Plan Review Details - Permit 01020577
Plan Review Stops For Permit 01020577
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-02-23 Cont ID  
Sent By hpiskura Date 2001-02-23 Time 10:30 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-04-04 Cont ID  
Sent By dpalmer Date 2001-04-04 Time 20:36 Rev Time 0.00
Received By dpalmer Date 2001-04-04 Time 20:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2001-03-02 Cont ID  
Sent By pkrauss Date 2001-03-02 Time 07:23 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-03-02 Cont ID  
Sent By pkrauss Date 2001-03-02 Time 07:24 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-03-01 Cont ID  
Sent By mcarsill Date 2001-03-01 Time 08:57 Rev Time 0.00
Received By mcarsill Date 2001-03-01 Time 08:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-04-05 Cont ID  
Sent By pkrauss Date 2001-04-05 Time 08:28 Rev Time 0.30
Received By pkrauss Date 2001-04-05 Time 08:16 Sent To  
Notes
2001-04-05 00:00:00REVISION - RELOCATED A FEW SUPPLY DROPS.
 CHANGED MECHANICAL ROOM (AHU 2) SO
 RETURN AIR IS NOT TRANSFERRED FROM
 STORAGE ROOM TO MECHANICAL ROOM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-02-23 Cont ID  
Sent By pkrauss Date 2001-02-23 Time 14:43 Rev Time 0.40
Received By pkrauss Date 2001-02-23 Time 14:43 Sent To  
Notes
2001-02-23 00:00:00PROVISO:RETURN AIR MUST BE DUCTED
 FROM COMMON AREA NOT TRANSFERRED FROM
 STORAGE ROOM AS PER 1997 SMC 609.1.1.
 ALSO, THE DOOR TO THE STORAGE ROOM MUST
 BE ABLE TO ACCOMIDATE SERVICE/REMOVAL
 OF AHU TO COMPLY WITH 97 SMC 304.2.3.
  
 MECHANICAL PERMIT NEEDED.

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-02-23 Cont ID  
Sent By jleech Date 2001-02-23 Time 15:14 Rev Time 0.25
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2001-03-02 Cont ID  
Sent By pkrauss Date 2001-03-02 Time 07:24 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
2001-04-05 00:00:00REVISION - RELOCATE A FEW DROPS CHANGED
 MECHANICAL ROOM (AHU 2) SO RETURN AIR IS
 NOT BEING TRANSFERRED FROM STORAGE ROOM
 TO MECHANICAL ROOM.
 APPROVED.