Plan Review Stops For Permit 00110723 |
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2002-02-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-02-12 |
Time |
19:50 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-02-12 |
Time |
19:50 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2002-01-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-01-22 |
Time |
11:38 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-01-22 |
Time |
11:38 |
Sent To |
M |
|
Notes |
2002-01-22 00:00:00 | *************** UNSAT ****************** | | | | 1) NOTE: SMOKE DETECTORS ARE REQUIRED | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | PER NFPA-72 2-2.1.1.1. | | | | 2) PLEASE NOTE MISSING OUTLET(S) REQ`D | | BY 210-52E OF THE NEC. | | FRONT MISSING | | | | 3) PLEASE NOTE MISSING OUTLET FOR A/C | | EQUIPMENT PER 210-63 OF NEC AND 309.2 | | MECHANICAL CODE. | | | | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | SHOWN ON ONE PANEL, BUT NOT THE OTHER? | | | | 5)NOTE: PLEASE NOTE MISSING HALL OUTLET | | PER 210-52 H | | | | 6)NOTE: PLEASE NOTE CLEARENCE FOR AHU | | DISC, FIRST FLOOR 110-26. ORIG PLANS | | SHOW DISC IN UNIT? | | | | 7)NOTE: PLEASE NOTE MISSING FOOTER STEEL | | PER 250-50 AND ON ORIG PLANS? | | | | 8)NOTE: PLEASE NOTE PANELS ARE SHOWN | | AT 150A AND PANEL SCHEDULES ARE SHOWN AT | | 300AMPS?? | | | | 9)NOTE: PLEASE NOTE POOL HEATER SHOWN ON | | PANEL SCHEDULES BUT NOT, IN LOAD CALCS?? | | | | 10)NOTE: PLEASE NNOTE TWO 3000W WATER | | HEATERS SHOWN ON SCHEDULES, BUT ONLY | | ONE 4500W ON LOAD CALCS??? | | | | 11)NOTE: PLEASE NOTE, PLANS ARE STILL | | SHOWING EXISTING HOUSE GL? PLEASE NOTE | | THIS IS NOT REALLY EXSITING SINCE THE | | ENTIRE STRUCTURE IS RE-DONE? | | PLEASE CLARIFY PLANS SHOW NEW FRONT | | HOUSE SERVICE? AND WHAT ABOUT SERIVCE TO | | ANY OTHER HOUSE? IS THERE ARE "BACK" | | HOUSE? | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THEREARE ANYQUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2001-02-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-02-01 |
Time |
11:45 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-02-01 |
Time |
11:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2001-01-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-01-25 |
Time |
19:50 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-01-25 |
Time |
19:49 |
Sent To |
|
|
Notes |
2001-01-25 00:00:00 | ***************** UNSAT **************** | | | | 1)NOTE: PLEASE SEE NOTES FROM FIRST | | REVIEW. NOTE #2 PANEL SCHEDULE USED TO | | SHOW 300A MAINS AND WAS ASKED TO | | CORRELATE WITH PANELS SHOWN ON RISER | | DIAGRAM. NOW PANELS DON'T SHOWN ANY | | MAIN BRKR RATING. | | | | 2)NOTE: PLEASE SEE NOTE 3 FROM FIRST | | REVIEW. PLANS SAY TO SEE ATTACHED | | LETTER FROM FPL.NO LETTER FOUND, BUT | | A LETTER FROM FPL ONLYS TELLS ME THE | | AVAILABLE FAULT CURRENT RATING AT | | TRANSFORMER. PLANS NEED TO INDICATE THE | | RATING OF EQUIPMENT BEING INSTALLED. | | THIS IS REQ`D TO BE ON PLANS. PER 110-9 | | AND 215-5. | | | | 3)NOTE: PLEASE VERIFY WATER HEATER | | WATTAGES. 2400W IS NOT A TYPICAL SIZE? | | JUST NOTE. | | | | | | 4)NOTE: NOT NOTED ON FIRST REVIEW, GROUN | | DING ELECTRODE CONDUCTOR TO BE SHOWN TO | | BUILDING STEEL ALSO PER 250-50. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | | REVIEW. PLEASE, IF THERE ARE ANY QUESTIO | | NS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2000-11-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-11-30 |
