|
 |
 |
 |
 |
 |
Plan Review Details - Permit 00111239
Plan Review Stops For Permit 00111239 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2000-12-04 |
|
|
Cont ID |
|
Sent By |
drunnels |
Date |
2000-12-04 |
Time |
09:24 |
Rev Time |
1.00 |
Received By |
drunnels |
Date |
2000-12-04 |
Time |
09:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2000-12-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-12-21 |
Time |
15:34 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-12-21 |
Time |
15:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2000-12-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-12-07 |
Time |
07:48 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-12-07 |
Time |
07:48 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE LABEL PANELS AND ALL | | RISER EQUIPMENT TO CLARIFY WHICH ONE IS | | WHICH. THE RISER ON THE RIGHT DOES NOT | | SHOW FEEDING A 100 A PANEL?? | | | | 2)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | #`S ON PLANS AND CORRELATE WITH PANEL | | SCHEDULES. | | | | 3) NOTE: PLEASE SEE ELEC RISER#2 WIRE | | FEEDING 100A PANEL #4?? PLEASE SEE 310- | | -16 FOR CORRECT WIRE SIZE.(75) COLULMN. | | ALSO PLEASE SEE 1-#4? | | | | 4)NOTE: PLEASE SEE PANEL SCHEDULE, #14 | | WIRE ON 20A BRKR. | | | | 5)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS | | FOR SERVICE AND NEW WORK. | | | | 6)NOTE: PLEASE CLARIFY ON PLAN THAT ALL | | KITCHEN ELECTRICAL WORK IS EITHER EXIST- | | -ING OR NEW. | | | | 7)NOTE: PLEASE SHOW WHERE THE 100A PANEL | | IS BEING FED? IS IT THE 200A PANEL ON | | THE SAME WALL. THE PLAN NEEDS TO SHOW | | THE SEPARATION OF CIRCUITS FROM EACH | | TENANT SPACE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL OR SET UP A MEETING . | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW. | | 659-8096 ETX 8372 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2000-11-29 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-11-29 |
Time |
14:25 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-11-29 |
Time |
14:25 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) APPROVED PANIC HARDWARE REQUIRED ON | | DOOR # 2 LOCATED NEAR THE HALLWAY. THE | | DOUBLE DOORS LABELED # 5 MUST BE | | EQUIPPED WITH A SIGN AS INDICATED IN THE | | NOTES SECTION. | | 2) OCCUPANT LOAD HAS BEEN COUNTED TO BE | | 153 PERSONS INSTEAD OF 151 PERSONS AS | | NOTED ON THE PLANS. THE FINAL OCCUPANT | | LOAD WILL BE DETERMINED BY THIS OFFICE. | | 3) PORTABLE FIRE EXTINGUISHERS ARE TO | | BE PROVIDED. | | | | APPROVED PROVISO: | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2001-01-02 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2001-01-02 |
Time |
13:44 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2001-01-02 |
Time |
13:44 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | IT APPEARS THAT NO WORK IS TO BE DONE ON | | THE HVAC SYSTEM. INSPECTION REQUIRED TO | | ASSURE NO DUCTS TO PENETRATE RATED WALLS | | WITHOUT PROPER PROTECTION PER 1997 SMC | | 610. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2000-12-04 |
|
|
Cont ID |
|
Sent By |
drunnels |
Date |
2000-12-04 |
Time |
09:26 |
Rev Time |
0.00 |
Received By |
drunnels |
Date |
2000-12-04 |
Time |
09:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-01-02 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-01-02 |
Time |
10:25 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2001-01-02 |
Time |
10:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2000-12-06 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2000-12-06 |
Time |
16:53 |
Rev Time |
1.00 |
Received By |
jleech |
Date |
2000-12-06 |
Time |
16:53 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | DENIED; | | | | 1.MENS ROOM MUST HAVE A URINAL. SPC | | TABLE 407 NOTE # 3 | | | | 2.CALCULATE USABLE SQUIRE FOOTAGE PER | | 407.1.3 TO FIND REQUIRED BATHROOM | | FACILITYS IN TABLE 407 | | | | 3.HANDICAP BATHROOMS MUST MEET REQUIRE- | | MENTS OF THE 97 FACBC CODE FOR | | REMODELING. | | | | 4.SHOW RESTAURANT EQUIPMENT SCHEDULE | | AND LOCATION OF EQUIPMENT.INDIRECT | | DRAINAGES TO DRAIN INTO FLOOR SINKS. | | | | 5.SHOW SANITARY RISER FOR KITCHEN | | EQUIPMENT. | | | | 6.GREASE TRAP REQUIREMENTS BY UTILITYS | | RODNEY COMPO ORD. #2938-96. | | | | 7.SHOW H2O RISER DIAGRAM. | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8377 |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |