Plan Review Stops For Permit 01011195 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
N |
Date |
2001-03-02 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2001-03-02 |
Time |
10:13 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2001-02-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-02-20 |
Time |
14:35 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2001-06-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-06-15 |
Time |
08:03 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-06-15 |
Time |
08:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2001-05-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-05-04 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-05-04 |
Time |
10:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-02-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-02-20 |
Time |
10:35 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-02-20 |
Time |
14:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2001-01-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-01-22 |
Time |
14:25 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-01-22 |
Time |
14:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2001-03-02 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2001-03-02 |
Time |
10:12 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2001-02-15 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-02-15 |
Time |
13:17 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-02-15 |
Time |
13:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-01-29 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2001-01-29 |
Time |
10:51 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-29 00:00:00 | REVIEW DONE BY M. CARSILL UNDER PERMIT | | #0001033 AS REV. 5, NOTES TRANSFERRED | | BY P. KRAUSS. | | | | 1.WRONG LIFE SAFETY CODE REFERENCED ON | | SHEET A-001.SHOULD READ 1985 EDITION | | INSTEAD OF 1994 EDITION. | | | | 2.PROVIDE SEPARATE PLANS AND PERMIT | | FOR FIRE SPRINKLER REMODEL. | | | | 3.PROVIDE SEPARATE PLANS AND PERMIT | | FOR FIRE ALARM EQUIPMENT SHOWN ON | | DRAWINGS.SYSTEM TO BE CLASS A OR | | ADDRESSABLE.CUT SHEETS, WIRING | | DIAGRAM, FLOOR PLANS AND BATTERY | | CALCULATIONS ARE TO BE PROVIDED. | | | | 4.PLEASE CLEARLY IDENTIFY EMERGENCY | | LIGHTING LOCATIONS WITHIN TENANT SPACE. | | | | 5.PLEASE PROVIDE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR TENANT | | SPACE. | | | | 6.PLEASE DISPLAY LOCATIONS OF PORTABLE | | FIRE EXTINGUISHERS.PLEASEPROVIDE | | RATING FOR EXTINGUISHERS. | | | | CAPTAIN MIKE CARSILLO | | 659-8096, EXT. 8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-03-02 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-03-02 |
Time |
10:18 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2001-03-02 |
Time |
10:18 |
Sent To |
|
|
Notes |
2001-03-02 00:00:00 | PROVISO:DUCT SMOKE DETECTOR MUST BE | | TESTED TO SHOW COMPPLIANCE WITH NFPA | | 90A 4-4.4.4.3, FAN SHUT DOWN WITH | | NOTIFICATION TO NORMALLY OCCUPIED AREAS | | BY ALARM/STROBE. | | | | AHU-5 IN THE COPY/FILE WORKROOM (ROOM | | 234), SHALL HAVE ACCESS/CLEARENCE FOR | | MAINTENANCE & SERVICE AS PER 1997 SMC | | 304.2.1 & 304.2.3. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2001-01-29 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2001-01-29 |
Time |
09:46 |
Rev Time |
0.50 |
Received By |
ndenmark |
Date |
2001-01-29 |
Time |
09:45 |
Sent To |
|
|
Notes |
2001-01-29 00:00:00 | **************DENIED******************** | | 1. PROVIDE INFORMATION ON EQUIPMENT TO | | BE USED. NO AC-2 DRAWING INCLUDED AS | | CALLED FOR ON SCHEDULE OF DRAWINGS. | | 2. ALL WALLS APPEAR TO GO FLOOR TO | | CEILING. PROVIDE RETURN AIR TRANSFER | | FOR AHU,S FROM ROOMS. | | 3. PROVIDE LEGEND, PLAN SHOWS EXISTING | | CHW IS THIS CONDENSER WATER OR CHILLED | | WATER? PLAN CALLS FOR CONDENSATE DRAIN | | AND EMERGENCY PAN. PROVIDE INFORMATION | | ON SECONDARY PIPIMG OR FLOAT SWITCH. | | 4. NOTE: NO COMBUSIBLE MATERIALS IN | | RETURN AIR PLENUM ABOVE CEILING AREA. | | 5. PROVIDE INFORMATION ON FAN SHUT DOWN | | BY DUCT SMOKE DETECTOR FOR ALL | | EQUIPMENT (COMMON PLENUM). | | 6. NOTE THIS PLAN CANNOT BE CROSS | | REFERENCED TO SHELL PLAN BECAUSE THE | | INFORMATION PROVIDED ON THIS PLAN DOES | | NOT CORRESPOND TO THE INFORMATION ON THE | | SHELL PLAN. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-03-02 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-03-02 |
Time |
07:18 |
Rev Time |
1.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-03-02 00:00:00 | PLUMBING PLAN REVIEW REVISIONS,PROVISO | | FLR DRAINS IN PUBLIC REST RM'S SPC 94 | | SEC 409.4 REQUIRED. SHT P-2. | | END OF COMMENTS. PAUL SCHMITZ | | QUESTIONS561-659 8096 X 8233 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-01-29 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2001-01-29 |
Time |
10:10 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2001-01-29 |
Time |
14:55 |
Sent To |
|
|
Notes |
2001-01-29 00:00:00 | REVIEW DONE BY J. LEECH UNDER PERMIT | | #0001033 AS REV. 5, NOTES TRANSFERRED | | BY P. KRAUSS. | | | | 1. KITCHEN SINK SHT. A-4 MUST COMPLY | | WITH 94 FACBC 4.24.1 THRU 4.24.7. | | | | 2. AIR CHAMBERS TO COMPLY WITH 94 SPC | | 607.8.2. | | | | 3. FIXTURE CONNECTION SCHEDULE SHOWS | | FLOOR DRAINS, BUT ARE NOT SHOWN ON | | DRAWINGS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT JOHN LEECH AT 659-8096 EXT. | | 8377. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2001-03-02 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2001-03-02 |
Time |
10:12 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|