Plan Review Details - Permit 01020772
Plan Review Stops For Permit 01020772
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-20 Cont ID  
Sent By dpalmer Date 2001-03-20 Time 14:24 Rev Time 0.00
Received By dpalmer Date 2001-03-20 Time 14:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-05 Cont ID  
Sent By dpalmer Date 2001-03-05 Time 19:37 Rev Time 0.00
Received By dpalmer Date 2001-03-05 Time 19:37 Sent To  
Notes
2001-03-05 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE
 MISSING THE REQ`D MEANS OF EGRESS
 LIGHTING
 PER 210-70. ENTERING HOUSE/FOYER HALLWAY
 DOWN TO BEDROOM ETC.
  
 2)NOTE: PLEASE NOTE THAT THE AIC RATING
 SUBMITTED IS SHOWN FOR BRKRS ONLY?
 PLEASE SUBMIT ALL EQUIPMENT AIC RATINGS
 INCLUDING MAIN DISCONNECT. PER 110-9
 AND215-5
  
 3) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-03-20 Cont ID  
Sent By jleech Date 2001-03-20 Time 17:47 Rev Time 0.33
Received By jleech Date 2001-03-20 Time 17:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-02-24 Cont ID  
Sent By jleech Date 2001-02-24 Time 13:55 Rev Time 0.50
Received By jleech Date 2001-02-24 Time 13:55 Sent To  
Notes
2001-02-24 00:00:00PROVISO;
  
 1.R/A REQUIRED IN MASTER BEDROOM.
  
 2.MISSING DROP IN BEDROOM #2.
  
 3.1455 CFM'S WITH MISSING DROP. A/H
 ONLY CAPABLE OF 1400 CFM'S.
  
 REVISED DRAWINGS BEFORE FINAL A/C
 INSPECTION.
  
 A/C PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-03-20 Cont ID  
Sent By jleech Date 2001-03-20 Time 17:39 Rev Time 0.25
Received By jleech Date 2001-03-20 Time 17:38 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2001-03-21 Cont ID  
Sent By lhatten Date 2001-03-21 Time 19:10 Rev Time 4.00
Received By lhatten Date 2001-03-08 Time 18:52 Sent To  
Notes
2001-03-21 00:00:00RECEIVED ALL CHANGED SHEETS-ELECT. AND
 MECH.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-02-21 Cont ID  
Sent By lhatten Date 2001-02-21 Time 19:11 Rev Time 0.25
Received By lhatten Date   Time   Sent To  
Notes
2001-03-21 00:00:00OK PER SHIRLEY GRAHAM 02/21/2001 SIGNED