Plan Review Details - Permit 01010487
Plan Review Stops For Permit 01010487
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-01-24 Cont ID  
Sent By jwitmer Date 2002-01-24 Time 17:15 Rev Time 0.33
Received By jwitmer Date   Time   Sent To  
Notes
2002-01-24 00:00:00STORM SHUTTERS FIRST FLOOR OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-05-18 Cont ID  
Sent By jwitmer Date 2001-05-18 Time 13:47 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-05-18 00:00:00PROVISO:
  
 1)- WINDOW BUCK ATTACHMENT: PRODUCT
 APPROVAL REPORTS MAY HAVE DETAIL ON THE
 BUCK ATTACHMENT IF NOT THE DESIGN
 PROFESSIONAL WILL BE REQUIRED TO DETAIL
 THE ATTACHMENT.
 2)- PRODUCT APPROVAL REPORTS FOR ALL
 GLAZED OPENINGS WILL BE REQUIRED FOR ALL
 GLAZED OPENINGS. SBCCI REPORT OR DADE
 COUNTY REPORT WILL BE REQUIRED.WPBPOLICY
 (GUIDELINES)FOR GLAZED OPENINGS MUST BE
 ADHERRED TO FOR LARGE PROJECTS.
 3)- ROOFING: WILL BE UNDER SEPERATE
 PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-04-06 Cont ID  
Sent By jwitmer Date 2001-04-06 Time 07:20 Rev Time 0.00
Received By jwitmer Date 2001-05-18 Time 13:45 Sent To  
Notes
2001-04-06 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01010487
 5400 EAST AV
 (OUT PATIENT OFFICE BLVD)
 THE WEITZ CO.
 686-5511
  
 1) SBC 1606.2.6.2. COMPONENTS & CLADDING
 MISSING IS A BUCK ATTACHMENT DETAIL FOR
 WINDOWS & DOORS.
  
 2)- PRODUCT APPROVALS: FOR ALL ROOFING
 SYSTEMS, ALL GLAZED OPENINGS, WINDOWS
 DOORS & SKYLIGHTS WILL REQUIRE PRODUCT
 APPROVAL REPORTS COMPLYING WITH CHAPTERS
 1606/ 1707 OF THE S.B.C. THESE ITEMS CAN
 BE PROVISOED: THE PRODUCT APPROVALS
 WOULD REQUIRE A SEPERATE SUB-PERMIT WITH
 THE ASSOCIATED FEES.
  
 3)- STATE RADON FEES TO BE PAID TO THE
 CITY : $ 148.00.
  
 4)- COUNTY IMPACT FEES,PLANS ARE TO
 STAMPED FOR PAYMENT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-24 Cont ID  
Sent By jwitmer Date 2001-01-24 Time 12:48 Rev Time 5.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-24 00:00:005400 EAST AV. / 01010487
 BUILDING PLAN REVIEW
 1). FL ENERGY CODE 400.ABCD.2 CODE
 COMPLIANCE CERTIFICATION- THE BUILDINGS
 OWNER, THE OWNER ARCHETECT, OR OTHER
 AUTHERIZED AGENT LEGALLY DESIGNATED BY
 THE OWNER SHALL CERTIFY TO THE BUILDING
 OFFICIAL THAT THE BUILDING IS IN COMPLI-
 ANCE WITH THE ENERGY EFFICIENCY CODE. A
 SIGNATURE IS REQUIRED, HIGHLIGHTED IN
 YELLOW HIGHLIGHTER ON ENERGY CALC. SHEET
 2). DISCREPANCIES:
 A). SHEET A-4, NOTE #9 IS TO BE DELETED
 AS PER CONVERSATION WITH ARCH. 01/24/01
 OR LETTER DELETING NOTE #9.
 B). SHEET S-2 IS THE SECOND FLOOR FRAM-
 ING PLAN, SHEET S-3 ALSO INDICATES IT IS
 THE SECOND FLOOR FRAMING PLAN?
 C). STRUCTURAL NOTES ON S-5 SEC.3
 PRECAST, PRESTRESSED CONCRETE NOTE 5.A
 ALL PRESRESSED UNITS TO BE DESIGNED TO C
 ONFORM TO THE LATEST REQUIREMENTS OF THE
 STANDARD BUILDING CODE NOT THE SOUTHERN
 STANDARD CODE.
 3). SBC 1606.2.6.2 COMPONENTS & CLADDING
 A BUCK DETAIL SHOWING ATTACHMENT TO THE
 STRUCTURE WILL BE REQUIRED.
 4). SBC 104.2.2. ADDITIONAL INFORMATION
 SHEET A-15 DETAIL 3&5 SHOW A HI LEG
 TRACK ANCHORED TO THE STRUCTURE ABOVE,
 WHAT SIZE ANCHOR IS TO BE USED, & HOW
 OFTEN?
 5).PRODUCT APPROVALS: FOR ROOFING,ALL
 GLAZED OPENINGS,WINDOWS, DOORS & SKY-
 LIGHRS WILL REQUIRE PRODUCT APPOVAL RE-
 PORTS COMPLYING WITH CHAP.1606/1707 OF
 THE S.B.C.THESE ITEMS CAN BE PROVISOED:
 THE PRODUCT APPROVALLS WOULD REQUIRE A
 SEPERATE SUB-PERMITS WITH THE ASSOCIATED
 FEES.
  
