Plan Review Details - Permit 00111162
Plan Review Stops For Permit 00111162
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-01-09 Cont ID  
Sent By dpalmer Date 2001-01-09 Time 19:34 Rev Time 0.00
Received By dpalmer Date 2001-01-09 Time 19:34 Sent To  
Notes
2001-01-09 00:00:00***************** UNSAT ***************
  
 1)NOTE:PLEASE SHOW ALL MEANS OF EGRESS
 LIGHTING REQ`D PER 210-70 OF THE NEC.
  
 2)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GF/GFI
 PROCTECTED PER 210-8-A-6.
  
 3)NOTE: PLEASE SEE MISSING OUTLETS PER
 210-52. 2`,6`,12` RULE.
  
 PLEASE REVISE AND SUBMIT THE ABOVE INFOR
 MATION FOR REVIEW BEFORE FINAL ELECTRICA
 L INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PLAMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-13 Cont ID  
Sent By dpalmer Date 2000-12-13 Time 20:34 Rev Time 0.00
Received By dpalmer Date 2000-12-13 Time 20:34 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ***************
  
 1)NOTE; AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 SHOWN AS GFI/GFI PROTECTED.
  
 2)NOTE: PLEASE SEE MISSING OUTLET PER
 210-52 FRONT BEDROOM.
  
 3)NOTE:PLEASE NOTE THAT NO SWITCHES ORR
 MEANS OF EGRESS LIGHTING IS SHOWN IN
 MAIN/LIVING ROOM?? PER 210-70
 PLEASE SHOW
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-12-05 Cont ID  
Sent By jleech Date 2000-12-05 Time 19:47 Rev Time 0.25
Received By jleech Date 2000-12-05 Time 19:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-12-05 Cont ID  
Sent By jleech Date 2000-12-05 Time 19:47 Rev Time 0.25
Received By jleech Date 2000-12-05 Time 19:47 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2001-01-25 Cont ID  
Sent By wlehnhar Date 2001-01-25 Time 10:27 Rev Time 0.10
Received By wlehnhar Date   Time   Sent To  
Notes
2001-01-25 00:00:00OK PER LOU HATTEN 12-26-2001 WL

Review Stop Z ZONING
Rev No 1 Status P Date 2000-12-05 Cont ID  
Sent By sgraham Date 2000-12-05 Time 07:41 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved