Plan Review Details - Permit 01020853
Plan Review Stops For Permit 01020853
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-03-07 Cont ID  
Sent By hpiskura Date 2001-03-07 Time 16:33 Rev Time 0.00
Received By hpiskura Date 2001-03-07 Time 09:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-04-24 Cont ID  
Sent By dpalmer Date 2001-04-24 Time 17:43 Rev Time 0.00
Received By dpalmer Date 2001-04-24 Time 17:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-29 Cont ID  
Sent By dpalmer Date 2001-03-29 Time 21:32 Rev Time 0.00
Received By dpalmer Date 2001-03-29 Time 21:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-06 Cont ID  
Sent By dpalmer Date 2001-03-06 Time 21:24 Rev Time 0.00
Received By dpalmer Date 2001-03-06 Time 21:24 Sent To  
Notes
2001-03-06 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT CLARIFICATION ON
 PANELS "H1A" AND "L1A" BOTH SHOW IN
 UPPER LEFT HAND CORNERS OF SCHEDULES
 MAIN: 225/MAIN LUGS ONLY. PLEASE
 CLARIFY?? "H1A" DOESN'T NEED MAIN,
 WHILE"L1A" DOES. PLEASE SHOW.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 AIC RATINGS ARE SHOWN FOR BOTH PANELS,
 BUT NOT FOR MAIN DISCONNECT ? PLEASE
 SUBMIT AND SHOW.215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-04-03 Cont ID  
Sent By lsmith Date 2001-04-03 Time 15:55 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-04-06 Cont ID  
Sent By mcarsill Date 2001-04-06 Time 10:37 Rev Time 0.00
Received By mcarsill Date 2001-04-06 Time 10:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-03-06 Cont ID  
Sent By mamini Date 2001-03-06 Time 14:36 Rev Time 0.00
Received By mamini Date 2001-03-06 Time 14:36 Sent To  
Notes
2001-03-06 00:00:001) PROVIDE PERMIT AND SHOP DRAWINGS
 FOR FIRE ALARM REMODEL.
 2) FIRE ALARM NOTES INDICATES CLASS B,
 STYLE C FIRE ALARM CIRCUITS. ONLY CLASS
 A, STYLE D CIRCUITS WILL BE PERMITTED.
 3) DUCT SMOKE DETECTOR IS REQUIRED TO
 BE CONNECTED TO FIRE ALARM SYSTEM.
 4) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS
 TO COMPLY WITH CITY CODE REQUIREMENTS.
 5) PLEASE PROVIDE PRODUCT APPROVALS FOR
 TWO HOUR RATED WALL FIRE SHUTTER LOCATED
 AT OFFICE 104.
 6) PLEASE INDICATE STORAGE ARRANGEMENTS
 FOR WAREHOUSE 110 AREA.
  
 PLAN REVIEW STOP DONE ON ENGINEERING
 COMPUTER BECAUSE FIRE COMPUTER IS DOWN.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-03-05 Cont ID  
Sent By pkrauss Date 2001-03-05 Time 13:27 Rev Time 0.35
Received By pkrauss Date 2001-03-05 Time 13:27 Sent To  
Notes
2001-03-05 00:00:00 
 NOTE:DUCT SMOKE DETECTOR ON FAN SHUT
 DOWN SHALL NOTIFY ALARM/STROBE,
 AS PER 1997 SMC 406.1 AND NFPA
 4-4.4.3.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-04-06 Cont ID  
Sent By jleech Date 2001-04-06 Time 08:55 Rev Time 0.50
Received By jleech Date 2001-04-06 Time 08:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-04-04 Cont ID  
Sent By jleech Date 2001-04-04 Time 08:54 Rev Time 0.75
Received By jleech Date 2001-04-04 Time 08:54 Sent To  
Notes
2001-04-04 00:00:00DENIED;
  
 BATHROOM FACILITIES DO NOT MEET MINIMUM
 REQUIRMENTS. SEE 94 SPC TABLE 407.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-03-06 Cont ID  
Sent By jleech Date 2001-03-06 Time 08:18 Rev Time 1.50
Received By jleech Date 2001-03-06 Time 08:18 Sent To  
Notes
2001-03-06 00:00:00DENIED;
  
 1.AIR CHAMBERS SHALL BE APPROVED AND
 SIZED PER. 94 SPC. 607.8.2 AND
 ACCESSIBLE PER 607.8.3.
  
 2.LOUNGE SINK MUST ALSO COMPLY TO 4.24.3
 THRU 4.24.7.
  
 3.MINIMUM FACILITYS ARE FROM 94 PLUMBING
 CODE NOT THE 97. WAREHOUSE 32 PEOPLE
 WOULD BE 2 W/C AND 2 LAVS. FOR EACH
 GENDER AND A DRINKING FOUNTAIN.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-04-03 Cont ID  
Sent By lsmith Date 2001-04-03 Time 15:55 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***