 BUILDING PLAN REVIEW:
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-04-05 Cont ID  
Sent By dpalmer Date 2001-04-05 Time 20:21 Rev Time 0.00
Received By dpalmer Date 2001-04-05 Time 20:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-01-29 Cont ID  
Sent By dpalmer Date 2001-01-29 Time 11:04 Rev Time 0.00
Received By dpalmer Date 2001-01-29 Time 11:04 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-03-29 Cont ID  
Sent By mamini Date 2001-03-29 Time 15:38 Rev Time 1.50
Received By mamini Date 2001-03-29 Time 15:09 Sent To  
Notes
2001-03-29 00:00:00PASSED;
 1. RESPONSES TO PREVIOUS REVIEW COMMENTS
 DATED 1-29-01 SATISFACTORY.
 IF ANY QUESTIONS PLEASE CONTACT 562-659-
 8096 EXT. 8492

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-01-29 Cont ID  
Sent By mgonzale Date 2001-01-29 Time 14:23 Rev Time 0.50
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-29 00:00:00FAILED
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION1. REVISED DUMPSTER AREA AS
 PER OUR STANDARD MINIMUM DETAIL
 DIMENSIONS.
 SEE ATTACHED
 2. PROVIDE DRAINAGE CALCULATIONS TO
 JOSE DEL RIOS, STORM WATER ENGINEER
 1000 45TH STREET WPB FL 33415
 (561) 659 8040 FOR APPROVAL.
 3. PROVIDE POLLUTION CONTROL PLAN
 SHOWING SILT FENCE WITH BALES OF HAY
 FOR ENTIRE PERIMETER OF CONSTRUCTION
 AREA.
 PROVIDE A NOTE STATING COVERAGE FOR
 EXISTING CATCH BASINS WITH SCREENS AND
 BALES OF HAY.
 4. DRIVEWAY APPROACH MUST MEET OUR
 STANDARDS. SEE ATTACHED CWPB STANDARD
 DRIVEWAY APPROACH DETAILS.
 5. PROVIDE IMPERVOIUS AND PERVOIUS
 CALCULATIONS FOR ENTIRE SITE THE TOTAL
 MUST ADD UP TO 100% OF THE TOTAL SITE
 AREA.
 PROVIDE THIS INFORMATION ON A 8 1/2 X11
 SHEET WITH EITHER THE PROPERTY CONTROL
 NUMBER OR THE PROJECT ADDRESS.
 IF ANY QUESTIONS PLEASE FEEL FREE TO
 CONTACT OUR OFFICE .
 561 659 8040 EXT. 2306

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-05-09 Cont ID  
Sent By mcarsill Date 2001-05-09 Time 12:38 Rev Time 0.00
Received By mcarsill Date 2001-05-09 Time 12:38 Sent To  
Notes
2001-05-09 00:00:00RECEIVED FAXED LETTER INDICATING THAT
 ANOTHER FIRE HYDRANT WILL BE INSTALLED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-04-04 Cont ID  
Sent By mcarsill Date 2001-04-04 Time 12:44 Rev Time 0.00
Received By mcarsill Date 2001-04-04 Time 12:44 Sent To  
Notes
2001-04-04 00:00:001) NO FIRE SPRINKLER OR HYDRAULIC
 CALCULATIONS PROVIDED WITH DRAWINGS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-01-17 Cont ID  
Sent By mcarsill Date 2001-01-17 Time 15:00 Rev Time 0.00
Received By mcarsill Date 2001-01-17 Time 15:00 Sent To  
Notes
2001-01-17 00:00:001) ELEVATION DRAWINGS DID NOT DISPLAY
 BUILDING ADDRESS. BUILDING ADDRESS TO
 BE INSTALLED AND COMPLY WITH CITY CODE
 REQUIREMENTS.
 2) AWNINGS PLANNED FOR USE ARE TO BE
 FIRE RETARDANT.
 3) IT APPEARS THAT ANOTHER FIRE HYDRANT
 IS NEEDED NEAR THE BUILDING. THE FIRE
 SPRINKLER SYSTEM CONNECTION FOR THE
 BUILDING SHALL NOT EXCEED 150 FEET FROM
 A FIRE HYDRANT.
 4) PLEASE INDICATE WHAT THE FUTURE RAMP
 AND PLATFORM WILL BE USED FOR. ARE THESE
 WHEN INSTALLED, TEMPORARY OR PERMANANT.
 WHAT CONSTRUCTION TYPE WILL THEY BE.
 5) ELEVATOR TO COMPLY WITH ANSI A17.1
 6) PORTABLE FIRE EXTINGUISHERS WHEN
 INSTALLED, ARE TO BE EQUIPPED WITH A
 CURRENT SERVICE TAG.
 7) PLEASE PROVIDE COMPLETE FIRE
 SPRINKLER SYSTEM DRAWINGS AND HYDRAULIC
 CALCULATIONS TO THIS OFFICE. SEPARATE
 PERMIT REQUIRED.
 8) PLEASE PROVIDE COMPLETE FIRE ALARM
 SYSTEM DRAWINGS TO THIS OFFICE. CUT
 SHEETS, WIRING DIAGRAM, BATTERY
 CALCULATIONS, FLOOR PLANS ARE REQUIRED.
 9) THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM TO BE SUPERVISED BY A
 LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 10) A KNOX-BOX WILL BE REQUIRED FOR
 RAPID FIRE ACCESS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-05-03 Cont ID  
Sent By ndenmark Date 2001-05-03 Time 15:14 Rev Time 0.50
Received By ndenmark Date 2001-05-03 Time 15:14 Sent To  
Notes
2001-05-03 00:00:00PROVISO:
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED PER 1997 SMC 406 INCLUDING
 HORN AND STROBE FOR NOTIFICATION PER
 1996 NFPA 90A
 ALL OTHER PREVIOUS INFORMATION REQUESTED
 EXISTS IN WITH BUILDING PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-04-13 Cont ID  
Sent By pkrauss Date 2001-04-13 Time 14:22 Rev Time 0.50
Received By pkrauss Date 2001-04-13 Time 11:46 Sent To  
Notes
2001-04-13 00:00:00PLEASE PROVIDE THE FOLLOWING
 INFORMATION WITH MECHANICAL PERMIT
 APPLICATION:
  
 O.A. CALCULATIONS AS PER ASHRAE 62-89.
  
 KEY NOTES ON DRAWING A-4 #19 & 20,
 EXHAUSET SHALL BE 10' FROM OR 24" ABOVE
 O.A. INTAKE.ONE OF THE EXHAUST OULETS
 WHEN SCALED ON PLAN IS ONLY 4' 6" FROM
 O.A. INTAKE.
  
 SUBMIT DETAIL ON CONDENSER UNIT STANDS.
  
 AHU'S WITH FAN CAPACITY GREATER THAN
 2,00 CFM SHALL HAVE FAN SHUTDOWN BY
 DUCT SMOKE DETECTOR AS PER 1997 SMC
 406.1 AND HAVE NOTIFICATION TO
 ALARM/STROBE IN NORMALLY OCCUPIED AREAS.
  
