Plan Review Details - Permit 01010486
Plan Review Stops For Permit 01010486
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-01-24 Cont ID  
Sent By jwitmer Date 2002-01-24 Time 17:26 Rev Time 0.33
Received By jwitmer Date   Time   Sent To  
Notes
2002-01-24 00:00:00STORM SHUTTERS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-08-07 Cont ID  
Sent By jwitmer Date 2001-08-07 Time 08:13 Rev Time 1.33
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-04-11 Cont ID  
Sent By hpiskura Date 2001-04-11 Time 11:06 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-04-11 00:00:00PROVISO: ARCHITECT WILL REVISE CORRIDOR
 DEPTH BEFORE FINAL CORRDORS C09 AND
 C09A
  
 HHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-25 Cont ID  
Sent By hpiskura Date 2001-01-25 Time 10:26 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-25 00:00:00PLEASE PROVIDE A RECENT SIGNED SEALED
 AND DATED PROPERTY SURVEY.
  
 THIS BUILDING WILL BE LOCATED IN AN AH
 FOOD ZONE WITH A BFE OF 17.0' NGVD.
  
 ON SHEET A5 STORAGE ROOM W04 DOES NOT SH
 THE RATED WALL REQUIRED BY SBC 410.2.2.
 PLEASE REVISE AS NECESSARY.
  
 THE FOYERS SHOWN AS C09 AND C09A ON
 SHEET A5 ARE DEAD END CORRIDORS GREATER
 THAN TWENTY FEEET AND ARE PROHIBITTED
 BY SBC TABLE 1004.PLEASE REVISE AS
 NECESSARY
 BEFORE A PERMIT TO CONSTRUCT CAN
 BEISSUED IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY.CALL 233-5025 FOR
 MORE INFORMATION

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-01 Cont ID  
Sent By dpalmer Date 2001-10-01 Time 17:32 Rev Time 0.00
Received By dpalmer Date 2001-10-01 Time 17:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-01-26 Cont ID  
Sent By dpalmer Date 2001-01-26 Time 16:03 Rev Time 0.00
Received By dpalmer Date 2001-01-26 Time 16:03 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-04-02 Cont ID  
Sent By mamini Date 2001-04-02 Time 11:24 Rev Time 2.00
Received By mamini Date 2001-04-02 Time 11:23 Sent To  
Notes
2001-04-02 00:00:00PASSED:
 1. RESPONSES TO PREVIOUS REVIEW COMMENTS
 DATED 1-29-01 SATISFACTORY.
 IF ANY QUESTIONS PLEASE CONTACT 561-659-
 8096 EXT. 8492

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-01-29 Cont ID  
Sent By mgonzale Date 2001-01-29 Time 14:57 Rev Time 0.50
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-29 00:00:00FAILED
 PLEASE REFER TO COMMENTS MADE UNDER
 PERMIT NO 01010487.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-10-01 Cont ID  
Sent By mcarsill Date 2001-10-01 Time 15:01 Rev Time 0.00
Received By mcarsill Date 2001-10-01 Time 15:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-05-24 Cont ID  
Sent By mcarsill Date 2001-05-24 Time 15:22 Rev Time 0.00
Received By mcarsill Date 2001-05-24 Time 15:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-03-29 Cont ID  
Sent By mcarsill Date 2001-03-29 Time 11:10 Rev Time 0.00
Received By mcarsill Date 2001-03-29 Time 11:09 Sent To  
Notes
2001-03-29 00:00:001) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 SUBMITTAL.
 2) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 3) PLEASE INDICATE WHAT PROVISIONS ARE
 MADE FOR FIRE RESCUE ACCESS IF LOSS OF
 POWER OCCURS TO THE SECURITY GATES.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-01-19 Cont ID  
Sent By mcarsill Date 2001-01-19 Time 09:03 Rev Time 0.00
Received By mcarsill Date 2001-01-19 Time 09:02 Sent To  
Notes
2001-01-19 00:00:001) ELEVATION DRAWINGS DID NOT DISPLAY
 BUILDING ADDRESS. BUILDING ADDRESS TO
 BE INSTALLED AND COMPLY WITH CITY CODE
 REQUIREMENTS 3343-00.
 2) AWNINGS PLANNED FOR USE ARE TO BE
 FIRE RETARDANT.
 3) PLEASE PROVIDE COMPLETE FIRE
 SPRINKLER SYSTEM DRAWINGS AND HYDRAULIC
 CALCULATIONS TO THIS OFFICE. SEPARATE
 PERMIT REQUIRED.
 4) PLEASE PROVIDE COMPLETE FIRE ALARM
 SYSTEM DRAWINGS TO THIS OFFICE.
 CUT SHEETS, WIRING DIAGRAM, BATTERY
 CALCULATIONS, FLOOR PLANS ARE REQUIRED.
 5) THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM TO BE SUPERVISED BY A
 LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 6) A KNOX-BOX WILL BE REQUIRED FOR
 RAPID FIRE ACCESS.
 7) PLEASE INDICATE PROPOSED FIRE RESCUE
 ACCESS TO THE NEW RESIDENTIAL FACILITY.
 SLIDING GATES ARE SHOWN ON THE SITE
 PLAN. WHAT PROVISIONS HAVE BEEN MADE
 FOR FIRE AND PARAMEDICAL ACCESS TO THE
 BUILDING. PLEASE PROVIDE SEPARATE PLANS
 AND PERMIT FOR SECURITY GATE. IS IT
 EXPECTED FOR FIRE RESCUE VEHICLES TO
 CLEAR A FOURTEEN FOOT OPENING WHEN THE
 CODE STIPULATES OPENINGS AT TWENTY FEET
 IN CLEAR WIDTH.
 8) NO EMERGENCY LIGHT SHOWN IN DAY ROOMS
 C 10 AND C 14.
 9) PORTABLE FIRE EXTINGUISHERS WHEN
 INSTALLED, ARE TO BE EQUIPPED WITH A
 CURRENT SERVICE TAG.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2001-10-01 Cont ID  
Sent By pkrauss Date 2001-10-01 Time 11:16 Rev Time 0.50
Received By pkrauss Date 2001-10-01 Time 11:04 Sent To  
Notes
2001-10-01 00:00:00 
 PLEASE PROVIDE REVISED OUTSIDE AIR
 CALCULATIONS AS PER ASHRAE 62-89 AS
 WELL AS A REVISED AIR BALANCE SCHEDULE
 SHOWING COMPLIANCE WITH 1997 SMC 501.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-04-23 Cont ID  
Sent By pkrauss Date 2001-04-23 Time 13:58 Rev Time 0.45
Received By pkrauss Date 2001-04-23 Time 12:45 Sent To  
Notes
2001-04-23 00:00:00*******************PROVISO**************
  
  
 CONDENSATE SHALL NOT GO TO THE SANITARY.
  
  
 MECHANICAL PERMIT REQUIRED PRIOR TO ANY
 MECHANICAL WORK BEING STARTED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-02-05 Cont ID  
Sent By ndenmark Date 2001-02-05 Time 14:54 Rev Time 1.00
Received By ndenmark Date 2001-02-05 Time 14:54 Sent To  
Notes
2001-02-05 00:00:00***************DENIED*******************
 1.FIRE DAMPERS ARE NOT SHOWN AT THE
 WALL PENETRATION BETWEEN THE STORAGE
 ROOMS AND THE CORRIDORS WHERE THE
 TRANSFER DUCT AND THE SUPPLY AIR DUCT
 PENETRATE THE WALLS. SHOW LOCATION AND
 INSTALLATION DETAILS PER 1997 SMC 610.6.
 2. OUTSIDE AIR SCHEDULE DOES NOT
 CORRESPOND TO THE ROOF TOP EQUIPMENT
 NUMBERS INDICATED IN THE EQUIPMENT
 SCHEDULE NUMBERS. CORRECT NOTES TO
 REFLECT EQUIPMENT PROVIDED.
 3. THERE ARE TWO RTU 7 INDICATED ON
 A-18AND NO RTU- 6 ON THE A/C PLAN.
 INDICATE CORRECT UNIT NUMBERS ON PLAN.
 4. WILL THERE BE PERSONNELL ACCESS TO
 THE HIGH ROOF OVER THE PARAPET WALL?
 5. FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 NOT SHOWN ON PLAN. ANY EQUIPMENT SERVING
 AREAS USED FOR EGRESS SHALL HAVE FAN
 SHUT DOWN BY DUCT SMOKE DETECTOR WITH
 NOTIFICATION BY BUILDING FIRE ALARM
 SYSTEM PER 1997 SMC 406.2 AND NFPA 96
 4-4.4

