Plan Review Details - Permit 01011195
Plan Review Stops For Permit 01011195
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2001-03-02 Cont ID  
Sent By lsmith Date 2001-03-02 Time 10:13 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-02-20 Cont ID  
Sent By dpalmer Date 2001-02-20 Time 14:35 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-06-15 Cont ID  
Sent By dpalmer Date 2001-06-15 Time 08:03 Rev Time 0.00
Received By dpalmer Date 2001-06-15 Time 08:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-05-04 Cont ID  
Sent By dpalmer Date 2001-05-04 Time 10:36 Rev Time 0.00
Received By dpalmer Date 2001-05-04 Time 10:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-20 Cont ID  
Sent By dpalmer Date 2001-02-20 Time 10:35 Rev Time 0.00
Received By dpalmer Date 2001-02-20 Time 14:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-01-22 Cont ID  
Sent By dpalmer Date 2001-01-22 Time 14:25 Rev Time 0.00
Received By dpalmer Date 2001-01-22 Time 14:24 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-03-02 Cont ID  
Sent By lsmith Date 2001-03-02 Time 10:12 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-02-15 Cont ID  
Sent By mcarsill Date 2001-02-15 Time 13:17 Rev Time 0.00
Received By mcarsill Date 2001-02-15 Time 13:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-01-29 Cont ID  
Sent By ndenmark Date 2001-01-29 Time 10:51 Rev Time 0.33
Received By ndenmark Date   Time   Sent To  
Notes
2001-01-29 00:00:00REVIEW DONE BY M. CARSILL UNDER PERMIT
 #0001033 AS REV. 5, NOTES TRANSFERRED
 BY P. KRAUSS.
  
 1.WRONG LIFE SAFETY CODE REFERENCED ON
 SHEET A-001.SHOULD READ 1985 EDITION
 INSTEAD OF 1994 EDITION.
  
 2.PROVIDE SEPARATE PLANS AND PERMIT
 FOR FIRE SPRINKLER REMODEL.
  
 3.PROVIDE SEPARATE PLANS AND PERMIT
 FOR FIRE ALARM EQUIPMENT SHOWN ON
 DRAWINGS.SYSTEM TO BE CLASS A OR
 ADDRESSABLE.CUT SHEETS, WIRING
 DIAGRAM, FLOOR PLANS AND BATTERY
 CALCULATIONS ARE TO BE PROVIDED.
  
 4.PLEASE CLEARLY IDENTIFY EMERGENCY
 LIGHTING LOCATIONS WITHIN TENANT SPACE.
  
 5.PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR TENANT
 SPACE.
  
 6.PLEASE DISPLAY LOCATIONS OF PORTABLE
 FIRE EXTINGUISHERS.PLEASEPROVIDE
 RATING FOR EXTINGUISHERS.
  
 CAPTAIN MIKE CARSILLO
 659-8096, EXT. 8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-03-02 Cont ID  
Sent By pkrauss Date 2001-03-02 Time 10:18 Rev Time 0.45
Received By pkrauss Date 2001-03-02 Time 10:18 Sent To  
Notes
2001-03-02 00:00:00PROVISO:DUCT SMOKE DETECTOR MUST BE
 TESTED TO SHOW COMPPLIANCE WITH NFPA
 90A 4-4.4.4.3, FAN SHUT DOWN WITH
 NOTIFICATION TO NORMALLY OCCUPIED AREAS
 BY ALARM/STROBE.
  
 AHU-5 IN THE COPY/FILE WORKROOM (ROOM
 234), SHALL HAVE ACCESS/CLEARENCE FOR
 MAINTENANCE & SERVICE AS PER 1997 SMC
 304.2.1 & 304.2.3.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-01-29 Cont ID  
Sent By ndenmark Date 2001-01-29 Time 09:46 Rev Time 0.50
Received By ndenmark Date 2001-01-29 Time 09:45 Sent To  
Notes
2001-01-29 00:00:00**************DENIED********************
 1. PROVIDE INFORMATION ON EQUIPMENT TO
 BE USED. NO AC-2 DRAWING INCLUDED AS
 CALLED FOR ON SCHEDULE OF DRAWINGS.
 2. ALL WALLS APPEAR TO GO FLOOR TO
 CEILING. PROVIDE RETURN AIR TRANSFER
 FOR AHU,S FROM ROOMS.
 3. PROVIDE LEGEND, PLAN SHOWS EXISTING
 CHW IS THIS CONDENSER WATER OR CHILLED
 WATER? PLAN CALLS FOR CONDENSATE DRAIN
 AND EMERGENCY PAN. PROVIDE INFORMATION
 ON SECONDARY PIPIMG OR FLOAT SWITCH.
 4. NOTE: NO COMBUSIBLE MATERIALS IN
 RETURN AIR PLENUM ABOVE CEILING AREA.
 5. PROVIDE INFORMATION ON FAN SHUT DOWN
 BY DUCT SMOKE DETECTOR FOR ALL
 EQUIPMENT (COMMON PLENUM).
 6. NOTE THIS PLAN CANNOT BE CROSS
 REFERENCED TO SHELL PLAN BECAUSE THE
 INFORMATION PROVIDED ON THIS PLAN DOES
 NOT CORRESPOND TO THE INFORMATION ON THE
 SHELL PLAN.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-03-02 Cont ID  
Sent By pschmitz Date 2001-03-02 Time 07:18 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-03-02 00:00:00PLUMBING PLAN REVIEW REVISIONS,PROVISO
 FLR DRAINS IN PUBLIC REST RM'S SPC 94
 SEC 409.4 REQUIRED. SHT P-2.
 END OF COMMENTS. PAUL SCHMITZ
 QUESTIONS561-659 8096 X 8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-01-29 Cont ID  
Sent By ndenmark Date 2001-01-29 Time 10:10 Rev Time 0.33
Received By jleech Date 2001-01-29 Time 14:55 Sent To  
Notes
2001-01-29 00:00:00REVIEW DONE BY J. LEECH UNDER PERMIT
 #0001033 AS REV. 5, NOTES TRANSFERRED
 BY P. KRAUSS.
  
 1. KITCHEN SINK SHT. A-4 MUST COMPLY
 WITH 94 FACBC 4.24.1 THRU 4.24.7.
  
 2. AIR CHAMBERS TO COMPLY WITH 94 SPC
 607.8.2.
  
 3. FIXTURE CONNECTION SCHEDULE SHOWS
 FLOOR DRAINS, BUT ARE NOT SHOWN ON
 DRAWINGS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT JOHN LEECH AT 659-8096 EXT.
 8377.

Review Stop Z ZONING
Rev No 1 Status N Date 2001-03-02 Cont ID  
Sent By lsmith Date 2001-03-02 Time 10:12 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***