Plan Review Details - Permit 01020602
Plan Review Stops For Permit 01020602
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-02-26 Cont ID  
Sent By hpiskura Date 2001-02-26 Time 09:23 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-03-01 Cont ID  
Sent By dpalmer Date 2001-03-01 Time 18:46 Rev Time 0.00
Received By dpalmer Date 2001-03-01 Time 18:46 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-03-06 Cont ID  
Sent By lmartine Date 2001-03-06 Time 10:31 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-03-06 Cont ID  
Sent By lmartine Date 2001-03-06 Time 10:32 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-03-06 00:00:00APPROVED BY MIKE CARSILLO ON 2/20/01

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-03-01 Cont ID  
Sent By pkrauss Date 2001-03-01 Time 08:51 Rev Time 0.30
Received By pkrauss Date 2001-03-01 Time 08:35 Sent To  
Notes
2001-03-01 00:00:00 
 PROVISO:
  
 HEAT PUMPS REQUIRE A DRAIN PAN WITH
 OVERFLOW PROTECTION SUCH AS FLOAT
 SWITCH OR SECONDARY DRAIN LINE, AS
 PER 1997 SMC 304.8.6.1.
  
 REFERENCE DRAWING M0.1, NOTE 12 -
 AS PER NFPA 90A 4-4.4.3(A), FAN SHUT
 DOWN SHALL HAVE NOTIFICATION TO HORN
 AND STROBE IN NORMALLY OCCUPIED
 AREAS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-03-03 Cont ID  
Sent By jleech Date 2001-03-03 Time 12:45 Rev Time 0.50
Received By jleech Date 2001-03-03 Time 12:45 Sent To  
Notes
2001-03-03 00:00:00DEMOLITION OF PLUMBING IS THE ONLY
 PLUMBING WORK SHOWN.

Review Stop Z ZONING
Rev No 1 Status N Date 2001-03-06 Cont ID  
Sent By lmartine Date 2001-03-06 Time 10:35 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved