Plan Review Stops For Permit 01010952 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-01-31 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2002-01-31 |
Time |
17:41 |
Rev Time |
1.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2001-01-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-01-30 |
Time |
08:18 |
Rev Time |
0.75 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-30 00:00:00 | PROVISO: SBC 705.1.3.2.3 | | EXIT ACCESS DOORS ARE TO BE FIRE RATED | | AND TO BE SELF CLOSING. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2002-01-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-01-22 |
Time |
13:41 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-01-22 |
Time |
13:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-02-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-02-20 |
Time |
13:04 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-02-20 |
Time |
13:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-01-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-01-31 |
Time |
12:00 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-01-31 |
Time |
12:00 |
Sent To |
|
|
Notes |
2001-01-31 00:00:00 | ****************** UNSAT *********** | | | | 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | #`S ON PLANS AND CORRELATE WITH PANEL | | SCHEDULES. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2001-02-28 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-02-28 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2002-01-15 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-01-15 |
Time |
08:51 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-01-15 |
Time |
08:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2001-01-23 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-01-23 |
Time |
10:10 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-01-23 |
Time |
10:10 |
Sent To |
|
|
Notes |
2001-01-23 00:00:00 | 1) NO INTERIOR FINISH INFORMATION | | COULD BE LOCATED FOR PLANS. INTERIOR | | FINISH ON WALLS AND CEILINGS IN EXITS | | TO BE CLASS A OR B. IN OFFICE AREAS, THE | | INTERIOR FINISH TO BE CLASS A,B OR C. | | 2) THE 3/4 DOORS TO BE EQUIPPED WITH | | SELF-CLOSING DEVICES. | | 3) SINCE THIS IS AN EXISTING BUILDING, | | MINIMUM HEADROOM SHALL BE SEVEN FEET | | AND ANY PROJECTION FROM THE CEILING | | SHALL BE NOT LESS THAN SIX FOOT EIGHT. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2002-01-24 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-01-24 |
Time |
12:03 |
Rev Time |
0.25 |
Received By |
pkrauss |
Date |
2002-01-24 |
Time |
12:03 |
Sent To |
|
|
Notes |
2002-01-24 00:00:00 | NO MECHANICAL SUBMITTED FOR REVISION. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2001-01-30 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2001-01-30 |
Time |
08:35 |
Rev Time |
0.25 |
Received By |
ndenmark |
Date |
2001-01-30 |
Time |
08:35 |
Sent To |
|
|
Notes |
2001-01-30 00:00:00 | INSUFFICIENT INFORMATION TO REVIEW. | | | | MECHANICAL CONTRACTOR TO PROVIDE PLANS | | AT TIME OF MECHANICAL PERMIT | | APPLICATION, PRIOR TO ANY MECHANICAL | | WORK BEING DONE. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2002-01-22 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-01-22 |
Time |
17:58 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2002-01-22 |
Time |
17:57 |
Sent To |
|
|
Notes |
2002-01-22 00:00:00 | REVISIONS OK ADDED SINKS (3) REMOVE | | FUTURE MOP SINK - CHANGE TOILET ROOM LAY | | OUT - MOVE DRINKING FOUNTAIN. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-02-28 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-02-28 |
Time |
14:04 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2001-02-28 |
Time |
14:04 |
Sent To |
|
|
Notes |
2001-02-28 00:00:00 | PROVISO; AS MARKED ON PLANS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-01-25 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-01-25 |
Time |
11:45 |
Rev Time |
0.75 |
Received By |
jleech |
Date |
2001-01-25 |
Time |
11:45 |
Sent To |
|
|
Notes |
2001-01-25 00:00:00 | 1.FLOOR DRAINS IN RESTROOMS SHALL BE 3" | | PER 94 SPC 409.4.1.1. | | | | 2.MECHANICAL WATER HAMMER ARRESTERS | | SHALL BE INSTALLED.SEC 607.8.2 AND | | MUSTBE ACCESEIBLE. SEC.607.8.3. | | | | 3.BREAK ROOM SINK SHALL COMPLY WITH 97 | | FACBC SEC. 4.24.1 THRU 4.24.7. | | | | PLUMBING PLAN REVIEW BY | | JOHN LEECH | | 659-8096 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2001-02-28 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-02-28 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|