Plan Review Details - Permit 01011199
Plan Review Stops For Permit 01011199
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-01-26 Cont ID  
Sent By mcarsill Date 2001-01-26 Time 12:03 Rev Time 0.00
Received By mcarsill Date 2001-01-26 Time 12:03 Sent To  
Notes
2001-01-26 00:00:001) FIRE ALARM SYSTEM TO BE CLASS A,
 STYLE D OR FULLY ADDRESSABLE.
 2) SMOKE DETECTORS TO BE INSTALLED A
 MINUMUM OF THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
 3) DUCT SMOKE DETECTORS REQUIRED IN
 SYSTEMS OVER 2000 CFM. WHEN ACTIVATED
 THESE DEVICES ARE TO SHUT DOWN AIR
 HANDLING EQUIPMENT AND ACTIVATE THE FIRE
 ALARM SYSTEM.
 4) ADDITIONAL DEVICES WILL BE REQUIRED
 WHEN THE INDIVIDUAL TENANT SPACES ARE
 FITTED UP.
 5) HORN-STROBES ARE TO BE MOUNTED
 BETWEEN 80 AND 96 INCHES FROM THE FLOOR.
 6) MANUAL PULL STATIONS ARE TO BE
 MOUNTED BETWEEN 3 1/2 TO 4 1/2 FEET
 ABOVE THE FOOR.
 7) SYSTEM TO BE TESTED WITH A MEMBER OF
 THE FIRE RESCUE DEPARTMENT.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910