Plan Review Details - Permit 01011330
Plan Review Stops For Permit 01011330
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-01-30 Cont ID  
Sent By mcarsill Date 2001-01-30 Time 09:03 Rev Time 0.00
Received By mcarsill Date 2001-01-30 Time 09:03 Sent To  
Notes
2001-01-30 00:00:001) SMOKE DETECTORS WHEN INSTALLED ARE TO
 BE AT LEAST THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
 2) SYSTEM TO BE CLASS A, STYLE D.
 3) THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEM TO BE MONITORED BY A LICENSED UL
 LISTED CENTRAL STATION APPROVED BY THE
 FIRE RESCUE DEPARTMENT.
 4) SYSTEM AFTER INSTALLATION IS TO BE
 TESTED WITH FIRE RESCUE PERSONNEL.
 5) PLEASE PROVIDE HORN-STROBE DEVICES
 IN WORK BAYS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910