Plan Review Stops For Permit 01020643 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2001-02-15 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-02-15 |
Time |
16:36 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-02-15 |
Time |
16:36 |
Sent To |
|
|
Notes |
2001-02-15 00:00:00 | 1) THE SMOKE DETECTORS WHEN INSTALLED | | ARE TO BE A MINIMUM OF THREE FEET FROM | | AIR CONDITIONER DIFFUSERS. | | 2) TAMPER SWITCHES ARE TO BE PROVIDED | | ON THE BACKFLOW DEVICE. | | 3) THE FIRE ALARM SYSTEM AND FIRE | | SPRINKLER SYSTEM ARE TO BE MONITORED | | BY A LICENSED UL LISTED CENTRAL STATION | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | 4) FIRE ALARM SYSTEM TO BE CLASS A OR | | ADDRESSABLE. | | | | APPROVED PROVISO: | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
|