Plan Review Details - Permit 00111172
Plan Review Stops For Permit 00111172
Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-03-21 Cont ID  
Sent By dpalmer Date 2001-03-21 Time 19:17 Rev Time 0.00
Received By dpalmer Date 2001-03-21 Time 19:17 Sent To  
Notes
2001-03-21 00:00:00SAME NOTES AS PROVISO

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-01-09 Cont ID  
Sent By dpalmer Date 2001-01-09 Time 18:44 Rev Time 0.00
Received By dpalmer Date 2001-01-09 Time 18:40 Sent To  
Notes
2001-01-09 00:00:00************** REVISION ****************
  
 1)NOTE: PLANS NEED TO BE REVISED
 SHOWINGALL MEANS OF EGRESS LIGHTING PER
 210-70.
  
 2)NOTE: PLEASE LABEL DEDICATEDBATH(S)
 PER 210-11-C-3.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE FINAL ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-13 Cont ID  
Sent By dpalmer Date 2000-12-13 Time 20:21 Rev Time 0.00
Received By dpalmer Date 2000-12-13 Time 20:21 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS PER
 NFPA-72 2-2.1.1.1
  
 2)NOTE: PLEASE SEE THE AIC RATING FOR
 BRKRS AT PANEL WERE SUBMITTED. THIS IS
 CORRECT AND NEEDED BUT NO AIC RATING FOR
 MAIN WAS SHOWN. PLEASE DO SO. PER 110-9
  
 3)NOTE: PLEASE CLARIFY ANY OF THE GFI
 CIRCUITS SHOWN ON PANEL SCHEDULEFOR
 BATH(S). PER 210-11-C-3
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESITONS
 PLEASE CALL.
  
 DEWEWY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-12-05 Cont ID  
Sent By jleech Date 2000-12-05 Time 19:19 Rev Time 0.25
Received By jleech Date 2000-12-05 Time 19:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-12-05 Cont ID  
Sent By jleech Date 2000-12-05 Time 19:20 Rev Time 0.25
Received By jleech Date 2000-12-05 Time 19:20 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2001-02-21 Cont ID  
Sent By mmclean Date 2001-02-21 Time 14:48 Rev Time 0.10
Received By mmclean Date 2001-02-21 Time 14:48 Sent To  
Notes
2001-02-21 00:00:00OK PER LOU H

Review Stop Z ZONING
Rev No 1 Status P Date 2001-02-21 Cont ID  
Sent By mmclean Date 2001-02-21 Time 14:49 Rev Time 1.00
Received By mmclean Date 2001-02-21 Time 14:49 Sent To  
Notes
2001-02-21 00:00:00OK PER SHIRLEY G 12/05/2000 DR