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-08-08 Cont ID  
Sent By kstevens Date 2001-08-08 Time 11:05 Rev Time 1.00
Received By kstevens Date 2001-08-08 Time 11:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-08-08 Cont ID  
Sent By kstevens Date 2001-08-08 Time 10:30 Rev Time 1.25
Received By kstevens Date 2001-08-08 Time 10:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-04-28 Cont ID  
Sent By jleech Date 2001-04-28 Time 11:11 Rev Time 2.50
Received By jleech Date 2001-04-28 Time 11:11 Sent To  
Notes
2001-04-28 00:00:00PROVISO;
  
 1.ELECTRIC WATER HEATER #1 SHALL BE
 READLY ACCESSIBLE.
  
 2.SEPARATE PLAN AND APPLICATION REQUIRED
 FOR GAS. PLEASE FOLLOW THE INFORMATION
 REQUIREMENT FORM ATTACHED.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-01-30 Cont ID  
Sent By jleech Date 2001-01-30 Time 10:03 Rev Time 3.00
Received By jleech Date 2001-01-30 Time 10:03 Sent To  
Notes
2001-01-30 00:00:00DENIED;
  
 1.HANDICAP RESIDENCE UNIT A-8 "TYPICAL
 ROOM PLAN", DOOR SWINGS INTO CLEAR
 FLOOR SPACE OF LAV. FACBC 4.19.3.
  
 2.HORIZONTAL RAIN WATER LEADERS AT 1/8"
 PITCH PER. FT. CAN CARRY 5350 SQ. FT.
 NOT 5400 SQ. FT.INCREASE PITCH OR PIPE
 SIZE.
  
 3.GAS PIPING. SUBMIT THE FOLLOWING
 INFORMATION; LONGEST RUN IN FEET,TYPE
 OF PIPE TO BE USED, AND SPECIFCATION
 SHEETS FOR REGULATOR.
  
 4.FLOOR DRAIN IN LAUNDRY ROOMS SHALL BE
 DEEP SEAL TRAPS OR EQUIPED WITH TRAP
 PRIMERS.
  
 5.DRINKING FOUNTAIN TO COMPLY WITH FACBC
 4.1.3(10) AND 4.15. PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 6.EWH-1 RELIEF VALVE SHALL BE PIPED TO
 THE OUTSIDE. 94 SPC 507.8.4.
  
 7.EWH-2 SHEET A-7 NOTE 8 IS NOT SHOWN ON
 WATER RISER OR FLOOR PLAN.
  
 8.ATMOSPHERIC VACUUM BREAKER REQUIRED ON
 GAS WATER HEATERS, WHERE COLD WATER
 ENTERS THE BOTTOM 1/2 OF THE HEATER.
  
 9.APPROVED MECHANICAL AIR CHAMBERS TO BE
 USED SPC 607.8.2 AND MUST BE
 ACCESSIBLE 607.8.3.
  
 10.PAGE A-17A GAS RISER DIAGRAM NOTE
 STATES 3 WATER HEATER LOCATIONS.
 WHERE IS THIRD GAS WATER HEATER?
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-24 Cont ID  
Sent By lmartine Date 2001-05-24 Time 10:17 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-05-24 00:00:00APPLICATION SIGNED BY SHIRLEY GRAHAM
 5/17/01LM