Plan Review Details - Permit 00121123
Plan Review Stops For Permit 00121123
Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-02-15 Cont ID  
Sent By pkrauss Date 2001-02-15 Time 09:52 Rev Time 0.33
Received By pkrauss Date 2001-02-15 Time 09:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-12-26 Cont ID  
Sent By jleech Date 2000-12-26 Time 14:03 Rev Time 0.33
Received By jleech Date 2000-12-26 Time 14:03 Sent To  
Notes
2001-01-08 00:00:001.LIST CFM'S FOR EACH DROP.
  
 2.R/A CANNOT BE RESTRICTED TO ONE ROOM.
 IS A/H IN GARAGE? IF SO DROPS AND R/A
 CANNOT BE LOCATED THERE.
  
 3.CAN 12" DUCT CARRY ENOUGH CFM'S TO
 SUPPLY 5 DROPS?
  
 A/C PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8377