Plan Review Stops For Permit 01020853 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2001-03-07 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-03-07 |
Time |
16:33 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2001-03-07 |
Time |
09:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2001-04-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-04-24 |
Time |
17:43 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-04-24 |
Time |
17:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-03-29 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-03-29 |
Time |
21:32 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-03-29 |
Time |
21:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-03-06 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-03-06 |
Time |
21:24 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-03-06 |
Time |
21:24 |
Sent To |
|
|
Notes |
2001-03-06 00:00:00 | **************** UNSAT *************** | | | | 1)NOTE: PLEASE SUBMIT CLARIFICATION ON | | PANELS "H1A" AND "L1A" BOTH SHOW IN | | UPPER LEFT HAND CORNERS OF SCHEDULES | | MAIN: 225/MAIN LUGS ONLY. PLEASE | | CLARIFY?? "H1A" DOESN'T NEED MAIN, | | WHILE"L1A" DOES. PLEASE SHOW. | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | AIC RATINGS ARE SHOWN FOR BOTH PANELS, | | BUT NOT FOR MAIN DISCONNECT ? PLEASE | | SUBMIT AND SHOW.215-5 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2001-04-03 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2001-04-03 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2001-04-06 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-04-06 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-04-06 |
Time |
10:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-03-06 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2001-03-06 |
Time |
14:36 |
Rev Time |
0.00 |
Received By |
mamini |
Date |
2001-03-06 |
Time |
14:36 |
Sent To |
|
|
Notes |
2001-03-06 00:00:00 | 1) PROVIDE PERMIT AND SHOP DRAWINGS | | FOR FIRE ALARM REMODEL. | | 2) FIRE ALARM NOTES INDICATES CLASS B, | | STYLE C FIRE ALARM CIRCUITS. ONLY CLASS | | A, STYLE D CIRCUITS WILL BE PERMITTED. | | 3) DUCT SMOKE DETECTOR IS REQUIRED TO | | BE CONNECTED TO FIRE ALARM SYSTEM. | | 4) BUILDING ADDRESS NOT SHOWN ON | | ELEVATION DRAWINGS. BUILDING ADDRESS | | TO COMPLY WITH CITY CODE REQUIREMENTS. | | 5) PLEASE PROVIDE PRODUCT APPROVALS FOR | | TWO HOUR RATED WALL FIRE SHUTTER LOCATED | | AT OFFICE 104. | | 6) PLEASE INDICATE STORAGE ARRANGEMENTS | | FOR WAREHOUSE 110 AREA. | | | | PLAN REVIEW STOP DONE ON ENGINEERING | | COMPUTER BECAUSE FIRE COMPUTER IS DOWN. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2001-03-05 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-03-05 |
Time |
13:27 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2001-03-05 |
Time |
13:27 |
Sent To |
|
|
Notes |
2001-03-05 00:00:00 | | | NOTE:DUCT SMOKE DETECTOR ON FAN SHUT | | DOWN SHALL NOTIFY ALARM/STROBE, | | AS PER 1997 SMC 406.1 AND NFPA | | 4-4.4.3. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2001-04-06 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-04-06 |
Time |
08:55 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2001-04-06 |
Time |
08:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2001-04-04 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-04-04 |
Time |
08:54 |
Rev Time |
0.75 |
Received By |
jleech |
Date |
2001-04-04 |
Time |
08:54 |
Sent To |
|
|
Notes |
2001-04-04 00:00:00 | DENIED; | | | | BATHROOM FACILITIES DO NOT MEET MINIMUM | | REQUIRMENTS. SEE 94 SPC TABLE 407. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-03-06 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-03-06 |
Time |
08:18 |
Rev Time |
1.50 |
Received By |
jleech |
Date |
2001-03-06 |
Time |
08:18 |
Sent To |
|
|
Notes |
2001-03-06 00:00:00 | DENIED; | | | | 1.AIR CHAMBERS SHALL BE APPROVED AND | | SIZED PER. 94 SPC. 607.8.2 AND | | ACCESSIBLE PER 607.8.3. | | | | 2.LOUNGE SINK MUST ALSO COMPLY TO 4.24.3 | | THRU 4.24.7. | | | | 3.MINIMUM FACILITYS ARE FROM 94 PLUMBING | | CODE NOT THE 97. WAREHOUSE 32 PEOPLE | | WOULD BE 2 W/C AND 2 LAVS. FOR EACH | | GENDER AND A DRINKING FOUNTAIN. | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2001-04-03 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2001-04-03 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|