Plan Review Details - Permit 00110723
Plan Review Stops For Permit 00110723
Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-02-12 Cont ID  
Sent By dpalmer Date 2002-02-12 Time 19:50 Rev Time 0.00
Received By dpalmer Date 2002-02-12 Time 19:50 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-01-22 Cont ID  
Sent By dpalmer Date 2002-01-22 Time 11:38 Rev Time 0.00
Received By dpalmer Date 2002-01-22 Time 11:38 Sent To M
Notes
2002-01-22 00:00:00*************** UNSAT ******************
  
 1) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 2) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
 FRONT MISSING
  
 3) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.2
 MECHANICAL CODE.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 SHOWN ON ONE PANEL, BUT NOT THE OTHER?
  
 5)NOTE: PLEASE NOTE MISSING HALL OUTLET
 PER 210-52 H
  
 6)NOTE: PLEASE NOTE CLEARENCE FOR AHU
 DISC, FIRST FLOOR 110-26. ORIG PLANS
 SHOW DISC IN UNIT?
  
 7)NOTE: PLEASE NOTE MISSING FOOTER STEEL
 PER 250-50 AND ON ORIG PLANS?
  
 8)NOTE: PLEASE NOTE PANELS ARE SHOWN
 AT 150A AND PANEL SCHEDULES ARE SHOWN AT
 300AMPS??
  
 9)NOTE: PLEASE NOTE POOL HEATER SHOWN ON
 PANEL SCHEDULES BUT NOT, IN LOAD CALCS??
  
 10)NOTE: PLEASE NNOTE TWO 3000W WATER
 HEATERS SHOWN ON SCHEDULES, BUT ONLY
 ONE 4500W ON LOAD CALCS???
  
 11)NOTE: PLEASE NOTE, PLANS ARE STILL
 SHOWING EXISTING HOUSE GL? PLEASE NOTE
 THIS IS NOT REALLY EXSITING SINCE THE
 ENTIRE STRUCTURE IS RE-DONE?
 PLEASE CLARIFY PLANS SHOW NEW FRONT
 HOUSE SERVICE? AND WHAT ABOUT SERIVCE TO
 ANY OTHER HOUSE? IS THERE ARE "BACK"
 HOUSE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THEREARE ANYQUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-02-01 Cont ID  
Sent By dpalmer Date 2001-02-01 Time 11:45 Rev Time 0.00
Received By dpalmer Date 2001-02-01 Time 11:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-01-25 Cont ID  
Sent By dpalmer Date 2001-01-25 Time 19:50 Rev Time 0.00
Received By dpalmer Date 2001-01-25 Time 19:49 Sent To  
Notes
2001-01-25 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST
 REVIEW. NOTE #2 PANEL SCHEDULE USED TO
 SHOW 300A MAINS AND WAS ASKED TO
 CORRELATE WITH PANELS SHOWN ON RISER
 DIAGRAM. NOW PANELS DON'T SHOWN ANY
 MAIN BRKR RATING.
  
 2)NOTE: PLEASE SEE NOTE 3 FROM FIRST
 REVIEW. PLANS SAY TO SEE ATTACHED
 LETTER FROM FPL.NO LETTER FOUND, BUT
 A LETTER FROM FPL ONLYS TELLS ME THE
 AVAILABLE FAULT CURRENT RATING AT
 TRANSFORMER. PLANS NEED TO INDICATE THE
 RATING OF EQUIPMENT BEING INSTALLED.
 THIS IS REQ`D TO BE ON PLANS. PER 110-9
 AND 215-5.
  
 3)NOTE: PLEASE VERIFY WATER HEATER
 WATTAGES. 2400W IS NOT A TYPICAL SIZE?
 JUST NOTE.
  
