Plan Review Stops For Permit 00110939
Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-03-08 Cont ID  
Sent By pkrauss Date 2001-03-07 Time 09:03 Rev Time 0.45
Received By pkrauss Date 2001-03-07 Time 09:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-02-23 Cont ID  
Sent By pkrauss Date 2001-02-23 Time 08:36 Rev Time 0.40
Received By pkrauss Date 2001-02-23 Time 08:36 Sent To  
Notes
2001-02-23 00:00:00*******************DENIED***************
  
 PROVIDE CALCULATIONS FOR VENTILATION IN
 MECHANICAL ROOM AS PER 1997 SMC 1105.7.1
  
 PROVIDE DETAIL FOR RELIEF VENT PIPING
 AND TERMINATION AS PER 1997 SMC 1105.9.
 ALSO INDICATE REFRIGERANT LEAK
 DETECTOR WITH HORN/STROBE OUTSIDE
 ENTRANCE TO MECHANICAL ROOM AS WELL AS
 IN MECHANICAL ROOM AS REQUIRED PER 97
 SMC 1105.3.
  
 INDICATE LOCATION OF BREATHING
 APPARATUS 97 SCM 1105.8.
  
 SHOW WHERE MAKE-UP AIR IS FOR THE
 EXISTING AHU THAT SUPPLIES A CORE AREA.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-12-04 Cont ID  
Sent By ndenmark Date 2000-12-04 Time 09:52 Rev Time 0.25
Received By ndenmark Date 2000-12-04 Time 09:52 Sent To  
Notes
2001-01-08 00:00:00PROVIDE INFORMATION ON EQUIPMENT AND
 COMPLIANCE WITH 1997 SMC CH. 11 AND
 ASHRAE 15 FOR MECHANICAL ROOMS