Plan Review Details - Permit 00121147
Plan Review Stops For Permit 00121147 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-02-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-02-16 |
Time |
07:41 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-02-16 |
Time |
07:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-01-03 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-01-03 |
Time |
18:34 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-01-03 |
Time |
18:34 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | 1)NOTE: PLANS SHOW A MAIN DISCONNECT | | NEXT TO METERCAN AND RISER SHOWS NO MAIN | | DSIC??? PLEASECORRELATE | | | | 2)NOTE: PLEASE NOTE THAT RISER SHOWS 3#1 | | CONDUCTORS IN A 8" CONDUIT? PLEASE CORR- | | -ECT OR CLARIFY. | | | | 3)NOTE: PLANS SHOW A FAN BEING SWITCHED | | IN BEDROOMS AND NO LIGHT? IS IT A FAN/ | | LIGHT? IF SO PLEASE SHOW FANS W/ LT KITS | | | | 4)NOTE: PLEASE NOTE THAT PLANS DO NOT | | SHOW THE DISC REQ`D FOR A/C CU. PLEASE | | SHOW PER 440-11 | | | | 5)NOTE: PLEASE NOTE MISSING OUTLET FOR | | CU PER MECH CODE 309.1 AND/OR GFI OUTLET | | MISSING IN REAR OF DWELLING PER 210-52E | | THAT MAY SERVE AS GFI FOR CU. | | | | 6)NOTE: PLEASE SHOW OUTLET INFRONT OF | | DWELLING AS GFI PER 210-8 | | | | 7)NOTE: PLEASE KW FOR ALL ON PANEL SCHED | | -ULE AND SHOW LOAD CACULATIONS PER 215-5 | | | | 8)NOTE: PLEASE SHOW THE REQ`D DEDICATED | | BATH(S) CIRCUIT(S) PER 210-11-C-3 | | MUST BE #12 AND 20A | | | | 9)NOTE: PLEASE NOTE MISSING OUTLETS PER | | 210-52, 2` OF WALL SPACE. | | | | 10)NOTE: PLEASE NOTE THAT LOCATION OF | | SD IN COMMON AREA IS SHOWN TOO CLOSE TO | | KITCHEN. PLEASE CHECK NFPA FOR SD SPAC- | | -ING REQ`MENTS | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 659-8096 EXT 8372 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2001-02-22 |
|
|
Cont ID |
|
Sent By |
fknapp |
Date |
2001-02-22 |
Time |
11:00 |
Rev Time |
0.00 |
Received By |
fknapp |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2001-02-22 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-01-02 |
Time |
07:54 |
Rev Time |
0.25 |
Received By |
pkrauss |
Date |
2001-01-02 |
Time |
07:54 |
Sent To |
|
|
Notes |
2001-02-22 00:00:00 | MECHANICAL PERMIT ON HOLD FOR A | | MECHANICAL CONTRAACTOR TO BE ASSIGNED. | | | | PLANS OKAY. | | | | PHK 2/22/01 | 2001-01-08 00:00:00 | SHOW CONDENSING UNIT LOCATION. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2001-01-02 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-01-02 |
Time |
07:57 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2001-01-02 |
Time |
07:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2001-02-22 |
|
|
Cont ID |
|
Sent By |
fknapp |
Date |
2001-02-22 |
Time |
11:01 |
Rev Time |
2.00 |
Received By |
fknapp |
Date |
2001-02-22 |
Time |
11:01 |
Sent To |
|
|
Notes |
2001-02-22 00:00:00 | | | | | ************BUILDING PROVISO************ | | | | SBC 104.2.2 | | | | 1) PROVIDE 2 CURRENT COMPLETE COPIES OF | | SBCCI OR METRO DADE PRODUCT APPROVALS | | FOR ALL EXTERIOR DOORS TO BE USED. | | | | PLEASE SUBMIT PRIOR TO INSTALLATION. | | | | 2) PROVIDE STORM PANEL INFORMATION WITH | | INSTALLATION SCHEDULE AND KEY PLAN WITH | | SPECIFIC ANCHORS AND MOUNTING TO BE USED | | FOR ALL NON-IMPACT GLAZING UNDER | | SEPARATE PERMIT. | | | | 3) PROVIDE MECHANICAL CONTRACTOR WITH | | MECHANICAL PERMIT APPLICATION. | | | | 4) PROVIDE ROOFING CONTRACTOR WITH | | ROOFING PERMIT APPLICATION. | | | | ANY QUESTIONS PLEASE CALL, | | FRANK KNAPP | | BUILDING PLAN REVIEW | | DEPARTMENT OF CONSTRUCTION SERVICES | | CITY OF WEST PALM BEACH | | (561) 659-8096 EXT. 8392 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2001-01-16 |
|
|
Cont ID |
|
Sent By |
fknapp |
Date |
2001-01-16 |
Time |
10:49 |
Rev Time |
4.00 |
Received By |
fknapp |
Date |
2001-01-16 |
Time |
10:49 |
Sent To |
|
|
Notes |
2001-01-16 00:00:00 | | | | | **************BLDG UNSAT**************** | | | | SBC 104.2.2 | | | | 1) PROVIDE 2 CURRENT COMPLETE COPIES OF | | SBCCI OR METRO DADE PRODUCT APPROVALS | | FOR: | | ALL EXTERIOR DOORS | | GLASS BLOCK | | ROOF COVERING | | | | 2) PROVIDE STORM PANEL INFORMATION WITH | | INSTALLATION SCHEDULE AND KEY PLAN WITH | | SPECIFIC ANCHORS AND MOUNTING TO BE USED | | FOR ALL NON-IMPACT GLAZING. | | | | 3) PROVIDE ENERGY CALCULATIONS THAT HAVE | | SIGNATURE OF OWNER/AGENT. | | | | 4) BEFORE A PERMIT TO CONSTRUCT CAN BE | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | BEACH CO.,THE PERMIT PLANS STAMPED BY | | THEM AND THE RECEIPT ATTACHED TO THE | | PERMIT APPLICATION. | | | | 5) PROVIDE NOC RECORDED WITH THE CLERK | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | 6)PROVIDE REVISED VALUE OF ALL MATERIALS | | AND LABOR, VALUE IS LOW FOR SCOPE OF | | WORK TO BE DONE. | | | | ANY QUESTIONS PLEASE CALL, | | FRANK KNAPP | | BUILDING PLAN REVIEW | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | (561) 659-8096 EXT. 8392 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-12-28 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2000-12-28 |
Time |
10:47 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|