  
 4)NOTE: NOT NOTED ON FIRST REVIEW, GROUN
 DING ELECTRODE CONDUCTOR TO BE SHOWN TO
 BUILDING STEEL ALSO PER 250-50.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
  
 REVIEW. PLEASE, IF THERE ARE ANY QUESTIO
 NS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-30 Cont ID  
Sent By dpalmer Date 2000-11-30 Time 19:59 Rev Time 0.00
Received By dpalmer Date 2000-11-30 Time 19:59 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SEE NOTES ON ME-1. THE
 TOP OF THE NOTES SAY ALL NOTES BELOW
 PERTAIN TO THIS PLAN. PLEASE SEE NOTES,,
 CASH REGISTER? FUSED MAIN DISCONNECTS??
 PLEASE CLARIFY.
  
 2)NOTE: PLEASE SEE PANEL SCHEDULES AND
 RISER,,, RISER SHOWS 150A MAINS AND
 PANEL SCH SHOWS 300A MAINS??? PLEASE
 CORRELATE.
  
 3)NOTE: PLEASE PROVIDE AIC RATINGS FOR
 ALL MAINS AND BREAKERS. ALL MAINS/PANELS
 MUST BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110-9
  
 4)NOTE: PLEASE SEE LOAD CALCULATIONS,,,
 WHIRLPOOL IN MB SHOWN?? PLEASE SEE
 PANEL SCHED.?? AND PLAN DOES NOT SHOW
 IN MASTER BATH.
  
 5)NOTE: PLEASE SEE LOAD CALCS. WATER
 HEATER SHOWN AT 4500W`S. THIS ALSO DOES-
 -NOT CORRELATE WITH PANEL SCHEDULES.
 PANELS SHOW MORE THAN ONE WATER HEATER??
 ALSO THE LOAD FOR WATER HEATERS FOR BOTH
 NEED TO CORRELATE W/ LOAD CALCS.
  
 6)NOTE: POOL HEATER SHOWN ON PANEL SCHED
 -ULE BUT NOT SHOWN ON LOAD CALCS. ?????
 PLEASE DO SO.
  
 7)NOTE: PLEASE CLARIFY THE MAIN?METER
 COMBO. ALSO PLEASE SHOW ALL EQUIPMENT
 AND SHOW LOCATIONS OF ALL EQUIPMENT ON
 PLANS/PANELS/METER ETC.
  
 THE FOLLOWING IS FOR E-1.0
  
 1)NOTE: PLEASE NOTE THAT SMOKE DETECTORS
 ARE REQ`D INSIDE AND OUTSIDE ALL SLEEP-
 -ING ROOMS AND ON EACH LEVEL OF DWELLING
 PER NFPA-72 2-2.1.1.1 PLEASE SHOW ALL
 REQ`D.
  
 2)NOTE: PLEASE SEE MISSING GFI OUTLETS
 PER 210-52E FRONT AND REAR OF DWELLING.
  
 3)NOTE: PLEASE SEE MISSING OUTLETS FOR
 HALLWAY(S) PER 210-52H
  
 4)NOTE: PLEASE SEE MISSING OUTLETS SPAC-
 -ING PER 210-52
  
 5)NOTE: PLEASE SEE LOCATIONS SHOWN FOR
 DISCONNECTS THROUGHOUT HOUSE. MUST MEET
 110-26 FOR CLEARENCE REQ`MENTS.
  
 6)NOTE: PLEASE SEE MISSING OUTLETS PER
 MECH CODE FOR CONDENSING UNITS. WP GFI`S
 309-1.
  
 THE FOLLOWING IS FOR SECOND FLOOR E-2.0
  
 MOST OF THE SAME NOTES FROM FIRST FLOOR
 FOR SD`S, OUTLET SPACING AND DISCONNECT
 CLEARENCE.
  
