Plan Review Details - Permit 01010358
Plan Review Stops For Permit 01010358
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-06-22 Cont ID  
Sent By hpiskura Date 2001-06-22 Time 11:40 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-06-22 00:00:00PROVISO FOR REVISION (5/15/01) RE
 EXTERIOR WALL CONSTRUCTION IS REQUIRED
 TO BE NON-COMBUSTIBLE AND ARCHITECT
 WILL SEND CHANGE WHETHER EXISTING DOOR
 STAYS AND NEW WALL BEHIND OR DESIGN
 EXTERIOR FINISH FOR NEW WALL. TELEPHONE
 CONVERSATION WITH ARCHITECT 6/21/01 HHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-01-22 Cont ID  
Sent By jwitmer Date 2001-01-22 Time 08:40 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-22 00:00:00PROVISO:
 1)- PLEASE PROVIDE PRODUCT APPROVAL FOR
 ALL DOORS BEFORE THE FIRST INSPECTION.
 A DADE COUNTY OR SBCCI REPORT WILL BE
 ACCEPTABLE, PLEASE INCLUDE ALL TECHNICAL
 DRAWINGS THAT ARE REFRENCED IN THE RE-
 PORT. THANK YOU. JIM WITMER.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-07-09 Cont ID  
Sent By dpalmer Date 2001-07-09 Time 18:32 Rev Time 0.00
Received By dpalmer Date 2001-07-09 Time 18:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-06-01 Cont ID  
Sent By jleahy Date 2001-06-01 Time 10:24 Rev Time 1.30
Received By jleahy Date 2001-06-01 Time 10:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-01-19 Cont ID  
Sent By dpalmer Date 2001-01-19 Time 12:04 Rev Time 0.00
Received By dpalmer Date 2001-01-19 Time 12:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-07-10 Cont ID  
Sent By mcarsill Date 2001-07-10 Time 10:16 Rev Time 0.00
Received By mcarsill Date 2001-07-10 Time 10:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-05-29 Cont ID  
Sent By mcarsill Date 2001-05-29 Time 10:32 Rev Time 0.00
Received By mcarsill Date 2001-05-29 Time 10:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-01-11 Cont ID  
Sent By mcarsill Date 2001-01-11 Time 08:21 Rev Time 0.00
Received By mcarsill Date 2001-01-11 Time 08:12 Sent To  
Notes
2001-01-11 00:00:001) PLEASE PROVIDE SEPARATE PLANS AND
 PERMITS FOR THE REMODEL OF THE FIRE
 SPRINKLER SYSTEM.
 2) PLEASE PROVIDE SEPARATE PLANS AND
 PERMITS FOR THE INSTALLATION OF FIRE
 ALARM EQUIPMENT SHOWN ON THE DRAWINGS.
 THE FIRE ALARM AND SPRINKLER SYSTEMS ARE
 TO MONITORED BY A LICENSED UL LISTED
 CENTRAL STATION APPROVED BY THE FIRE
 RESCUE DEPARTMENT. THE FIRE ALARM
 CONTROL PANEL SHOULD BE LOCATED ON
 THE INTERIOR OF THE BUILDING ADJACENT
 TO THE NEW PROPOSED KNOX-BOX LOCATION.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-09-17 Cont ID  
Sent By pkrauss Date 2001-09-17 Time 13:09 Rev Time 0.35
Received By pkrauss Date 2001-09-17 Time 12:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-10 Cont ID  
Sent By pkrauss Date 2001-07-09 Time 15:20 Rev Time 0.25
Received By ydavis Date 2001-07-09 Time 15:11 Sent To  
Notes
2001-07-09 00:00:00 
 NO MECHANICAL PLANS SUBMITTED WITH THIS
 REVISION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-01-22 Cont ID  
Sent By ndenmark Date 2001-01-22 Time 08:18 Rev Time 0.33
Received By ndenmark Date 2001-01-22 Time 08:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-01-21 Cont ID  
Sent By pschmitz Date 2001-01-21 Time 10:13 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-21 00:00:00PROVISO: SEE SHT PFP-1
 B/F ON DOMESTIC WATER.
 NO MORE THAN 2 FIXTURES ON 1/2" COLD.
 VENT ON 2 W/C'S SPC 94 SEC 914.3.4
 END OF COMMENTS.PAUL SCHMITZ