Plan Review Details - Permit 00110282
Plan Review Stops For Permit 00110282
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-02-16 Cont ID  
Sent By jwitmer Date 2001-02-16 Time 16:18 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-02-16 00:00:00PROVISO: PROVIDE SHOP DRAWINGS SHOWING
 THE ATTACHMENT OF THE BOOTH TO THE SLAB.
 BUILDING PLAN REVIEW J WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-11-29 Cont ID  
Sent By hpiskura Date 2000-11-29 Time 16:49 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-20 Cont ID  
Sent By dpalmer Date 2001-02-20 Time 12:11 Rev Time 0.00
Received By dpalmer Date 2001-02-20 Time 12:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-11 Cont ID  
Sent By dpalmer Date 2000-12-11 Time 19:25 Rev Time 0.00
Received By dpalmer Date 2000-12-11 Time 19:25 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE PROVIDE AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 PER 110-9.
  
 2)NOTE: PLEASE PROVIDE CALCULATION TO
 INCLUDE LARGEST MOTOR AT 125%.
  
 3)NOTE: PLEASE PROVIDE CLARIFICATION
 OF EQUIPMENT GROUNDING CONDUCTORS OR
 CONDUIT TYPE AFTER FIRST MEANS OF DISC-
 -ONNECT.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-12-12 Cont ID  
Sent By mgonzale Date 2000-12-12 Time 07:05 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED
 ALL WORK WILL BE PERFORMED ON-SITE
 THE PLANS DO NOT REFLECT ANY WATER
 AND SEWER. ROADWAY ADDITION
 DRAINAGE MUST BE RETAINED ON SITE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-03-05 Cont ID  
Sent By mcarsill Date 2001-03-05 Time 14:45 Rev Time 0.00
Received By mcarsill Date 2001-03-05 Time 14:45 Sent To  
Notes
2001-03-05 00:00:001) PROVIDE INFORMATION ON GATE ARM AT
 NEW BOOTH. WHAT PROVISIONS HAVE BEEN
 MADE FOR FIRE AND PARAMEDICAL ACCESS.
 WILL THE NEW BOOTH BE OPERATIONAL
 24 HOURS A DAY OR BE OPENED FOR LIMITED
 AMOUNT OF TIME DURING THE DAY.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-12-07 Cont ID  
Sent By ndenmark Date 2000-12-07 Time 15:27 Rev Time 0.33
Received By ndenmark Date 2000-12-07 Time 15:27 Sent To  
Notes
2001-01-08 00:00:00NO MECHANICAL INCLUDED

Review Stop P PLUMBING
Rev No 2 Status N Date 2001-03-02 Cont ID  
Sent By jleech Date 2001-03-02 Time 14:26 Rev Time 0.50
Received By jleech Date 2001-03-02 Time 14:26 Sent To  
Notes
2001-03-02 00:00:00NO PLUMBING IS SHOWN. LAST SET OF COMENT
 S WERE NOT ADDRESSED.

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-11-22 Cont ID  
Sent By jleech Date 2000-11-22 Time 13:05 Rev Time 0.50
Received By jleech Date   Time   Sent To  
Notes
2001-01-08 00:00:00NO PLUMBING.
 STORM WATER DRAINAGE PLAN REQUIRED.
  
 WHERE ARE BATHROOM FACILITIES FOR
 EMPLOYEES.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-11-14 Cont ID  
Sent By sgraham Date 2000-11-14 Time 10:23 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***