  
 PLEASE SHOW AND SUBMIT ALL THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2002-01-24 Cont ID  
Sent By pkrauss Date 2002-01-24 Time 09:28 Rev Time 0.25
Received By pkrauss Date 2002-01-24 Time 09:23 Sent To  
Notes
2002-01-24 00:00:00NO MECHANICAL REVISIONS WITH THIS
 SUBMITTAL.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-01-20 Cont ID  
Sent By dpalmer Date 2002-01-22 Time 12:17 Rev Time 0.33
Received By jleech Date 2001-01-20 Time 09:27 Sent To  
Notes
2001-01-20 00:00:00REVISED DRAWINGS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-12-01 Cont ID  
Sent By jleech Date 2000-12-01 Time 15:18 Rev Time 0.33
Received By jleech Date 2000-12-01 Time 15:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-02-20 Cont ID  
Sent By kstevens Date 2002-02-20 Time 17:59 Rev Time 0.50
Received By kstevens Date 2002-02-20 Time 17:59 Sent To  
Notes
2002-02-20 00:00:00REVISION OK - BAR SINK ADDED.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-01-16 Cont ID  
Sent By dpalmer Date 2002-02-12 Time 19:50 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-01-16 00:00:00PROVISO:BACK FLOW PREVENTER ON WATER
 SERVICE, SWIMMING POOL .PES

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-01-20 Cont ID  
Sent By jleech Date 2001-01-20 Time 09:28 Rev Time 0.25
Received By jleech Date 2001-01-20 Time 09:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-12-01 Cont ID  
Sent By jleech Date 2000-12-01 Time 15:19 Rev Time 0.50
Received By jleech Date 2000-12-01 Time 15:19 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 1.SECOND FLOOR OUTSIDE WALLS, TWO AND
 THREE INCH. PIPES CANNOT BE USED. SEE
 94 SPC. 306.2.3.
  
 2.FIRST FLOOR BLOCK WALL. THREE INCH.
 PIPES WILL NOT FIT IN BLOCK WEBS
 AND WILL TAKE UP TOO MUCH ROOM IN THE
 TIE BEAM.
  
 3.SIZE ALL PIPES ON P-1 AND P-2.
  
 4.PLUMBING RISER NOT TO CODE.
  
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop R ROOF PLAN REVIEW
Rev No 9 Status F Date 2002-03-25 Cont ID  
Sent By jgomez Date 2002-03-25 Time 17:51 Rev Time 0.33
Received By jgomez Date 2002-03-25 Time 17:51 Sent To  
Notes
2002-03-25 00:00:00STORM SHUTTERS CHECKLIST:
 1-NEED TO SUBMITT COMPLETE INFORMATION
 FOR STORM SHUTTERS UNDER A SEPARATE
 PERMIT AS REQUESTED ON PROVISO DATED
 2-01-01.

Review Stop R ROOF PLAN REVIEW
Rev No 8 Status P Date 2002-02-22 Cont ID  
Sent By jgomez Date 2002-02-22 Time 19:46 Rev Time 2.00
Received By jgomez Date 2002-02-22 Time 19:08 Sent To  
Notes
2002-02-22 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE A5 (EL. 7.0'). MINIMUM FIN.
 FLOOR TO BE 7.5' AS REQUIRED BY SEC.
 12-22(B)(1) OF CITY CODE.
 2-COMPLY WITH ITEMS REQUESTED ON PROVISO
 DATED 2-01-01.

