Plan Review Details - Permit 00110183
Plan Review Stops For Permit 00110183
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-01-22 Cont ID  
Sent By lmartine Date 2001-01-22 Time 12:38 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-01-16 Cont ID  
Sent By lmartine Date 2001-01-16 Time 11:53 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-16 00:00:00BUILDING COMMENTS
 -------------------
  
 1]
 SUBMIT AN APPROVED 1 HR. ASSEMBLY FOR IN
 TERIOR WALL 20' HIGH.
 2]
 PROVIDE LEGAL DOCUMENTATION FOR 15' EASE
 MENT WEST OF PROPERTY LINE, WERE STEPS A
 ND LANDING WILL BE CONSTRUCTED, [SUBMIT
 DETAILS FOR STEPS AND LANDING].
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 659-8096
 #8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-11-08 Cont ID  
Sent By lmartine Date 2000-11-08 Time 10:25 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE COMMENTS ON BACK OF APPLICATION
 11/8LM

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-01-22 Cont ID  
Sent By lmartine Date 2001-01-22 Time 12:35 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-22 00:00:00 
  
 APPROVED BY, DEWEY PALMER ON 1/17
 SEE BACK OF APPLICATION.
  
 L.MARTINEZ

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-01-18 Cont ID  
Sent By mcarsill Date 2001-01-18 Time 12:42 Rev Time 0.00
Received By mcarsill Date 2001-01-18 Time 12:41 Sent To  
Notes
2001-01-18 00:00:00APPROVED PROVISO: ENTIRE BUILDING IS
 TO BE INSPECTED AND APPROVED BY THE
 FIRE RESCUE DEPARTMENT, PRIOR TO
 RECEIVING APPROVAL.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-01-10 Cont ID  
Sent By mcarsill Date 2001-01-10 Time 10:03 Rev Time 0.00
Received By mcarsill Date 2001-01-10 Time 10:02 Sent To  
Notes
2001-01-10 00:00:001) PLEASE CLEARLY INDICATE THE OCCUPANCY
 TYPES FOR THE TWO BAYS.
 2) EXITING NOT PERMITTED THROUGH STORAGE
 ROOM.
 3) ELECTRICAL PLANS DO NOT DISPLAY
 EXISTING EMERGENCY LIGHTS OR ILLUMINATED
 EXIT SIGNS WITHIN THE TWO BAYS.
 4) ANY OPENING PROTECTIVE DEVICE PLANNED
 FOR THE TWO HOUR WALL.
 5) EXITING IS NOT VERY CLEAR TO WRITER
 ON THE DEAD-END STREET SIDE.
 6) CLEARLY INDICATE THE TWO MEANS OF
 EGRESS FROM THE BAY LOCATED ADJACENT TO
 THE PARKING LOT.
 7) PLANS DO NOT INDICATE TYPE X FIRE
 RATED DRYWALL. PLEASE PROVIDE WALL
 DETAIL AND APPLICABLE UL NUMBER.
 8) NO INTERIOR FINISH INFORMATION
 LOCATED ON PLANS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910