Time |
19:59 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-11-30 |
Time |
19:59 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | 1)NOTE: PLEASE SEE NOTES ON ME-1. THE | | TOP OF THE NOTES SAY ALL NOTES BELOW | | PERTAIN TO THIS PLAN. PLEASE SEE NOTES,, | | CASH REGISTER? FUSED MAIN DISCONNECTS?? | | PLEASE CLARIFY. | | | | 2)NOTE: PLEASE SEE PANEL SCHEDULES AND | | RISER,,, RISER SHOWS 150A MAINS AND | | PANEL SCH SHOWS 300A MAINS??? PLEASE | | CORRELATE. | | | | 3)NOTE: PLEASE PROVIDE AIC RATINGS FOR | | ALL MAINS AND BREAKERS. ALL MAINS/PANELS | | MUST BE RATED FOR THE AVAILABLE FAULT | | CURRENT PER 110-9 | | | | 4)NOTE: PLEASE SEE LOAD CALCULATIONS,,, | | WHIRLPOOL IN MB SHOWN?? PLEASE SEE | | PANEL SCHED.?? AND PLAN DOES NOT SHOW | | IN MASTER BATH. | | | | 5)NOTE: PLEASE SEE LOAD CALCS. WATER | | HEATER SHOWN AT 4500W`S. THIS ALSO DOES- | | -NOT CORRELATE WITH PANEL SCHEDULES. | | PANELS SHOW MORE THAN ONE WATER HEATER?? | | ALSO THE LOAD FOR WATER HEATERS FOR BOTH | | NEED TO CORRELATE W/ LOAD CALCS. | | | | 6)NOTE: POOL HEATER SHOWN ON PANEL SCHED | | -ULE BUT NOT SHOWN ON LOAD CALCS. ????? | | PLEASE DO SO. | | | | 7)NOTE: PLEASE CLARIFY THE MAIN?METER | | COMBO. ALSO PLEASE SHOW ALL EQUIPMENT | | AND SHOW LOCATIONS OF ALL EQUIPMENT ON | | PLANS/PANELS/METER ETC. | | | | THE FOLLOWING IS FOR E-1.0 | | | | 1)NOTE: PLEASE NOTE THAT SMOKE DETECTORS | | ARE REQ`D INSIDE AND OUTSIDE ALL SLEEP- | | -ING ROOMS AND ON EACH LEVEL OF DWELLING | | PER NFPA-72 2-2.1.1.1 PLEASE SHOW ALL | | REQ`D. | | | | 2)NOTE: PLEASE SEE MISSING GFI OUTLETS | | PER 210-52E FRONT AND REAR OF DWELLING. | | | | 3)NOTE: PLEASE SEE MISSING OUTLETS FOR | | HALLWAY(S) PER 210-52H | | | | 4)NOTE: PLEASE SEE MISSING OUTLETS SPAC- | | -ING PER 210-52 | | | | 5)NOTE: PLEASE SEE LOCATIONS SHOWN FOR | | DISCONNECTS THROUGHOUT HOUSE. MUST MEET | | 110-26 FOR CLEARENCE REQ`MENTS. | | | | 6)NOTE: PLEASE SEE MISSING OUTLETS PER | | MECH CODE FOR CONDENSING UNITS. WP GFI`S | | 309-1. | | | | THE FOLLOWING IS FOR SECOND FLOOR E-2.0 | | | | MOST OF THE SAME NOTES FROM FIRST FLOOR | | FOR SD`S, OUTLET SPACING AND DISCONNECT | | CLEARENCE. | | | | | | PLEASE SHOW AND SUBMIT ALL THE ABOVE | | INFORMATION FOR REVIEW. IF THERE ARE ANY | | QUESTIONS PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW. | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
N |
Date |
2002-01-24 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-01-24 |
Time |
09:28 |
Rev Time |
0.25 |
Received By |
pkrauss |
Date |
2002-01-24 |
Time |
09:23 |
Sent To |
|
|
Notes |
2002-01-24 00:00:00 | NO MECHANICAL REVISIONS WITH THIS | | SUBMITTAL. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-01-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-01-22 |
