2001-01-08 00:00:00 | 1) FIRE ALARM SYSTEM TO BE CLASS A OR | | FULLY ADDRESSABLE. | | 2) FIRE ALARM SYSTEM WHEN ACTIVATED IS | | TO BE AUDIBLE THROUGHOUT BUILDING. | | 3) SMOKE DETECTORS WHEN INSTALLED TO BE | | A MINIMUM OF THREE FEET FROM AIR | | CONDITIONER DIFFUSERS. | | 4) BACKFLOW DEVICE TO BE EQUIPPED WITH | | TAMPER SWITCHES. | | 5) FIRE ALARM SYSTEM IS TO BE MONITORED | | BY A UL LISTED CENTRAL STATION | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | 6) SYSTEM TO BE COMPLETELY TESTED | | AFTER INSTALLATION WITH FIRE RESCUE. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
|