Plan Review Details - Permit 00111378
Plan Review Stops For Permit 00111378
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-01-25 Cont ID  
Sent By jwitmer Date 2001-01-25 Time 16:34 Rev Time 3.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-25 00:00:00PROVISO: GLAZED EXTERIOR OPENINGS WILL
 REQUIRE PRODUCT APPROVAL REPORTS AS WELL
 AS SEPERATE PERMITS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-12-21 Cont ID  
Sent By hpiskura Date 2000-12-21 Time 10:45 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00LETTER W/APPLICATION

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-12-14 Cont ID  
Sent By dpalmer Date 2000-12-14 Time 18:56 Rev Time 0.00
Received By dpalmer Date 2000-12-14 Time 18:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-03-07 Cont ID  
Sent By mcarsill Date 2001-03-07 Time 08:03 Rev Time 0.00
Received By mcarsill Date 2001-03-07 Time 08:03 Sent To  
Notes
2001-03-07 00:00:001) COULD NOT LOCATE FIRE ALARM SYSTEM
 EQUIPMENT WITHIN TENANT SPACE. CALLED
 CONTRACTOR ON 3-06-01 AND ADVISED THEM
 OF THIS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-01-23 Cont ID  
Sent By mcarsill Date 2001-01-23 Time 14:50 Rev Time 0.00
Received By mcarsill Date 2001-01-23 Time 14:50 Sent To  
Notes
2001-01-23 00:00:001) IT APPEARS THAT THE PREVIOUS PLAN
 REVIEW COMMENTS HAVE NOT BEEN
 ADDRESSED. PLEASE ADDRESS THE COMMENTS
 PROVIDED TO YOU BY THE FIRE RESCUE
 DEPARTMENT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-12-11 Cont ID  
Sent By mcarsill Date 2000-12-11 Time 12:07 Rev Time 0.00
Received By mcarsill Date 2000-12-11 Time 12:07 Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 2) NO FIRE ALARM EQUIPMENT SHOWN ON
 PLANS. FIRE ALARM SYSTEM LEGEND LOCATED
 ON PLANS BUT NO DEVICES COULD BE FOUND.
 3) NO INTERIOR FINISH INFORMATION
 INCLUDED IN PLANS.
 4) DOOR TO DRESSING ROOM 1, HANDICAPPED
 APPEARS TO INTERFERE WITH EXITING WHEN
 DOOR IS OPENED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-02-06 Cont ID  
Sent By ndenmark Date 2001-02-06 Time 08:27 Rev Time 0.33
Received By ndenmark Date 2001-02-06 Time 08:27 Sent To  
Notes
2001-02-06 00:00:00PROVISO:
 1. FIELD VERIFY EXISTING FIRE DAMPERS
 ATTENANT SEPARATION WALL.
 2. LOCAL CODE REQUIRES MINIMUM 18"
 C;EARANCE BETWEEN ROOF SURFACE AND
 BOTTOM OF SUPPORT STRUCTURE OF STAND.
 3. AHU TO HAVE ACCESS FOR SERVICE AND
 THE REMOVAL OF EQUIPMENT PER 1997 SMC
 304.2.1
 4. OVERFLOW PROTECTION REQUIRED FOR AHU
 PER 1997 SMC 304.8.6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-12-20 Cont ID  
Sent By ndenmark Date 2000-12-20 Time 13:09 Rev Time 0.50
Received By ndenmark Date 2000-12-20 Time 13:09 Sent To  
Notes
2001-01-08 00:00:00************DENIED**********************
 1. PROVIDE INFORMATION ON CONDENSING
 UNIT LOCATION AND REFRIGERANT PIPING
 LOCATION THROUGH BUILDING
 2. AHU TO HAVE ACCESS FOR SERVICE AND
 THE REMOVAL OF EQUIPMENT AS 1997 SMC
 304.2.1 PROVIDE SERVICE CLEARANCE
 REQUIREMENTS PER MANUFACTURES INSTALLATI
 ON INSTRUCTIONS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-03-09 Cont ID  
Sent By lmartine Date 2001-03-09 Time 16:11 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-03-09 00:00:00APPROVED BY JOHN LEECH, SEE APPL. AND
 PLANS.LM3/9/01

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-12-10 Cont ID  
Sent By pschmitz Date 2000-12-10 Time 13:35 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW PAUL SCHMITZ
 DENIED
 (1) SHT A-2 DRESSING RM #1 TO COMPLY W/
 FACBC-97 SEC 4.35.2 A CLEAR FLR SPACE TO
 ALLOW A PERSON IN A WHEEL CHAIR TO MAKE
 A 180-DEGREE TURN, SHALL BE PROVIDED.
 EVERY ACCESSIBLE DRESSING RM SHALL HAVE
 A FIXED BENCH, 24" X 48" AT 17"TO 19"
 ABOVE FF.
 (2) SHT A-2 H/C REST RM'S SHALL COMPLY
 W/FACBC 4.1,4.2,4.3,SPC 94 SEC 407.2.2
 REST RM'S SHALL BE INDEBILY POSTED FOR
 INTENDED USE, BE AVILABLE TO PATRONS
 WITH OUT RESTRICTION, TO HAVE A CLEARLY
 DEFINED ROUTE ON THE PLANS.
 (3) SHT P-2 AIR CHAMBERS TO COMPLY WITH
 SPC 94 SEC 607.8.3, TO BE ACCESSIBLE &
 RECHARGEABLE.
 END OF COMMENTS PAUL SCHMITZ
 561-659-8096 X 8233