Plan Review Details - Permit 01010947
Plan Review Stops For Permit 01010947 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2001-01-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-01-30 |
Time |
08:08 |
Rev Time |
0.75 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-30 00:00:00 | SBC 705.1.3.2.3- REQUIRES ALL DOORS LEAD | | ING TO EXIT ACCESS CORIDORS TO BE FIRE | | RATED AND SELF CLOSING. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-02-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-02-20 |
Time |
12:28 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-02-20 |
Time |
12:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-01-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-01-31 |
Time |
07:19 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-01-31 |
Time |
07:18 |
Sent To |
|
|
Notes |
2001-01-31 00:00:00 | ******************* UNSAT ************* | | | | 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | #`S ON PLANS, AND CORRELATE WITH PANEL | | SCHEDULES. | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRNET PER 110-9. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS PLEAS | | E CALL. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2001-01-23 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-01-23 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-01-23 |
Time |
10:47 |
Sent To |
|
|
Notes |
2001-01-23 00:00:00 | 1) NO INTERIOR FINISH INFORMATION COULD | | BE LOCATED ON THE PLANS. INTERIOR FINISH | | IN EXITS SHALL BE CLASS A OR B. IN | | OFFICE AREAS, IT SHALL BE CLASS A, B, OR | | C. | | 2) NEW 3/4 HOUR DOOR TO BE EQUIPPED WITH | | A SELF-CLOSING DEVICE. | | 3) ANOTHER EXIT SIGN IS NEEDED IN THE | | CORRIDOR TO DIRECT PERSONS TO EXIT | | LOCATED IN FILE ROOM. | | 4) ANOTHER EMERGENCY LIGHT APPEARS TO | | BE NEEDED IN EXISTING WAITING ROOM. | | | | APPROVED PROVISO: | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2001-01-30 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2001-01-30 |
Time |
08:26 |
Rev Time |
0.25 |
Received By |
ndenmark |
Date |
2001-01-30 |
Time |
08:26 |
Sent To |
|
|
Notes |
2001-01-30 00:00:00 | INSUFFICIENT INFO. TO REVIEW. | | MECHANICAL CONTRACTOR TO PROVIDE PLANS | | AT TIME OF MECH PERMIT APPLICATION | | PRIOR TO ANY MECH WORK BEING DONE. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-02-28 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-02-28 |
Time |
09:50 |
Rev Time |
0.50 |
Received By |
pschmitz |
Date |
2001-02-28 |
Time |
09:50 |
Sent To |
|
|
Notes |
2001-02-28 00:00:00 | PROVISO; AS MARKED ON DRAWINGS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-01-31 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-01-31 |
Time |
09:55 |
Rev Time |
0.75 |
Received By |
pschmitz |
Date |
2001-01-31 |
Time |
09:55 |
Sent To |
|
|
Notes |
2001-01-31 00:00:00 | DENIED; | | | | 1.AIR CHAMBERS SHALL BE APPROVED | | ENGINEERED,SIZED AND ACCESSIBLE. | | 2.PAGE E-1 PLUMBING NOTE 7 FLOOR DRAINS | | ARE NOT SHOWN ON DRAWINGS. |
|
|
|