Review Stop R ROOF PLAN REVIEW
Rev No 7 Status F Date 2002-01-25 Cont ID  
Sent By jgomez Date 2002-01-25 Time 17:02 Rev Time 3.00
Received By jgomez Date 2002-01-25 Time 17:02 Sent To  
Notes
2002-01-25 00:00:00REVISION CHECKLIST:
 1-EXTERIOR STAIRS AT SOUTH ELEVATION
 DON'T COMPLY WITH RATIO OF SECTION
 1007.3.1 SBC 1997. REVISE AS REQ'D.
 2-STAIRS AT GARAGE DON'T COMPLY WITH
 STAIR RATIO. REVISE AS REQUIRED.
 3-NEED TO PROVIDE A LANDING AT OUTSIDE
 DOORS FROM FAMILY ROOM AS REQUIRED BY
 SECTION 1012.1.6 SBC 1997. REVISE.
 4-NEED TO PROVIDE RAILINGS AT ENTRY
 STEPS. SEC. 1007.5.1. ALSO, SEE SEC.
 1007.5.7 FOR LOCATION OF RAILINGS.
 5-PROVIDE SMOKE DETECTORS AT EACH STORY
 BY THE STAIWAY. SEC. 905.2.2 SBC 1997.
 6-CLARIFY WHERE IS THE LAUNDRY CHUTE
 GOING TO. PROVIDE DETAIL/SECTION.
 7-REVISE SIZE OF ATTIC ACCESS IN BEDROOM
 #2 CLOSET. SEC. 2309.6 SBC 1997.
 8-BALCONY RAILINGS TO HAVE BOTTOM RAIL'G
 THAT WILL NOT ALLOW A 2" SPHERE TO
 PASS THRU. SEE SEC. 1015.3 SBC AND
 REVISE DRAWINGS AS REQUIRED.
 9-WHERE IS DRAWING A-7.2?
 10-ENLARGED MASTER BEDROOM PLANS AND
 ELEVATIONS ON SHEET A-7.3.
 11-DATE WHEN ALL ARCHITECTURAL DRAWINGS
 WERE SIGNED IS INCOMPLETE. WHAT YEAR
 WERE THEY SIGNED? FOLLOW CHAPTER 481
 FL. STATUTES REQUIREMENTS.
 12-NEED TO PROVIDE ATTIC ACCESS AT ROOF
 ABOVE GARAGE. SEC. 2309.6 SBC 1997.
 13-PROVIDE FRAMING DETAILS AND SPECS AT
 ROOF AREA ABOVE GARAGE TO ALLOW FOR
 ACCESS TO NEW SUNDECK. SEC. 104.2.2
 CITY AMENDMENTS TO SBC 1997.
 -PROVIDE FRAMING AND SPECIFICATIONS FOR
 NEW SUNDECK. NOTE THAT FRAMING WAS
 DESIGNED FOR A FLAT ROOF. NOW, THE USE
 WAS CHANGED FOR A SUNDECK. THEREFORE,
 LIVE LOADS CHANGE. SEE TABLE 1604.1
 SBC 1997 AND REVISE DWGS AS REQ'D.
 14-SHEET S.2.0 IS VERY CONFUSING. IS IT
 1ST OR 2ND FLOOR FRAMING?
 -IS THIS THE FRAMING PLAN USED TO RAISE
 HOUSE TO THE MIN. FIN. FLOOR REQ'D?.
 -PROVIDE SEPARATE FRAMING PLANS FOR
 EACH FLOOR.
 15-PROVIDE INFORMATION FOR ENTRY GATES
 UNDER A SEPARATE PERMIT.
 16-SEE COMMENTS ON PLANS AND RETURN
 REVIEWED SET AFTER REVISIONS ARE DONE
 TO ORIGINAL DRAWINGS IN ORDER TO
 EXPEDITE THE REVIEW PROCESS.
 -SEE ELECTRICAL COMMENTS.

Review Stop R ROOF PLAN REVIEW
Rev No 6 Status P Date 2001-11-08 Cont ID  
Sent By jgomez Date 2001-11-08 Time 18:15 Rev Time 0.50
Received By jgomez Date 2001-11-08 Time 18:15 Sent To  
Notes
2001-11-08 00:00:00PRODUCT APPROVALS REVIEW.

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status F Date 2001-09-25 Cont ID  
Sent By jgomez Date 2001-09-25 Time 17:00 Rev Time 1.00
Received By jgomez Date 2001-09-25 Time 17:00 Sent To  
Notes
2001-09-25 00:00:00CHECKLIST:
 1-SITE SPECIFIC SUBMITTAL FOR DOORS AND
 WINDOWS PRODUCT APPROVAL NEEDS TO BE
 SIGNED, SEALED AND DATED BY THE
 ARCHITECT OF RECORD.
  