Time |
12:17 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2001-01-20 |
Time |
09:27 |
Sent To |
|
|
Notes |
2001-01-20 00:00:00 | REVISED DRAWINGS |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2000-12-01 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2000-12-01 |
Time |
15:18 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2000-12-01 |
Time |
15:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2002-02-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-02-20 |
Time |
17:59 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2002-02-20 |
Time |
17:59 |
Sent To |
|
|
Notes |
2002-02-20 00:00:00 | REVISION OK - BAR SINK ADDED. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2002-01-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-02-12 |
Time |
19:50 |
Rev Time |
1.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-01-16 00:00:00 | PROVISO:BACK FLOW PREVENTER ON WATER | | SERVICE, SWIMMING POOL .PES |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-01-20 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-01-20 |
Time |
09:28 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2001-01-20 |
Time |
09:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2000-12-01 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2000-12-01 |
Time |
15:19 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2000-12-01 |
Time |
15:19 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | DENIED; | | 1.SECOND FLOOR OUTSIDE WALLS, TWO AND | | THREE INCH. PIPES CANNOT BE USED. SEE | | 94 SPC. 306.2.3. | | | | 2.FIRST FLOOR BLOCK WALL. THREE INCH. | | PIPES WILL NOT FIT IN BLOCK WEBS | | AND WILL TAKE UP TOO MUCH ROOM IN THE | | TIE BEAM. | | | | 3.SIZE ALL PIPES ON P-1 AND P-2. | | | | 4.PLUMBING RISER NOT TO CODE. | | | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT.8377 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
9 |
Status |
F |
Date |
2002-03-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2002-03-25 |
Time |
17:51 |
Rev Time |
0.33 |
Received By |
jgomez |
Date |
2002-03-25 |
Time |
17:51 |
Sent To |
|
|
Notes |
2002-03-25 00:00:00 | STORM SHUTTERS CHECKLIST: | | 1-NEED TO SUBMITT COMPLETE INFORMATION | | FOR STORM SHUTTERS UNDER A SEPARATE | | PERMIT AS REQUESTED ON PROVISO DATED | | 2-01-01. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
8 |
Status |
P |
Date |
2002-02-22 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2002-02-22 |
Time |
19:46 |
Rev Time |
2.00 |
Received By |
jgomez |
Date |
2002-02-22 |
Time |
19:08 |
Sent To |
|
|
Notes |
2002-02-22 00:00:00 | APPROVED WITH PROVISO: | | 1-FLOOD ZONE A5 (EL. 7.0'). MINIMUM FIN. | | FLOOR TO BE 7.5' AS REQUIRED BY SEC. | | 12-22(B)(1) OF CITY CODE. | | 2-COMPLY WITH ITEMS REQUESTED ON PROVISO | | DATED 2-01-01. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
7 |
Status |
F |
Date |
2002-01-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2002-01-25 |
Time |
17:02 |
Rev Time |
3.00 |
Received By |
