Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-06-05 Cont ID  
Sent By mcarsill Date 2001-06-05 Time 09:44 Rev Time 0.00
Received By mcarsill Date 2001-06-05 Time 09:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-01-08 Cont ID  
Sent By mcarsill Date 2001-01-08 Time 08:46 Rev Time 0.00
Received By mcarsill Date 2001-01-08 Time 08:46 Sent To  
Notes
2001-01-08 00:00:001) SMOKE DETECTORS WHEN INSTALLED ARE TO
 BE A MINIMUM OF THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
 2) FIRE ALARM SYSTEM WHEN ACTIVATED IS
 TO BE AUDIBLE THROUGHOUT THE BUILDING.
 3) FIRE ALARM SYSTEM TO BE CLASS A OR
 FULLY ADDRESSABLE.
 4) FIRE ALARM SYSTEM TO BE MONITORED BY
 A LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910