 2-ENGINEER NEEDS TO SIGN, SEAL AND DATE
 ALL ENGINEERED DOCUMENTS FOR THIS SITE
 SPECIFIC PRODUCT APPROVAL. NOTE THAT
 SOME PAGES ARE NOT SIGNED, SEALED AND
 DATED. CHAPTER 471 OF FLORIDA STATUTES
 WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
  
 3-ARCHITECT NEEDS TO REVIEW ALL TRUSS
 DRAWINGS PRIOR TO SUBMITTAL TO THIS
 OFFICE. PROVIDE REVIEW STAMP OR WRITE
 THE NECESSARY INFORMATION AND SIGN
 ACCORDINGLY.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2001-07-27 Cont ID  
Sent By jgomez Date 2001-07-27 Time 17:42 Rev Time 0.50
Received By jgomez Date 2001-07-27 Time 17:42 Sent To  
Notes
2001-07-27 00:00:00CHECKLIST:
 1-TRUSS DRAWINGS WERE REVISE ADDRESSING
 PREVIOUS CHECKLIST. BUT, THE MEAN ROOF
 HEIGHT WAS CHANGED. THE CORRECT MEAN
 ROOF HEIGHT IS 25'-0" +/- (NOT 20'-0")
 THE MEAN ROOF HEIGHT IS TAKEN FROM THE
 FINISH GRADE (NOT FINISH FLOOR)
 TO THE AVERAGE POINT OF THE HIGHEST
 ROOF.
  
 2-INFORMATION REQUESTED ON PREVIOUS
 CHECKLIST WAS NOT ADDRESSED. SEE COPY
 ATTACHED.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2001-07-18 Cont ID  
Sent By jgomez Date 2001-07-18 Time 10:52 Rev Time 2.00
Received By jgomez Date 2001-07-17 Time 18:15 Sent To  
Notes
2001-07-17 00:00:001-FRENCH DOORS PRODUCT APPROVAL THAT WAS
 SUBMITTED IS GOOD ONLY FOR DOUBLE
 DOORS AS SHOWN ON APPROVED DRAWINGS.
 -NEED TO PROVIDE PRODUCT APPROVAL FOR
 FRENCH DOORS WITH SIDELITES SINGLE
 ASSEMBLY AS SHOWN ON ARCHITECT'S PLANS
 2-PROVIDE PRODUCT APPROVAL FOR:
 -FIXED WINDOWS.
 -ROUND WINDOWS.
 -EXTERIOR SWING SINGLE DOORS.
 -ENTRY DOOR WITH SIDELITES AND TRANSOM
 ABOVE AS SHOWN ON ARCHITECT'S PLANS.
 3-TRUSS DRAWINGS:
 A)TRUSS ENGINEER TO PROVIDE ALL HIS INFO
 ON TRUSS LAYOUT AS REQUIRED BY CHAPTER
 471 OF FLORIDA STATUTES.
 B)TRUSS ENGINEER TO HAVE ORIGINAL
 SIGNATURE ON ALL ENGINEERED TRUSSES AS
 REQUIRED BY CHAPTER 471 FL. STATUTES.
 C)TRUSS ENGINEER TO UPDATE ALL GENERAL
 TRUSS DETAILS. USE ASCE 7-95 (NOT 93)
 FOR 145MPH.
 ALSO, PROVIDE ORIGINAL SIGNATURE AND
 DATE OF SEALING THE DRAWING. CH. 471.
 D)ENGINEERED TRUSSES TO BE REVISED USING
 ASCE 7-95 FOR 145MPH (NOT 140MPH).
 E)TRUSS LAYOUT AND ARCHITECT'S ROOF
 FRAMING PLAN ARE DIFFERENT. ROOF TRUSS
 LAYOUT CALLS FOR A 4" COL. TO SUPPORT
 TRUSS MG16. REVISE PLANS SHOWING THE
 RIGHT COLUMN SIZE AND CONNECTIONS AT
 SECOND FLOOR AND ROOF AREA.
 -ALSO, PROVIDE COLUMN DETAIL SHOWING
 SUPPORT OF TRUSS FG-7 AND FG-9.
 F)CONNECTOR SPECIFIED FOR TRUSS HG-13
 DOESN'T RESIST THE LOADS CALCULATED ON
 THE ENGINEERED TRUSSES. REVISE AS
 REQUIRED.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-02-01 Cont ID  
Sent By jgomez Date 2001-02-01 Time 13:28 Rev Time 5.00
Received By jgomez Date 2001-02-01 Time 13:28 Sent To  
Notes
2001-02-01 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE A5. NEED ELEVATION CERT.
 SHOWING FINISH FL. @ 7.5' MINIMUM.
 CITY CODE SEC 12-22(B)(1).
 REVISE SURVEY ACCORDINGLY.
 2-STAIRS AT GARAGE AREA NEED TO BE
 REVISED TO COMPLY WITH SECTION
 1007.3 OF SBC 1997.
 3-REVISE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM. SEE
 COMMENTS ON FORM.
 4-PROVIDE CURRENT SBCCI OR DADE COUNTY
 PRODUCT APPROVAL FOR:
 -ALL EXTERIOR DOORS AND WINDOWS FOR THE
 SPECIFIC ASSEMBLY AS SHOWN ON THE
 ARCHITECTURAL PLANS AND ELEVATIONS.
 EG: DOORS W/ SIDELITES & TRANSOM, ETC.
 -WINDOWS AND DOORS MULLIONS.
 5-PROVIDE COMPLETE INFORMATION FOR STORM
 PANELS UNDER A SEPARATE PERMIT.
  