jgomez |
Date |
2002-01-25 |
Time |
17:02 |
Sent To |
|
|
Notes |
2002-01-25 00:00:00 | REVISION CHECKLIST: | | 1-EXTERIOR STAIRS AT SOUTH ELEVATION | | DON'T COMPLY WITH RATIO OF SECTION | | 1007.3.1 SBC 1997. REVISE AS REQ'D. | | 2-STAIRS AT GARAGE DON'T COMPLY WITH | | STAIR RATIO. REVISE AS REQUIRED. | | 3-NEED TO PROVIDE A LANDING AT OUTSIDE | | DOORS FROM FAMILY ROOM AS REQUIRED BY | | SECTION 1012.1.6 SBC 1997. REVISE. | | 4-NEED TO PROVIDE RAILINGS AT ENTRY | | STEPS. SEC. 1007.5.1. ALSO, SEE SEC. | | 1007.5.7 FOR LOCATION OF RAILINGS. | | 5-PROVIDE SMOKE DETECTORS AT EACH STORY | | BY THE STAIWAY. SEC. 905.2.2 SBC 1997. | | 6-CLARIFY WHERE IS THE LAUNDRY CHUTE | | GOING TO. PROVIDE DETAIL/SECTION. | | 7-REVISE SIZE OF ATTIC ACCESS IN BEDROOM | | #2 CLOSET. SEC. 2309.6 SBC 1997. | | 8-BALCONY RAILINGS TO HAVE BOTTOM RAIL'G | | THAT WILL NOT ALLOW A 2" SPHERE TO | | PASS THRU. SEE SEC. 1015.3 SBC AND | | REVISE DRAWINGS AS REQUIRED. | | 9-WHERE IS DRAWING A-7.2? | | 10-ENLARGED MASTER BEDROOM PLANS AND | | ELEVATIONS ON SHEET A-7.3. | | 11-DATE WHEN ALL ARCHITECTURAL DRAWINGS | | WERE SIGNED IS INCOMPLETE. WHAT YEAR | | WERE THEY SIGNED? FOLLOW CHAPTER 481 | | FL. STATUTES REQUIREMENTS. | | 12-NEED TO PROVIDE ATTIC ACCESS AT ROOF | | ABOVE GARAGE. SEC. 2309.6 SBC 1997. | | 13-PROVIDE FRAMING DETAILS AND SPECS AT | | ROOF AREA ABOVE GARAGE TO ALLOW FOR | | ACCESS TO NEW SUNDECK. SEC. 104.2.2 | | CITY AMENDMENTS TO SBC 1997. | | -PROVIDE FRAMING AND SPECIFICATIONS FOR | | NEW SUNDECK. NOTE THAT FRAMING WAS | | DESIGNED FOR A FLAT ROOF. NOW, THE USE | | WAS CHANGED FOR A SUNDECK. THEREFORE, | | LIVE LOADS CHANGE. SEE TABLE 1604.1 | | SBC 1997 AND REVISE DWGS AS REQ'D. | | 14-SHEET S.2.0 IS VERY CONFUSING. IS IT | | 1ST OR 2ND FLOOR FRAMING? | | -IS THIS THE FRAMING PLAN USED TO RAISE | | HOUSE TO THE MIN. FIN. FLOOR REQ'D?. | | -PROVIDE SEPARATE FRAMING PLANS FOR | | EACH FLOOR. | | 15-PROVIDE INFORMATION FOR ENTRY GATES | | UNDER A SEPARATE PERMIT. | | 16-SEE COMMENTS ON PLANS AND RETURN | | REVIEWED SET AFTER REVISIONS ARE DONE | | TO ORIGINAL DRAWINGS IN ORDER TO | | EXPEDITE THE REVIEW PROCESS. | | -SEE ELECTRICAL COMMENTS. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
6 |
Status |
P |
Date |
2001-11-08 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-11-08 |
Time |
18:15 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2001-11-08 |
Time |
18:15 |
Sent To |
|
|
Notes |
2001-11-08 00:00:00 | PRODUCT APPROVALS REVIEW. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
5 |
Status |
F |
Date |
2001-09-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-09-25 |
Time |
17:00 |
Rev Time |
1.00 |
Received By |
jgomez |
Date |
2001-09-25 |
Time |
17:00 |
Sent To |
|
|
Notes |
