Plan Review Details - Permit 01010947
Plan Review Stops For Permit 01010947
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-01-30 Cont ID  
Sent By jwitmer Date 2001-01-30 Time 08:08 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-30 00:00:00SBC 705.1.3.2.3- REQUIRES ALL DOORS LEAD
 ING TO EXIT ACCESS CORIDORS TO BE FIRE
 RATED AND SELF CLOSING.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-20 Cont ID  
Sent By dpalmer Date 2001-02-20 Time 12:28 Rev Time 0.00
Received By dpalmer Date 2001-02-20 Time 12:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-31 Cont ID  
Sent By dpalmer Date 2001-01-31 Time 07:19 Rev Time 0.00
Received By dpalmer Date 2001-01-31 Time 07:18 Sent To  
Notes
2001-01-31 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS, AND CORRELATE WITH PANEL
 SCHEDULES.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS PLEAS
 E CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-01-23 Cont ID  
Sent By mcarsill Date 2001-01-23 Time 10:47 Rev Time 0.00
Received By mcarsill Date 2001-01-23 Time 10:47 Sent To  
Notes
2001-01-23 00:00:001) NO INTERIOR FINISH INFORMATION COULD
 BE LOCATED ON THE PLANS. INTERIOR FINISH
 IN EXITS SHALL BE CLASS A OR B. IN
 OFFICE AREAS, IT SHALL BE CLASS A, B, OR
 C.
 2) NEW 3/4 HOUR DOOR TO BE EQUIPPED WITH
 A SELF-CLOSING DEVICE.
 3) ANOTHER EXIT SIGN IS NEEDED IN THE
 CORRIDOR TO DIRECT PERSONS TO EXIT
 LOCATED IN FILE ROOM.
 4) ANOTHER EMERGENCY LIGHT APPEARS TO
 BE NEEDED IN EXISTING WAITING ROOM.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-01-30 Cont ID  
Sent By ndenmark Date 2001-01-30 Time 08:26 Rev Time 0.25
Received By ndenmark Date 2001-01-30 Time 08:26 Sent To  
Notes
2001-01-30 00:00:00INSUFFICIENT INFO. TO REVIEW.
 MECHANICAL CONTRACTOR TO PROVIDE PLANS
 AT TIME OF MECH PERMIT APPLICATION
 PRIOR TO ANY MECH WORK BEING DONE.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-02-28 Cont ID  
Sent By jleech Date 2001-02-28 Time 09:50 Rev Time 0.50
Received By pschmitz Date 2001-02-28 Time 09:50 Sent To  
Notes
2001-02-28 00:00:00PROVISO; AS MARKED ON DRAWINGS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-01-31 Cont ID  
Sent By jleech Date 2001-01-31 Time 09:55 Rev Time 0.75
Received By pschmitz Date 2001-01-31 Time 09:55 Sent To  
Notes
2001-01-31 00:00:00DENIED;
  
 1.AIR CHAMBERS SHALL BE APPROVED
 ENGINEERED,SIZED AND ACCESSIBLE.
 2.PAGE E-1 PLUMBING NOTE 7 FLOOR DRAINS
 ARE NOT SHOWN ON DRAWINGS.