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-12-18 Cont ID  
Sent By jgomez Date 2000-12-18 Time 08:35 Rev Time 4.00
Received By jgomez Date 2000-12-16 Time 15:18 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY
 BRING BACK STAMPED DRAWINGS & RECEIPT.
 2-FLOOD ZONE A-5. PROVIDE SURVEY WITH
 COMPLETE ELEVATIONS. EG FINISH FLOOR
 AND STREET ELEVATIONS. NEW FINISH FL
 TO BE NOT LESS THAN 18" ABOVE CROWN OF
 THE ROAD.
 3-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC 2405.2 SBC 1997.
 4-PROVIDE AREA TABULATION. EXISTING/NEW
 5-PROVIDE ATTIC ACCESS AT GARAGE AREA
 AND AT SECOND FLOOR. SEC 2309.6 SBC/97
 6-PROVIDE DOOR WITH 29" MINIMUM CLEAR
 OPENING AT FIRST FLOOR BATH. SECTION
 11 OF FLORIDA ACCESSIBILITY CODE FOR
 BUILDING CONSTRUCTION. 1997 ED.
 7-PROVIDE DESIGN CERTIFICATION FOR BLDG
 CODE COMPLIANCE FORM (ATTACHED)
 8-SPECIFY DESIGN PRESSURES CALCULATED
 FOR GARAGE DOORS.
 9-SPECIFY SIZE OF EXISTING FOOTINGS TO
 DETERMINE IF THEY ARE ADEQUATE TO
 RECEIVE THE ADDITIONAL 2ND STORY LOAD.
 SECTION 104.2.2 CITY AMENDMENTS TO SBC
 10-PROVIDE PRODUCT APPROVAL FOR:
 -ROOF TILE.
 -ALL EXTERIOR DOORS AND WINDOWS.
 -GARAGE DOORS.
 -UL LISTING AND SPECS FOR FIREPLACE.
 11-ARCHITECT TO DATE ALL DRAWINGS AND
 INFORMATION SUBMITTED FOR PUBLIC
 RECORDS. CHAPTER 481 FLORIDA STATUTES.
 12-SEE ADDITIONAL COMMENTS ON PLANS,
 INCLUDING COMMENTS BY THE OTHER TRADES
 AND RETURN REVIEWED SET AFTER ALL
 CORRECTIONS ARE DONE TO ORIGINAL DWGS
 IN ORDER TO EXPEDITE THE REVIEW.
 13-OWNER TO SIGN AND DATE ENERGY CALCS.
 14-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS OR IMPACT RESISTANT GLASS
 15-PROVIDE COMPLETE DETAIL/SECTION THRU
 BALCONY. SEC 104.2.2 CITY AMENDMENTS.
  
  
  
 NOTES:
  
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop Z ZONING
Rev No 2 Status P Date 2002-02-25 Cont ID  
Sent By sgraham Date 2002-02-25 Time 08:18 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-11-27 Cont ID  
Sent By sgraham Date 2000-11-27 Time 08:36 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***