2001-09-25 00:00:00 | CHECKLIST: | | 1-SITE SPECIFIC SUBMITTAL FOR DOORS AND | | WINDOWS PRODUCT APPROVAL NEEDS TO BE | | SIGNED, SEALED AND DATED BY THE | | ARCHITECT OF RECORD. | | | | 2-ENGINEER NEEDS TO SIGN, SEAL AND DATE | | ALL ENGINEERED DOCUMENTS FOR THIS SITE | | SPECIFIC PRODUCT APPROVAL. NOTE THAT | | SOME PAGES ARE NOT SIGNED, SEALED AND | | DATED. CHAPTER 471 OF FLORIDA STATUTES | | WHEN SUBMITTING DOCUMENTS FOR PUBLIC | | RECORDS. | | | | 3-ARCHITECT NEEDS TO REVIEW ALL TRUSS | | DRAWINGS PRIOR TO SUBMITTAL TO THIS | | OFFICE. PROVIDE REVIEW STAMP OR WRITE | | THE NECESSARY INFORMATION AND SIGN | | ACCORDINGLY. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
4 |
Status |
F |
Date |
2001-07-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-07-27 |
Time |
17:42 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2001-07-27 |
Time |
17:42 |
Sent To |
|
|
Notes |
2001-07-27 00:00:00 | CHECKLIST: | | 1-TRUSS DRAWINGS WERE REVISE ADDRESSING | | PREVIOUS CHECKLIST. BUT, THE MEAN ROOF | | HEIGHT WAS CHANGED. THE CORRECT MEAN | | ROOF HEIGHT IS 25'-0" +/- (NOT 20'-0") | | THE MEAN ROOF HEIGHT IS TAKEN FROM THE | | FINISH GRADE (NOT FINISH FLOOR) | | TO THE AVERAGE POINT OF THE HIGHEST | | ROOF. | | | | 2-INFORMATION REQUESTED ON PREVIOUS | | CHECKLIST WAS NOT ADDRESSED. SEE COPY | | ATTACHED. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
3 |
Status |
F |
Date |
2001-07-18 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-07-18 |
Time |
10:52 |
Rev Time |
2.00 |
Received By |
jgomez |
Date |
2001-07-17 |
Time |
18:15 |
Sent To |
|
|
Notes |
2001-07-17 00:00:00 | 1-FRENCH DOORS PRODUCT APPROVAL THAT WAS | | SUBMITTED IS GOOD ONLY FOR DOUBLE | | DOORS AS SHOWN ON APPROVED DRAWINGS. | | -NEED TO PROVIDE PRODUCT APPROVAL FOR | | FRENCH DOORS WITH SIDELITES SINGLE | | ASSEMBLY AS SHOWN ON ARCHITECT'S PLANS | | 2-PROVIDE PRODUCT APPROVAL FOR: | | -FIXED WINDOWS. | | -ROUND WINDOWS. | | -EXTERIOR SWING SINGLE DOORS. | | -ENTRY DOOR WITH SIDELITES AND TRANSOM | | ABOVE AS SHOWN ON ARCHITECT'S PLANS. | | 3-TRUSS DRAWINGS: | | A)TRUSS ENGINEER TO PROVIDE ALL HIS INFO | | ON TRUSS LAYOUT AS REQUIRED BY CHAPTER | | 471 OF FLORIDA STATUTES. | | B)TRUSS ENGINEER TO HAVE ORIGINAL | | SIGNATURE ON ALL ENGINEERED TRUSSES AS | | REQUIRED BY CHAPTER 471 FL. STATUTES. | | C)TRUSS ENGINEER TO UPDATE ALL GENERAL | | TRUSS DETAILS. USE ASCE 7-95 (NOT 93) | | FOR 145MPH. | | ALSO, PROVIDE ORIGINAL SIGNATURE AND | | DATE OF SEALING THE DRAWING. CH. 471. | | D)ENGINEERED TRUSSES TO BE REVISED USING | | ASCE 7-95 FOR 145MPH (NOT 140MPH). | | E)TRUSS LAYOUT AND ARCHITECT'S ROOF | | FRAMING PLAN ARE DIFFERENT. ROOF TRUSS | | LAYOUT CALLS FOR A 4" COL. TO SUPPORT | | TRUSS MG16. REVISE PLANS SHOWING THE | | RIGHT COLUMN SIZE AND CONNECTIONS AT | | SECOND FLOOR AND ROOF AREA. | | -ALSO, PROVIDE COLUMN DETAIL SHOWING | | SUPPORT OF TRUSS FG-7 AND FG-9. | | F)CONNECTOR SPECIFIED FOR TRUSS HG-13 | | DOESN'T RESIST THE LOADS CALCULATED ON | | THE ENGINEERED TRUSSES. REVISE AS | | REQUIRED. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2001-02-01 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-02-01 |
Time |
13:28 |
Rev Time |
5.00 |
Received By |
jgomez |
Date |
2001-02-01 |
Time |
13:28 |
Sent To |
|
|
Notes |
