Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-16 Cont ID  
Sent By dpalmer Date 2001-02-16 Time 07:41 Rev Time 0.00
Received By dpalmer Date 2001-02-16 Time 07:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-03 Cont ID  
Sent By dpalmer Date 2001-01-03 Time 18:34 Rev Time 0.00
Received By dpalmer Date 2001-01-03 Time 18:34 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLANS SHOW A MAIN DISCONNECT
 NEXT TO METERCAN AND RISER SHOWS NO MAIN
 DSIC??? PLEASECORRELATE
  
 2)NOTE: PLEASE NOTE THAT RISER SHOWS 3#1
 CONDUCTORS IN A 8" CONDUIT? PLEASE CORR-
 -ECT OR CLARIFY.
  
 3)NOTE: PLANS SHOW A FAN BEING SWITCHED
 IN BEDROOMS AND NO LIGHT? IS IT A FAN/
 LIGHT? IF SO PLEASE SHOW FANS W/ LT KITS
  
 4)NOTE: PLEASE NOTE THAT PLANS DO NOT
 SHOW THE DISC REQ`D FOR A/C CU. PLEASE
 SHOW PER 440-11
  
 5)NOTE: PLEASE NOTE MISSING OUTLET FOR
 CU PER MECH CODE 309.1 AND/OR GFI OUTLET
 MISSING IN REAR OF DWELLING PER 210-52E
 THAT MAY SERVE AS GFI FOR CU.
  
 6)NOTE: PLEASE SHOW OUTLET INFRONT OF
 DWELLING AS GFI PER 210-8
  
 7)NOTE: PLEASE KW FOR ALL ON PANEL SCHED
 -ULE AND SHOW LOAD CACULATIONS PER 215-5
  
 8)NOTE: PLEASE SHOW THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) PER 210-11-C-3
 MUST BE #12 AND 20A
  
 9)NOTE: PLEASE NOTE MISSING OUTLETS PER
 210-52, 2` OF WALL SPACE.
  
 10)NOTE: PLEASE NOTE THAT LOCATION OF
 SD IN COMMON AREA IS SHOWN TOO CLOSE TO
 KITCHEN. PLEASE CHECK NFPA FOR SD SPAC-
 -ING REQ`MENTS
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-02-22 Cont ID  
Sent By fknapp Date 2001-02-22 Time 11:00 Rev Time 0.00
Received By fknapp Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-02-22 Cont ID  
Sent By jleech Date 2001-01-02 Time 07:54 Rev Time 0.25
Received By pkrauss Date 2001-01-02 Time 07:54 Sent To  
Notes
2001-02-22 00:00:00MECHANICAL PERMIT ON HOLD FOR A
 MECHANICAL CONTRAACTOR TO BE ASSIGNED.
  
 PLANS OKAY.
  
 PHK 2/22/01
2001-01-08 00:00:00SHOW CONDENSING UNIT LOCATION.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-01-02 Cont ID  
Sent By jleech Date 2001-01-02 Time 07:57 Rev Time 0.25
Received By jleech Date 2001-01-02 Time 07:55 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-02-22 Cont ID  
Sent By fknapp Date 2001-02-22 Time 11:01 Rev Time 2.00
Received By fknapp Date 2001-02-22 Time 11:01 Sent To  
Notes
2001-02-22 00:00:00 
  
 ************BUILDING PROVISO************
  
 SBC 104.2.2
  
 1) PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR ALL EXTERIOR DOORS TO BE USED.
  
 PLEASE SUBMIT PRIOR TO INSTALLATION.
  
 2) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING UNDER
 SEPARATE PERMIT.
  
 3) PROVIDE MECHANICAL CONTRACTOR WITH
 MECHANICAL PERMIT APPLICATION.
  
 4) PROVIDE ROOFING CONTRACTOR WITH
 ROOFING PERMIT APPLICATION.
  
 ANY QUESTIONS PLEASE CALL,
 FRANK KNAPP
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8392

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-01-16 Cont ID  
Sent By fknapp Date 2001-01-16 Time 10:49 Rev Time 4.00
Received By fknapp Date 2001-01-16 Time 10:49 Sent To  
Notes
2001-01-16 00:00:00 
  
 **************BLDG UNSAT****************
  
 SBC 104.2.2
  
 1) PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR:
 ALL EXTERIOR DOORS
 GLASS BLOCK
 ROOF COVERING
  
 2) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
  
 3) PROVIDE ENERGY CALCULATIONS THAT HAVE
 SIGNATURE OF OWNER/AGENT.
  
 4) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
  
 5) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 6)PROVIDE REVISED VALUE OF ALL MATERIALS
 AND LABOR, VALUE IS LOW FOR SCOPE OF
 WORK TO BE DONE.
  
 ANY QUESTIONS PLEASE CALL,
 FRANK KNAPP
 BUILDING PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8392

Review Stop Z ZONING
Rev No 1 Status P Date 2000-12-28 Cont ID  
Sent By sgraham Date 2000-12-28 Time 10:47 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved