2001-03-13 00:00:00 | DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3) PROVIDE (2) COPIES OF DESIGN |
| CERTIFICATION COMPLIANCE FORM OR |
| INCLUDEALL THE INFORMATION ON THE PLANS. |
| |
| 4) PROVIDE STORM PANEL INFORMATION WITH |
| INSTALLATION SCHEDULE AND KEY PLAN WITH |
| SPECIFIC ANCHORS AND MOUNTING TO BE |
| USEDFOR ALL NON-IMPACT GLAZING. |
| |
| 5)PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - WINDOWS |
| - STRUCTURAL WINDOW MULLIONS |
| - EXTERIOR DOORS |
| NOTE: SITE SPECIFIC ENGINEERING IS |
| ACCEPTABLE. USE PRODUCT APPROVAL |
| SUBMITTAL FORM. |
| |
| 6) PROVIDE ELEVATIONS OF EXISTING |
| STRUCTURE AND OF PROPOSED ADDITION. |
| PROPERTY IS LOCATED IN AN A5 ZONE BASE |
| FLOOD ELEVATION OF 7'. NEW ADDITION IS |
| REQUIRED TO HAVE A MINIMUM FLOOR |
| ELEVATION OF 7'6" PER CITY CODE. |
| ELEVATION CERTIFICATE WILL BE REQUIRED. |
| |
| 7) PROVIDE SOIL TEST PER SEC. 1804.2.2 |
| OF CITY AMENDMENTS TO 1997 SBC. |
| |
| 8) PROVIDE ENERGY CALCULATIONS AS |
| REQUIRED BY THE FLORIDA ENERGY |
| EFFICIENCY CODE. |
| |
| 9) PROVIDE LINTEL SCHEDULE FOR ALL |
| OPENINGS IN BLOCK WALLS. |
| |
| 10) PROVIDE CALCULATED UPLIFT VALUES |
| FOR ROOF TRUSSES. PROVIDE HURRICANE |
| SCHEDULE. SPECIFY THE CONNECTORS THAT |
| WILL BE USED TO ANCHOR TRUSSES AT THE |
| EXISTING STRUCTURE. IF TRUSSES ARE |
| ANCHORED TO 2X4 INTERIOR BEARING WALL AS |
| INDICATED ON SHEET A7, PLEASE SPECIFY |
| HOW CONTINOUS CONNECTION FROM FOUNDATION |
| WILL BE ACHIEVED. CONNECTOR STC GIVEN |
| FOR WOOD TRUSS TO WOOD BEARING IS A ROOF |
| TRUSS CLIP USED FOR ALIGNMENT CONTROL |
| BETWEEN TRUSSES AND NONBEARING WALLS, IT |
| PROVIDES NO UPLIFT OR LATERAL RESISTANCE |
| |
| 11) INDICATE THICKENED EDGE FOR INTERIOR |
| BEARING WALL ON THE FOUNDATION PLAN ON |
| SHEET A4. |
| |
| 12) PROVIDE DETAILS OF WINDOW AND DOOR |
| BUCKS THAT ARE CAPABLE OF WITHSTANDING |
| DESIGN WIND LOADS. |
| |
| 13) PROVIDE FASTENING SCHEDULE FOR ROOF |
| SHEATHING COMPLYING WITH TABLE 2306.1 OF |
| THE CITY OF WPB AMENDMENTS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |