Plan Review Details - Permit 01020819
Plan Review Stops For Permit 01020819
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-03-27 Cont ID  
Sent By mcarsill Date 2001-03-27 Time 09:50 Rev Time 0.00
Received By mcarsill Date 2001-03-27 Time 09:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-02-21 Cont ID  
Sent By mcarsill Date 2001-02-21 Time 12:02 Rev Time 0.00
Received By mcarsill Date 2001-02-21 Time 12:02 Sent To  
Notes
2001-02-21 00:00:001) SMOKE DETECTOR REQUIRED ABOVE FIRE
 ALARM CONTROL PANEL.
 2) SMOKE DETECTORS ARE REQUIRED IN ALL
 LOUNGES, RECREATION AREAS AND SLEEPING
 ROOMS OF THE CENTER.
 3) SYSTEM TO BE CLASS A OR FULLY
 ADDRESSABLE.
 4) IF 100 OR MORE DAY CARE STUDENTS ARE
 PRESENT THEN THE REQUIRED FIRE ALARM
 SYSTEM IS TO BE MONITORED.
 5) SYSTEM TO BE TESTED IN THE PRESENCE
 OF A FIRE RESCUE REPRENSATIVE AFTER
 INSTALLATION.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910