Plan Review Details - Permit 00110332
Plan Review Stops For Permit 00110332
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-12-27 Cont ID  
Sent By mcarsill Date 2000-12-27 Time 14:13 Rev Time 0.00
Received By mcarsill Date 2000-12-27 Time 14:13 Sent To  
Notes
2001-01-08 00:00:00APPROVED PROVISO: SEPARATE PLANS AND
 PERMITS REQUIRED FOR GAS AND ELECTRIC
 WORK.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-12-11 Cont ID  
Sent By mcarsill Date 2000-12-11 Time 15:18 Rev Time 0.00
Received By mcarsill Date 2000-12-11 Time 15:18 Sent To  
Notes
2001-01-08 00:00:00ON DECEMBER 11, 2000, WRITER ALONG WITH
 PLUMBING PLAN REVIEWER JOHN LEECH
 EXAMINED THE INFORMATION FOR PERMIT
 00110332. SEVERAL CONCERNS WERE RAISED
 BY JOHN LEECH AND THIS WRITER. ON SAME
 DATE, WRITER CONTACTED MARK KAPLAN OF
 BRADLEY HEATING AND A/C, INC.
 ACCORDING TO MR. KAPLAN THE PROPANE
 TANKS ARE APPROXIMATELY 25 FEET FROM
 OTHER BUILDINGS. THIS INFORMATION IS
 NOT SHOWN ON THE DRAWINGS. HE ALSO
 ADVISED THAT THE PROPANE TANKS ARE
 APPROXIMATELY 25 FEET FROM PROPERTY
 LINES. HE FURTHER ADVISED THAT GAS
 PIPING WILL BE DONE BY OTHERS. HE
 ALSO ADVISED THAT HE BELIEVES THAT
 THIS PIPING WILL BE 1/2 INCH GALVANIZED
 OR BLACK AND WOULD PROBABLY BE CLAMPED
 OR UNISTRUTED TO THE BUILDING.HE ALSO
 STATED THAT NO DOORS ARE PRESENT ALONG
 THE SIDE OF THE BUILDING NEAR THE
 PROPANE STORAGE.
 1) NO SMOKING SIGNS ARE TO BE PROVIDED.
 2) COMPLIANCE WITH NFPA 704 IS
 REQUIRED.
 3) COMPLIANCE WITH NFPA 58 IS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-12-27 Cont ID  
Sent By ndenmark Date 2000-12-27 Time 15:05 Rev Time 0.50
Received By ndenmark Date 2000-12-27 Time 15:05 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1. ELECTRICAL PERMIT REQUIRED FOR ALL
 ELECTRICAL WORK RELATED TO THIS PERMIT
 ELECTRICAL CONTRACTOR TO PROVIDE INFO ON
 GENERATOR ALONG W/ WIRING INFO AT TIME
 OF PERMIT APPLICATION FOR ELECTRIC WORK
 2. GAS PERMIT REQUIRED FOR GAS CONNECT-
 ED TO THIS PROJECT. CONTRACTOR TO PROVID
 INFORMATION ON PIPING, TANK AND CODE
 COMPLIANCE AS REQUIRED BY ATTACHED FIRE
 REVIEW COMMENTS