Plan Review Details - Permit 00121189
Plan Review Stops For Permit 00121189
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-07-31 Cont ID  
Sent By mcarsill Date 2001-07-31 Time 13:33 Rev Time 0.00
Received By mcarsill Date 2001-07-31 Time 13:33 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 1 Status P Date 2000-12-27 Cont ID  
Sent By mcarsill Date 2000-12-27 Time 14:49 Rev Time 0.00
Received By mcarsill Date 2000-12-27 Time 14:49 Sent To  
Notes
2001-01-08 00:00:001) FIRE DEPARTMENT CONNECTION TO BE NO
 FARTHER THAN 150 FEET FROM A FIRE
 HYDRANT.
 2) THE ENTIRE BUILDING IS TO BE
 COMPLETELY FIRE SPRINKLER PROTECTED.
 THIS INCLUDES ALL ELECTRICAL, MECHANICAL
 AND SERVICE ROOMS. ALL VERTICAL SHAFTS
 ARE ALSO TO BE PROPERLY FIRE SPRINKLER
 PROTECTED.
 3) THE STANDPIPE SYSTEM IS REQUIRED TO
 PROVIDE 750 GPM AT 65 PSI AT THE ROOF.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910