Plan Review Details - Permit 00110184
Plan Review Stops For Permit 00110184
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-01-09 Cont ID  
Sent By dpalmer Date 2001-01-09 Time 07:26 Rev Time 0.00
Received By dpalmer Date 2001-01-09 Time 07:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-16 Cont ID  
Sent By dpalmer Date 2000-11-16 Time 22:12 Rev Time 0.00
Received By dpalmer Date 2000-11-16 Time 22:12 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT NOW A MAIN DISC
 HAS BEEN ADDED TO METER. AIC RATING OF
 PANEL IS SHOWN BUT NOT THE AIC RATING
 REQ`D FOR MAIN? PLEASE SUBMIT. MAIN
 ALSO MUST BE RATED FOR THE AVAILALE
 FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE SEE PLAN,,,THIS STILL
 REFLECTS METER W/ NO MAIN?? CORRELATE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 ETX 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-11-16 Cont ID  
Sent By jleech Date 2000-11-16 Time 18:32 Rev Time 0.33
Received By jleech Date 2000-11-16 Time 18:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-11-16 Cont ID  
Sent By jleech Date 2000-11-16 Time 18:32 Rev Time 0.33
Received By jleech Date 2000-11-16 Time 18:32 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2001-03-12 Cont ID  
Sent By jgomez Date 2001-03-12 Time 19:14 Rev Time 0.25
Received By jgomez Date 2001-03-12 Time 19:14 Sent To  
Notes
2001-03-12 00:00:00TRUSS DRAWINGS CHECKLIST:
  
 1-ENGINEER TO PROVIDE SIGNED, SEALED AND
 DATED GENERAL TRUSS DRAWINGS AS WELL
 AS REQUIRED BY CHAPTER 471 OF FLORIDA
 STATUTES.
  
 2-UPDATE ALL GENERAL TRUSS DRAWINGS AS
 REQUIRED. ALSO, THERE ARE MANY
 DIFFERENT DESIGN WIND LOADS. SEE
 HIGHLIGHTED TRUSS DRAWINGS.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-01-10 Cont ID  
Sent By jgomez Date 2001-01-10 Time 17:41 Rev Time 1.00
Received By jgomez Date 2001-01-10 Time 17:41 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-12-07 Cont ID  
Sent By jgomez Date 2000-12-07 Time 17:30 Rev Time 2.50
Received By jgomez Date 2000-12-07 Time 17:30 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
  
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 2-RESUBMIT ENERGY CALCULATIONS WITH
 ORIGINAL SIGNATURES AND DATES BY THE
 PERSONWHO PREPARED IT AND BY THE
 OWNER/AGENT. SEC 103.0 OF FLORIDA
 ENERGY EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION, 1997 EDITION.
 3-OWES $774.92 FOR RADON FEES, WESTERN
 EXPANSION AND WETLANDS FEES.
 SEE ATTACHED RECEIPT.
 4-DENIED BY ELECTRICAL. SEE COMMENTS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-11-06 Cont ID  
Sent By sgraham Date 2000-11-06 Time 11:14 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***