Plan Review Details - Permit 01010525
Plan Review Stops For Permit 01010525
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-01-22 Cont ID  
Sent By dpalmer Date 2001-01-22 Time 21:06 Rev Time 0.00
Received By dpalmer Date 2001-01-22 Time 21:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-01-20 Cont ID  
Sent By jleech Date 2001-01-20 Time 06:40 Rev Time 0.33
Received By jleech Date 2001-01-20 Time 06:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-01-20 Cont ID  
Sent By jleech Date 2001-01-20 Time 06:40 Rev Time 0.25
Received By jleech Date 2001-01-20 Time 06:40 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-03-21 Cont ID  
Sent By lhatten Date 2001-03-21 Time 21:18 Rev Time 2.00
Received By lhatten Date   Time   Sent To  
Notes
2001-03-21 00:00:00CORRECTED ALL STRUCTURAL PROBLEMS PER
 LOU HATTENS REVIEW03/21/2001

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-01-30 Cont ID  
Sent By rmcdouga Date 2001-01-30 Time 09:58 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-30 00:00:00DENIED
  
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR:
 - GLASS BLOCK (WIND LOADS)
 - SLIDING GLASS DOORS
 - FIXED GLASS AND ARCHED TOP FIXED GLASS
 WINDOWS
 - HORIZONTAL SLIDING WINDOWS
 - SINGLE HUNG WINDOWS
 - WINDOW MULLIONS
 - 8'OUTSWING DOOR WITH SIDELITE
 - MANUFACTURES INFORMATION ON BBQ INC.
 UL LISTING
  
 3) PROVIDE CALCULATED DESIGN PRESSURES
 FOR ALL EXTERIOR WINDOW AND DOOR
 OPENINGS.
  
 4) DESIGN PARAMETERS ON SHEET A-5A AND
 A-5B INCORRECTLY REFERENCE SSBC 1994,
 THE CITY OF WEST PALM BEACH HAS ADOPTED
 THE 1997 STANDARD BUILDING CODE. PLEASE
 CORRECT.
  
 5) NO FOOTING IS INDICATED FOR THE
 CENTER COLUMN AT THE REAR COVERED PATIO
 ON SHEET A-1. PLEASE CORRECT.
  
 6) ON SHEET A-5A DETAIL 2/A-6 SHOULD BE
 2/A-8,THERE IS NO DETAIL 2 ON A-6.
 PLEASE CORRECT.
  
 7) DETAILS 4/A-8 AND 3/A-8 INDICATED ON
 SHEETS A-5A AND A-5B ARE NOT CORRECT.
 PLEASE MAKE CORRECTIONS.
  
 8) DETAIL 5/A-8 ON SHEET A-5A,B SHOULD
 BE 3/A-8. PLEASE CORRECT.
  
 9) PLANS ARE REQUIRED TO BE SPECIFIC
 PER 104.2 OF THE 97 SBC. PLEASE INDICATE
 WHICH ONE OF THE ROOF FRAMING PLANS IS
 TO BE CONSTRUCTED AND CROSS OUT THE
 OTHER SHEET.
  
 10)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
  
 IF YOU HAVE QUESTIONS, PLEASE CALL.
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-01-31 Cont ID  
Sent By sgraham Date 2001-01-31 Time 07:45 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***