Plan Review Details - Permit 00110460
Plan Review Stops For Permit 00110460
Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2001-07-11 Cont ID  
Sent By pkrauss Date 2001-07-11 Time 11:10 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
2001-07-11 00:00:00PER RON'S INSPECTION AHU 2 RETURN HAS 12
 "BETWEEN AHU AND 1ST DISTRIBUTION BOX.
  
  
 AHU 1SHOWS 8" INTO 1ST BOX WITH 10" LE
 AVING (SUPPLY) IN ACTUALITY IT IS 10" IN
 AND 10" OUT.
  
 7-11-01PHK.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-27 Cont ID  
Sent By pkrauss Date 2001-06-27 Time 12:56 Rev Time 0.35
Received By pkrauss Date 2001-06-27 Time 11:54 Sent To  
Notes
2001-06-27 00:00:00*******************PROVISO**************
  
 ACCESS FOR AHU IN ATTIC SHALL HAVE AN
 ACCESS OPENING LARGE ENOUGH TO REMOVE
 THE LARGEST PIECE OF EQUIPMENT TO THE
 AHU BUT IN NO CASE LESS THAN 22" X 36".
 (1997 SMC 304.4.1)
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-11-14 Cont ID  
Sent By jleech Date 2000-11-14 Time 17:35 Rev Time 0.33
Received By jleech Date 2000-11-14 Time 17:35 Sent To  
Notes
***NONE***