | (7) SHT P4.1 PROVIDE A COMPLETE GAS | | ISOMETRIC,FROM THE METER TO THE FARTHEST | | POINT OF USE,INCLUDE BOILER & KITCHEN. | | SEE ATTACHED GAS PERMIT APPLICATION REQ- | | UIRMENTS,SGC 97 SEC 104.3 ADDRESS EACH | | OF NINE ITEMS. | | (8) SHT P4.2 SHOW CALCULATIONS FOR ROOF | | & SCUPPER DRAINS, INCLUDING VERTICAL | | WALLS,ALSO SECONDARY DRAINS FROM ABOVE | | DRAINING ON TO LOWER ROOFS.SPC 94 | | SEC 1101.2,1108.3,1109.1 | | (9) SHTP4.1 SPC 94 SEC 921.4 GEN. DESIGN | | HORIZONTAL WASTE & VENT SYSTEM, EACH F/S | | BRANCH TO CONNECT SEPERATELY TO MAIN | | VENTED LINE, MIN SIZE 3". | | END OF COMMENTSPAUL SCHMITZ | | QUESTIONS561-659-8096 X8233 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-03-19 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-03-19 |
Time |
16:05 |
Rev Time |
3.00 |
Received By |
pschmitz |
Date |
2001-03-19 |
Time |
16:05 |
Sent To |
|
|
Notes |
2001-03-19 00:00:00 | DENIED; | | | | 1.A1.1 (119) WOMENS ROOM HANDICAP STALL. | | DOOR CANNOT SWING INTO CLEAR FLOOR | | SPACE OF LAV. ALSO ROOM (305) | | | | 2.GREASE TRAP SIZE AND LOCATION TO BE | | APPROVED BY RODNEY COMPO OF THE UTILTY | | DEPARTMENT. 835-7423 | | | | 3.SHOW ARCHITECTURAL DRAWINGS OF | | HANDICAP STALLS AND HANDICAP URINALS | | SHOWING SIZES TO COMPLY WITH THE 97 | | FACBC. | | | | 4.RISER DIAGRAMS REQUIRED FOR WATER, | | SANITARY, RAIN WATER AND GAS. | | | | 5.NEED ARCHITECTURAL DRAWING OF BOILERS. | | SHOW PIPE INSTALLATION. | | | | 6.MORE INFOMATION REQUIRED FOR GAS; | | A.TYPE OF GAS. | | B.DELIVERY PRESSURE. | | C.TYPE OF PIPE AND HOW IT WILL BE | | INSTALLED. | | D.BTU LOAD FOR EACH APPLIANCE AND | | TOTAL BTU LOAD ON SYSTEM. | | E.DISTANCE TO MOST REMOTE OUTLET. | | F.CALCULATIONS FOR COMBUSTION AIR FOR | | BOILERS. | | G.SHOW GAS VENTS FOR BOILERS. | | | | 7.SITE DRAWINGS DO NOT SHOW TIE IN FOR | | RAIN LEADERS. | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2001-05-16 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2001-05-16 |
Time |
08:54 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-05-16 00:00:00 | ZONING REQUIREMENTS MUST BE APPROVED | | BEFORE SIGN OFF |
|
|