 PLEASE INDICATE ON PLAN WHERE THE
 CONDENSATE IS BEING DISPOSED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-02-05 Cont ID  
Sent By ndenmark Date 2001-02-05 Time 15:31 Rev Time 1.00
Received By ndenmark Date 2001-02-05 Time 15:31 Sent To  
Notes
2001-02-05 00:00:00*************DENIED*********************
 1. VENT STACKES AND EXHAUST OUTLETS
 SHALL BE MINIMUM 10 FOOT FROM OUTSIDE
 AIR INTAKE PER 1997 SMC 405SEE A-3
 2. OUTSIDE AIR SCHEDULE AND A/C
 EQUIPMENT SCHEDULES DO NOT MATCH.
 PROVIDE CORRECTED INFORMATION ON
 OUTSIDE AIR TO MATCH EQUIPMENT SUPPLIED.
 3. PROVIDE FIRE DAMPER INSTALLATION
 INFORMATION PER 1997 SMC 610.
 4. EXHAUST FANS FROM RR103 AND RR 103A
 DUCT THROUGH WALL AND UP THROUGH 2ND
 FLOOR. DUCTS FROM 1ST FLOOR NEED TO BE
 ENCLOSED IN SHAFT THROUGH 2ND FLOOR PER
 1997 SMC 610.4.
 5. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-10-01 Cont ID  
Sent By kstevens Date 2001-10-01 Time 13:37 Rev Time 0.33
Received By kstevens Date 2001-10-01 Time 13:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-08-08 Cont ID  
Sent By kstevens Date 2001-08-08 Time 10:03 Rev Time 0.00
Received By kstevens Date 2001-08-08 Time 10:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-07-20 Cont ID  
Sent By jleech Date 2001-07-20 Time 08:22 Rev Time 1.00
Received By jleech Date 2001-07-20 Time 08:22 Sent To  
Notes
2001-07-20 00:00:00REVISION TO PLAN;
 CONDENSATE UNDER GROUND.
 PROVISO; CONDENSATE DRAIN SHOULD BE
 TRAPED AT A/H UNIT.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-04-28 Cont ID  
Sent By kstevens Date 2001-04-28 Time 13:07 Rev Time 1.00
Received By kstevens Date 2001-04-28 Time 13:07 Sent To  
Notes
2001-04-28 00:00:00PLUMBING PLAN REVIEW. SPC-94
  
 PASSED
  
 PROVISO:
  
 AIR-CHAMBERS TO BE ACCESSABLE AND
 RECHARGEABLE. 607.8.2 - 607.8.3
 1-1/4" SUPPLY TO WATER CLOSETS?
  
 SUBMIT REVISED H2O RISER DIAGRAMS BEFORE
 INSPECTIONS.
  
 REVIEW BY KEN STEVENS (561) 569-8096
 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-01-26 Cont ID  
Sent By jleech Date 2001-01-26 Time 09:32 Rev Time 1.75
Received By jleech Date 2001-01-26 Time 09:32 Sent To  
Notes
2001-01-26 00:00:00DENIED;
  
 1.COFFEE ROOM SINKS SHALL COMPLY WITH
 FACBC 4.24.1 THRU 4.24.7.
  
 2.DRINKING FOUNTAIN SHALL COMPLY WITH
 FACBC 4.1.3 (10) AND 4.15. PROVISIONS
 SHALL BE MADE FOR PEOPLE WHO HAVE
 TROUBLE BENDING OR STOOPING. CHECK
 CLEAR FLOOR SPACE, SECOND FLOOR
 DRINKING FOUNTAIN 30"X 48".
  
 3.P-3 (RISER DIAGRAM) HORIZONTAL DRY
 VENTS ARE NOT PERMITED. 94 SPC 914.2.
  
 4.WATER RISER DIAGRAM REQUIRED.
  
 5.PROVIDE RAIN FALL CALCULATIONS, TOTAL
 SQUIRE FOOTAGE OF ROOF AREA FOR EACH
 ROOF DRAIN AND DEGREE OF PITCH FOR
 HORIZONTAL RAIN LEADERS AND STORM
 SEWER. SPC TABLE 1108.1, 1108.2 AND
 1108.4.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-17 Cont ID  
Sent By sgraham Date 2001-05-17 Time 14:54 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***