2001-02-01 00:00:00 | APPROVED WITH PROVISO: | | 1-FLOOD ZONE A5. NEED ELEVATION CERT. | | SHOWING FINISH FL. @ 7.5' MINIMUM. | | CITY CODE SEC 12-22(B)(1). | | REVISE SURVEY ACCORDINGLY. | | 2-STAIRS AT GARAGE AREA NEED TO BE | | REVISED TO COMPLY WITH SECTION | | 1007.3 OF SBC 1997. | | 3-REVISE DESIGN CERTIFICATION FOR | | BUILDING CODE COMPLIANCE FORM. SEE | | COMMENTS ON FORM. | | 4-PROVIDE CURRENT SBCCI OR DADE COUNTY | | PRODUCT APPROVAL FOR: | | -ALL EXTERIOR DOORS AND WINDOWS FOR THE | | SPECIFIC ASSEMBLY AS SHOWN ON THE | | ARCHITECTURAL PLANS AND ELEVATIONS. | | EG: DOORS W/ SIDELITES & TRANSOM, ETC. | | -WINDOWS AND DOORS MULLIONS. | | 5-PROVIDE COMPLETE INFORMATION FOR STORM | | PANELS UNDER A SEPARATE PERMIT. | | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ AT 659-8096 EXT. 8232. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2000-12-18 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2000-12-18 |
Time |
08:35 |
Rev Time |
4.00 |
Received By |
jgomez |
Date |
2000-12-16 |
Time |
15:18 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | CHECKLIST: | | 1-PAY IMPACT FEES TO PALM BEACH COUNTY | | BRING BACK STAMPED DRAWINGS & RECEIPT. | | 2-FLOOD ZONE A-5. PROVIDE SURVEY WITH | | COMPLETE ELEVATIONS. EG FINISH FLOOR | | AND STREET ELEVATIONS. NEW FINISH FL | | TO BE NOT LESS THAN 18" ABOVE CROWN OF | | THE ROAD. | | 3-SPECIFY SAFETY GLASS WHERE REQUIRED. | | SEE PLANS AND SEC 2405.2 SBC 1997. | | 4-PROVIDE AREA TABULATION. EXISTING/NEW | | 5-PROVIDE ATTIC ACCESS AT GARAGE AREA | | AND AT SECOND FLOOR. SEC 2309.6 SBC/97 | | 6-PROVIDE DOOR WITH 29" MINIMUM CLEAR | | OPENING AT FIRST FLOOR BATH. SECTION | | 11 OF FLORIDA ACCESSIBILITY CODE FOR | | BUILDING CONSTRUCTION. 1997 ED. | | 7-PROVIDE DESIGN CERTIFICATION FOR BLDG | | CODE COMPLIANCE FORM (ATTACHED) | | 8-SPECIFY DESIGN PRESSURES CALCULATED | | FOR GARAGE DOORS. | | 9-SPECIFY SIZE OF EXISTING FOOTINGS TO | | DETERMINE IF THEY ARE ADEQUATE TO | | RECEIVE THE ADDITIONAL 2ND STORY LOAD. | | SECTION 104.2.2 CITY AMENDMENTS TO SBC | | 10-PROVIDE PRODUCT APPROVAL FOR: | | -ROOF TILE. | | -ALL EXTERIOR DOORS AND WINDOWS. | | -GARAGE DOORS. | | -UL LISTING AND SPECS FOR FIREPLACE. | | 11-ARCHITECT TO DATE ALL DRAWINGS AND | | INFORMATION SUBMITTED FOR PUBLIC | | RECORDS. CHAPTER 481 FLORIDA STATUTES. | | 12-SEE ADDITIONAL COMMENTS ON PLANS, | | INCLUDING COMMENTS BY THE OTHER TRADES | | AND RETURN REVIEWED SET AFTER ALL | | CORRECTIONS ARE DONE TO ORIGINAL DWGS | | IN ORDER TO EXPEDITE THE REVIEW. | | 13-OWNER TO SIGN AND DATE ENERGY CALCS. | | 14-PROVIDE COMPLETE INFORMATION FOR | | STORM PANELS OR IMPACT RESISTANT GLASS | | 15-PROVIDE COMPLETE DETAIL/SECTION THRU | | BALCONY. SEC 104.2.2 CITY AMENDMENTS. | | | | | | | | NOTES: | | | | -IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ AT 659-8096 EXT. 8232. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2002-02-25 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-02-25 |
Time |
08:18 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-11-27 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2000-11-27 |
Time |
08:36 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|