Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-02-20 Cont ID  
Sent By mcarsill Date 2001-02-20 Time 12:14 Rev Time 0.00
Received By mcarsill Date 2001-02-20 Time 12:14 Sent To  
Notes
2001-02-20 00:00:001) THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEM TO BE MONITORED BY A LICENSED
 UL LISTED CENTRAL STATION APPROVED
 BY THE FIRE RESCUE DEPARTMENT. THE
 FOLLOWING SIGNALS ARE TO BE SENT,
 WATERFLOW, GENERAL ALARM, TROUNBLE
 AND SUPERVISORY.
 2) FIRE ALARM SYSTEM TO BE CLASS A OR
 FULLY ADDRESSABLE.
 3) SYSTEM AFTER INSTALLATION TO BE
 TESTED WITH FIRE RESCUE PERSONNEL.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-01-17 Cont ID  
Sent By mcarsill Date 2001-01-17 Time 13:14 Rev Time 0.00
Received By mcarsill Date 2001-01-17 Time 13:14 Sent To  
Notes
2001-01-17 00:00:001) VALUE OF JOB APPEARS TO BE UNDER
 VALUED. PLEASE ADJUST VALUE OR SUBMIT
 CONTRACT.
 2) NO CUT SHEETS, WIRING DIAGRAM,
 PROVIDED WITH DRAWINGS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910