Plan Review Details - Permit 01020278
Plan Review Stops For Permit 01020278
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-02-12 Cont ID  
Sent By hpiskura Date 2001-02-12 Time 15:36 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-04-27 Cont ID  
Sent By dpalmer Date 2001-04-27 Time 10:33 Rev Time 0.00
Received By dpalmer Date 2001-04-27 Time 10:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-04-10 Cont ID  
Sent By dpalmer Date 2001-04-10 Time 15:04 Rev Time 0.00
Received By dpalmer Date 2001-04-10 Time 15:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-02-20 Cont ID  
Sent By dpalmer Date 2001-02-20 Time 09:45 Rev Time 0.00
Received By dpalmer Date 2001-02-20 Time 09:45 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-03-13 Cont ID  
Sent By ndenmark Date 2001-03-13 Time 15:34 Rev Time 0.10
Received By ndenmark Date   Time   Sent To  
Notes
2001-03-13 00:00:00INTERIOR BUILDOUT

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-04-10 Cont ID  
Sent By mcarsill Date 2001-04-10 Time 13:08 Rev Time 0.00
Received By mcarsill Date 2001-04-10 Time 13:08 Sent To  
Notes
2001-04-10 00:00:001) PLEASE BE ADVISED THAT THE FIRE
 SPRINKLER SYSTEM MUST BE SUPERVISED
 BY A LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 PLANS AND PERMIT REQUIRED FOR THE
 INSTALLATION.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-02-21 Cont ID  
Sent By mcarsill Date 2001-02-21 Time 09:23 Rev Time 0.00
Received By mcarsill Date 2001-02-21 Time 09:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-04-18 Cont ID  
Sent By pkrauss Date 2001-04-18 Time 12:33 Rev Time 0.40
Received By pkrauss Date 2001-04-18 Time 12:00 Sent To  
Notes
2001-04-18 00:00:00******************PROVISO***************
  
 DRAWING M2.2, A/C ROOF EQUIPMENT
 MOUNTING DETAIL - SHALL COMPLY WITH
 AMENDED 1997 SMC 304.2.5, MOUNTING
 HEIGHT SHALL BE A MINIMUM OF 18" FROM
 ROOF SURFACE TO BOTTOM OF SUPPORT BEAM.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-03-13 Cont ID  
Sent By ndenmark Date 2001-03-13 Time 15:32 Rev Time 0.55
Received By ndenmark Date 2001-03-13 Time 15:32 Sent To  
Notes
2001-03-13 00:00:00CORRECTIONS PROVIDED IN REVISIONS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-02-21 Cont ID  
Sent By pkrauss Date 2001-02-21 Time 13:19 Rev Time 0.40
Received By pkrauss Date 2001-02-21 Time 13:19 Sent To  
Notes
2001-02-21 00:00:00*****************DENIED*****************
  
 PROVIDE OUTSIDE AIR CALCULATION AS PER
 ASHRAE 62-89.
  
 PROVIDE AIR BALANCE SCHEDULE AS PER 1997
 SMC 501.2.
  
 DRAWING #M2.1 AHU-3 AND AHU-8 DO NOT
 INDICATE CFM FOR EVERY DROP.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-03-10 Cont ID  
Sent By jleech Date 2001-03-10 Time 09:51 Rev Time 1.00
Received By jleech Date 2001-03-10 Time 09:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-02-28 Cont ID  
Sent By pschmitz Date 2001-02-28 Time 05:47 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-02-28 00:00:00PLUMBING PLAN REVIEWDENIED
 COMMENTSREFERENCE STD PLBG CODE 94
 (1) SHT PO.1 DETAIL P3.1
 COMPLY W/ SEC 501.7 WTR HTR READLY
 ACCESSIBLE,PROVIDE A DETAIL OF A WORKING
 PLATFORM WITH A SHIPS LADDER FIXED IN
 PLACE.
 DIELECTRIC UNIONS NOT PERMITTED, USE A
 DIELECTRIC NIPPLE OR COUPLING.
 PAN DRAIN MIN SIZE 1".
 (2) SHT P5.1 AIR CHAMBERS,COMPLY WITH
 SEC 607.8.3 AIR CHAMBERS READLY ACCESS-
 IBLE, SHOW A TYPICAL DETAIL HOW TO
 RESTORE AIR IN THE AIR CHAMBER WHEN IT
 BECOMES WATER LOGGED.
 (3)SHT P5.1 ISOMETRIC DRWG. SEC 901.2
 MOP SINK NOT VENTED.
 END OF COMMENTS QUESTIONS CONTACT
 PAUL SCHMITZ 561-659-8096X 8233

Review Stop Z ZONING
Rev No 1 Status N Date 2001-03-13 Cont ID  
Sent By ndenmark Date 2001-03-13 Time 15:36 Rev Time 0.25
Received By ndenmark Date   Time   Sent To  
Notes
2001-03-13 00:00:00INTERIOR BUILDOUT