Plan Review Details - Permit 00101480
Plan Review Stops For Permit 00101480
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-11-22 Cont ID  
Sent By drunnels Date 2000-11-22 Time 12:08 Rev Time 2.00
Received By drunnels Date 2000-11-22 Time 12:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-30 Cont ID  
Sent By dpalmer Date 2000-11-30 Time 22:26 Rev Time 0.00
Received By dpalmer Date 2000-11-30 Time 22:26 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ***************
  
 1)NOTE:PLEASE NOTE THAT A DISCONNECT IS
 REQ`D INLINE FROM GENERATOR TO ATS. PER
 230-70/225-31 AND GROUPING OF DISCONNECT
 PER 230-72 AND 225-34 AND LOCATION PER
 225-32.
  
 2)NOTE: PLEASE PROVIDE CLARIFICATION
 FOR GFI PROTECTION OF SERVICE PER 230-95
  
  
 3)NOTE: PLEASE SUBMIT PANEL SCHEDULES
 NOT SUBMITTED FOR NEW PANELS SHOWN ON
 6TH FLOOR.
  
 PLEASE CLARIFY FIRE PUMP(S) AND IF
 EXISTING AND WHERE THEY ARE CONNECTED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
  
 561-659-8096 EXT 8372
  
  
 4)NOTE: PLEASE NOTE THAT ALL OUTLET
 SPACING IS TO MEET LOCAL CODE ART:210-50
 OFFICES= EVERY 12` AND STORAGE AREAS
 EVERY 20` OF UNENCUMBERED WALL SPACE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-11-28 Cont ID  
Sent By mcarsill Date 2000-11-28 Time 11:42 Rev Time 0.00
Received By mcarsill Date 2000-11-28 Time 11:41 Sent To  
Notes
2001-01-08 00:00:001) PLEASE CLARIFY BATTERY ROOM. WHAT
 TYPE OF BATTERIES, HOW MANY, WHAT ARE
 THEY USED FOR, AND WHAT IF ANY DANGER
 DO THEY POSE.
 2) PLEASE PROVIDE COMPLETE FIRE ALARM
 SYSTEM SHOP DRAWINGS FOR THE FIRE ALARM
 EQUIPMENT SHOWN ON THE PLANS. CUT SHEETS
 WIRING DIAGRAM, AND FLOOR PLAN ARE
 NEEDED WHEN SUBMITTED UNDER SEPARATE
 PERMIT.
 3) PLEASE SUBMIT COMPLETE FIRE SPRINKLER
 DRAWINGS FOR THE PRE-ACTION FIRE
 SPRINKLER SYSTEM SHOWN ON THE DRAWINGS.
 A SEPARATE PLAN AND PERMIT REQUIRED.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-11-30 Cont ID  
Sent By ndenmark Date 2000-11-30 Time 13:08 Rev Time 0.33
Received By ndenmark Date 2000-11-30 Time 13:08 Sent To  
Notes
2001-01-08 00:00:00*****************DENIED*****************
 1.1997 SMC 610.6.1 REQUIRES LOCATION AND
 INSTALLATION DETAILS OF REQUIRED FIRE
 DAMPERS ETC. SHALL BE SHOWN AND CLEARLY
 IDENTIFIED ON THE PLANS BY THE DESIGNER.
 RATED WALL AT BATTERY ROOM HAVE OPENINGS
 IN WALLS AND NO PROTECTION SHAOWN AS
 REQUIRED BY 610.1.2
 2. CONDENSATE DRAIN LINE SHOWS TERMINATE
 TO MOP SINK. LOCAL ORDINANCE DOES NOT
 PERMIT CONDENSATE TO FLOW INTO SANITARY
 SEWER.
 3. LOCAL CODE REQUIRES MINIMUM 18"
 CLEARANCE BETWEEN ROOF SURFACE AND
 BOTTOM OF EQUIPMENT SUPPORT FOR ACCESS
 BELOW EQUIPMENT TO REROOF.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-11-04 Cont ID  
Sent By tlarge Date 2000-11-04 Time 09:00 Rev Time 1.00
Received By tlarge Date 2000-11-04 Time 08:18 Sent To  
Notes
2001-01-08 00:00:001)THE NUMBER OF REQD.SANITARY FACILITIES
 SHALL BE BASED UPON HABITABLE FLOOR
 SPACE PER SPC 407.1.3.AND TABLE 407.
 REVIEW,REVISE AND COMPLY.
  
 2)SUBMIT SANITARY AND WATER RISER
 DIAGRAMS FOR ALL PLUMBING WORK.(ADD'L.
 FIXTURES,MOP SINK,DRINKING FOUNTAIN,ETC.
  
 3)SUBMIT OCCUPANT LOAD FOR COMPLIANCE W/
 SPC TABLE 407.
  
 4)SHOW CLEAR INSIDE DIMENSIONS OF TOILET
 ROOM AND REQD.WHEELCHAIR TURNING SPACE
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.,FACBC SEC.4.2.3.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved