Plan Review Details - Permit 01020684
Plan Review Stops For Permit 01020684
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-04-11 Cont ID  
Sent By dpalmer Date 2001-04-05 Time 15:23 Rev Time 0.00
Received By dpalmer Date 2001-04-05 Time 15:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-05 Cont ID  
Sent By dpalmer Date 2001-03-05 Time 16:29 Rev Time 0.00
Received By dpalmer Date 2001-03-05 Time 16:29 Sent To  
Notes
2001-03-05 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER 220-3-C-1 AND SIZE OF EXISTING
 SERVICE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-04-13 Cont ID  
Sent By pkrauss Date 2001-04-06 Time 07:28 Rev Time 0.40
Received By pkrauss Date 2001-04-06 Time 07:28 Sent To  
Notes
2001-04-06 00:00:00******************DENIED****************
  
  
 TO BE BROUGHT IN UNDER MECHANICAL PERMIT
 ONLY - TOOK OUT OF ORIGINAL SUBMITTAL SO
 OTHER PERMITS COULD BE ISSUED.
  
 AS PER COMMENTS DATED 3/5/01, PLEASE
 SUBMITT SIZE OF NEW DUCT THE MAIN TRUNK
 LINE AS WELL AS THE BRANCH LINES.
 PLEASE DESIGNATE THE CFM'S TO THE AREA.
 IF TOTAL CFM SUPPLIED IS GREATER THAN
 300, THAN A RETURN AIR IS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-03-05 Cont ID  
Sent By jleech Date 2001-03-05 Time 07:40 Rev Time 0.33
Received By jleech Date 2001-03-05 Time 07:40 Sent To  
Notes
2001-03-05 00:00:00NOT ENOUGH INFORMATION.SUBMIT DRAWING
 SHOWING A/C WORK TO BE DONE, SIZE OF
 EQUIPMENT AND SIZE OF EXISTING DUCTS
 FEEDING NEW DUCT WORK.

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-03-05 Cont ID  
Sent By jleech Date 2001-03-05 Time 07:40 Rev Time 0.25
Received By jleech Date 2001-03-05 Time 07:40 Sent To  
Notes
2001-03-05 00:00:00NO PLUMBING SHOWN ON PLANS.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-04-12 Cont ID  
Sent By rmcdouga Date 2001-04-12 Time 12:12 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-04-12 00:00:00PROVISO
  
 1) PROVIDE SOIL TEST PER SEC. 1804.2.2
 OF THE CITY AMENDMENTS TO 1997 S.B.C.,
 AFTER EXISTING PAVEMENT IN AREA OF NEW
 FOUNDATION IS REMOVED AND BEFORE NEW
 FOUNDATION IS POURED.
  
 2) HAVE ARCHITECT CORRECT BASIC VELOCITY
 PRESSURE ON DESIGN COMPLIANCE FORM.
 VELOCITY PRESSURE FOR MEAN ROOF HEIGHT
 0-15'IS 24.7 PSF FROM TABLE 1606.2A.
  
 3) ELEVATION CERTIFICATE WILL BE
 REQUIRED FOR ADDITION PRIOR TO RECEIVING
 A C.O.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - EXTERIOR DOOR
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-03-13 Cont ID  
Sent By rmcdouga Date 2001-03-13 Time 14:42 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-03-13 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) PROVIDE (2) COPIES OF DESIGN
 CERTIFICATION COMPLIANCE FORM OR
 INCLUDEALL THE INFORMATION ON THE PLANS.
  
 4) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE
 USEDFOR ALL NON-IMPACT GLAZING.
  
 5)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - WINDOWS
 - STRUCTURAL WINDOW MULLIONS
 - EXTERIOR DOORS
 NOTE: SITE SPECIFIC ENGINEERING IS
 ACCEPTABLE. USE PRODUCT APPROVAL
 SUBMITTAL FORM.
  
 6) PROVIDE ELEVATIONS OF EXISTING
 STRUCTURE AND OF PROPOSED ADDITION.
 PROPERTY IS LOCATED IN AN A5 ZONE BASE
 FLOOD ELEVATION OF 7'. NEW ADDITION IS
 REQUIRED TO HAVE A MINIMUM FLOOR
 ELEVATION OF 7'6" PER CITY CODE.
 ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 7) PROVIDE SOIL TEST PER SEC. 1804.2.2
 OF CITY AMENDMENTS TO 1997 SBC.
  
 8) PROVIDE ENERGY CALCULATIONS AS
 REQUIRED BY THE FLORIDA ENERGY
 EFFICIENCY CODE.
  
 9) PROVIDE LINTEL SCHEDULE FOR ALL
 OPENINGS IN BLOCK WALLS.
  
 10) PROVIDE CALCULATED UPLIFT VALUES
 FOR ROOF TRUSSES. PROVIDE HURRICANE
 SCHEDULE. SPECIFY THE CONNECTORS THAT
 WILL BE USED TO ANCHOR TRUSSES AT THE
 EXISTING STRUCTURE. IF TRUSSES ARE
 ANCHORED TO 2X4 INTERIOR BEARING WALL AS
 INDICATED ON SHEET A7, PLEASE SPECIFY
 HOW CONTINOUS CONNECTION FROM FOUNDATION
 WILL BE ACHIEVED. CONNECTOR STC GIVEN
 FOR WOOD TRUSS TO WOOD BEARING IS A ROOF
 TRUSS CLIP USED FOR ALIGNMENT CONTROL
 BETWEEN TRUSSES AND NONBEARING WALLS, IT
 PROVIDES NO UPLIFT OR LATERAL RESISTANCE
  
 11) INDICATE THICKENED EDGE FOR INTERIOR
 BEARING WALL ON THE FOUNDATION PLAN ON
 SHEET A4.
  
 12) PROVIDE DETAILS OF WINDOW AND DOOR
 BUCKS THAT ARE CAPABLE OF WITHSTANDING
 DESIGN WIND LOADS.
  
 13) PROVIDE FASTENING SCHEDULE FOR ROOF
 SHEATHING COMPLYING WITH TABLE 2306.1 OF
 THE CITY OF WPB AMENDMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-03-12 Cont ID  
Sent By sgraham Date 2001-03-12 Time 09:58 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***