Plan Review Details - Permit 01020262
Plan Review Stops For Permit 01020262
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-02-13 Cont ID  
Sent By hpiskura Date 2001-02-13 Time 08:37 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-02-20 Cont ID  
Sent By dpalmer Date 2001-02-20 Time 10:31 Rev Time 0.00
Received By dpalmer Date 2001-02-20 Time 10:31 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-03-15 Cont ID  
Sent By lsmith Date 2001-03-15 Time 15:10 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-03-28 Cont ID  
Sent By mcarsill Date 2001-03-28 Time 16:20 Rev Time 0.00
Received By mcarsill Date 2001-03-28 Time 16:20 Sent To  
Notes
2001-03-28 00:00:00PLANS APPROVED BY CAPTAIN RHETT
 TURNQUEST ON MARCH 22, 2001.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-02-20 Cont ID  
Sent By mcarsill Date 2001-02-20 Time 16:02 Rev Time 0.00
Received By mcarsill Date 2001-02-20 Time 16:02 Sent To  
Notes
2001-02-20 00:00:001) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR PLANS.
 2) PLEASE INDICATE LOCATIONS OF FIRE
 ALARM DEVICES.
 3) PLEASE EXPLAIN IF THE DOUBLE DOORS
 THAT SWING OTWARD ARE EXITS.
 4) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-03-23 Cont ID  
Sent By pkrauss Date 2001-03-23 Time 11:18 Rev Time 0.35
Received By pkrauss Date 2001-03-23 Time 11:02 Sent To  
Notes
2001-03-23 00:00:00RESUB - ALL COMMENTS WERE ADDRESSED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-02-27 Cont ID  
Sent By pkrauss Date 2001-02-21 Time 11:45 Rev Time 0.45
Received By pkrauss Date 2001-02-21 Time 11:44 Sent To  
Notes
2001-02-21 00:00:00*******************DENIED***************
  
 MECHANICAL PERMIT REQUIRED.
  
 NOTE:AS PER 1997 SMC 609.1.1 THERE
 SHALL BE NO COMBUSTIBLES ABOVE CEILING
 IN RETURN AIR PLENUM.
  
 AS PER 1997 SMC 304.8.6.1 OVER FLOW
 PROTECTION IS REQUIRED FOR DX-2.
  
 PROVIDE INFORMATION FOR BACKFLOW
 PREVENTION DRAWING M-4, NOTE 16 THRU 18.
  
 PROVIDE AIR BALANCE SCHEDULE AS WELL AS
 OUTSIDE AIR CALCULATIONS TO SHOW
 COMPLIANCE WITH ASHRAE 62-89.
  
 AS PER 1997 SMC 609.1.1 - DUCT SMOKE
 DETECTORS REQUIRED FOR FAN SHUT DOWN
 WITH NOTIFICATION TO ALARM/STROBE AS
 PER NFPA 90A 4-4.4.3.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-02-27 Cont ID  
Sent By jleech Date 2001-02-27 Time 12:50 Rev Time 0.50
Received By jleech Date 2001-02-27 Time 12:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2001-03-15 Cont ID  
Sent By lsmith Date 2001-03-15 Time 15:10 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***