Plan Review Stops For Permit 00121189 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2001-07-31 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-07-31 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-07-31 |
Time |
13:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FS |
|
Rev No |
1 |
Status |
P |
Date |
2000-12-27 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-12-27 |
Time |
14:49 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-12-27 |
Time |
14:49 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) FIRE DEPARTMENT CONNECTION TO BE NO | | FARTHER THAN 150 FEET FROM A FIRE | | HYDRANT. | | 2) THE ENTIRE BUILDING IS TO BE | | COMPLETELY FIRE SPRINKLER PROTECTED. | | THIS INCLUDES ALL ELECTRICAL, MECHANICAL | | AND SERVICE ROOMS. ALL VERTICAL SHAFTS | | ARE ALSO TO BE PROPERLY FIRE SPRINKLER | | PROTECTED. | | 3) THE STANDPIPE SYSTEM IS REQUIRED TO | | PROVIDE 750 GPM AT 65 PSI AT THE ROOF. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
|