Plan Review Details - Permit 00120309
Plan Review Stops For Permit 00120309
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-01-16 Cont ID  
Sent By lsmith Date 2001-01-16 Time 15:04 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2001-03-11 Cont ID  
Sent By dpalmer Date 2001-03-11 Time 13:26 Rev Time 0.00
Received By dpalmer Date 2001-03-11 Time 13:26 Sent To  
Notes
2001-03-11 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT MORE ELECTRICAL
 DETAIL. UNCLEAR IS WHAT IS REVISED?
 PLEASE SUBMIT, PLEASE CALL IF THERE ARE
 ANY QUESTIONS.
  
 SHEET FOR CLARIFICATION MAY BE FAXED
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372
 FAX 659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-01-16 Cont ID  
Sent By dpalmer Date 2001-01-16 Time 09:54 Rev Time 0.00
Received By dpalmer Date 2001-01-16 Time 09:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-12-28 Cont ID  
Sent By dpalmer Date 2000-12-28 Time 18:58 Rev Time 0.00
Received By dpalmer Date 2000-12-28 Time 18:58 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: SAME AS FIRST SET OF REVIEW NOTE
 -S. PLEASE SHOW WHERE POWER IS COMING
 FORM AND SIZE OF DISCONNECT!! IS POWER
 GOING TO BE BY OTHERS? IS IT EXISTING?
 PLEASE CLARIFY AS ASKED FOR ON FIRST
 REVIEW.
  
 2)NOTE: NEED TO PROVIDE NOC BEFORE
 PERMIT IS ISSUED.
 FEES OWED ON VALUE INCREASE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 FIRST BEFORE RESUBMITTING.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-18 Cont ID  
Sent By dpalmer Date 2000-12-18 Time 07:36 Rev Time 0.00
Received By dpalmer Date 2000-12-18 Time 07:36 Sent To  
Notes
2001-01-08 00:00:00*********************UNSAT *************
  
 1)NOTE: PLEASE SEE ELECTRICAL PLAN.
 16-400WATT FIXTURES AND A LOAD SHOWN AT
 62.4 AMPS? PLEASE PROVIDE CLARIFICATION
 ON LOAD AND LIGHTING.
  
 2)NOTE: PLEASE SUBMIT DETAIL ON WHERE
 THE POWER IS COMING FROM. DETAIL ON
 THE EXT DISC SWITCH BEING RATED FOR
 THE LOAD SHOWN.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop Z ZONING
Rev No 1 Status P Date 2000-12-14 Cont ID  
Sent By sgraham Date 2000-12-14 Time 07:58 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***