Plan Review Details - Permit 01010422
Plan Review Stops For Permit 01010422
Review Stop FS  
Rev No 1 Status P Date 2001-01-18 Cont ID  
Sent By mcarsill Date 2001-01-18 Time 10:01 Rev Time 0.00
Received By mcarsill Date 2001-01-18 Time 10:01 Sent To  
Notes
2001-01-18 00:00:001) UNDERGROUND FIRE LINE INSTALLATION
 TO COMPLY WITH NFPA 24.
 2) ENTIRE BUILDING TO BE COMPLETELY FIRE
 SPRINKLER PROTECTED. THIS INCLUDES ALL
 MECHANICAL, ELECTRICAL AND SERVICE ROOMS
 ALSO ALL VERTICAL SHAFTS ARE TO BE
 FIRE SPRINKLER PROTECTED.
 3) THE FIRE DEPARTMENT CONNECTION SHOWN
 ON SITE PLAN IS POSITIONED THAT HOSE MAY
 KINK WHEN IT IS CONNECTED. PLEASE
 ADJUST AS NECESSARY.
 4) PLEASE PROVIDE SPARE HEAD BOX AND
 WRENCH.
 5) UNDERGROUND PIPING AND FIRE SPRINKLER
 SYSTEM TO BE PRESSURE TESTED AT 200 PSI.
 FOR TWO HOURS.
 6) FIRE HYDRANT INSTALLATION TO COMPLY
 WITH CITY REQUIREMENTS.
 7) NO CUT SHEETS PROVIDED FOR FIRE
 SPRINKLER HEADS PLANNED FOR USE.
  