|
 |
 |
 |
 |
 |
Plan Review Details - Permit 00101480
Plan Review Stops For Permit 00101480 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2000-11-22 |
|
|
Cont ID |
|
Sent By |
drunnels |
Date |
2000-11-22 |
Time |
12:08 |
Rev Time |
2.00 |
Received By |
drunnels |
Date |
2000-11-22 |
Time |
12:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2000-11-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-11-30 |
Time |
22:26 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-11-30 |
Time |
22:26 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | **************** UNSAT *************** | | | | 1)NOTE:PLEASE NOTE THAT A DISCONNECT IS | | REQ`D INLINE FROM GENERATOR TO ATS. PER | | 230-70/225-31 AND GROUPING OF DISCONNECT | | PER 230-72 AND 225-34 AND LOCATION PER | | 225-32. | | | | 2)NOTE: PLEASE PROVIDE CLARIFICATION | | FOR GFI PROTECTION OF SERVICE PER 230-95 | | | | | | 3)NOTE: PLEASE SUBMIT PANEL SCHEDULES | | NOT SUBMITTED FOR NEW PANELS SHOWN ON | | 6TH FLOOR. | | | | PLEASE CLARIFY FIRE PUMP(S) AND IF | | EXISTING AND WHERE THEY ARE CONNECTED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | | | 561-659-8096 EXT 8372 | | | | | | 4)NOTE: PLEASE NOTE THAT ALL OUTLET | | SPACING IS TO MEET LOCAL CODE ART:210-50 | | OFFICES= EVERY 12` AND STORAGE AREAS | | EVERY 20` OF UNENCUMBERED WALL SPACE. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2000-11-28 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-11-28 |
Time |
11:42 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-11-28 |
Time |
11:41 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) PLEASE CLARIFY BATTERY ROOM. WHAT | | TYPE OF BATTERIES, HOW MANY, WHAT ARE | | THEY USED FOR, AND WHAT IF ANY DANGER | | DO THEY POSE. | | 2) PLEASE PROVIDE COMPLETE FIRE ALARM | | SYSTEM SHOP DRAWINGS FOR THE FIRE ALARM | | EQUIPMENT SHOWN ON THE PLANS. CUT SHEETS | | WIRING DIAGRAM, AND FLOOR PLAN ARE | | NEEDED WHEN SUBMITTED UNDER SEPARATE | | PERMIT. | | 3) PLEASE SUBMIT COMPLETE FIRE SPRINKLER | | DRAWINGS FOR THE PRE-ACTION FIRE | | SPRINKLER SYSTEM SHOWN ON THE DRAWINGS. | | A SEPARATE PLAN AND PERMIT REQUIRED. | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2000-11-30 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-11-30 |
Time |
13:08 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2000-11-30 |
Time |
13:08 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | *****************DENIED***************** | | 1.1997 SMC 610.6.1 REQUIRES LOCATION AND | | INSTALLATION DETAILS OF REQUIRED FIRE | | DAMPERS ETC. SHALL BE SHOWN AND CLEARLY | | IDENTIFIED ON THE PLANS BY THE DESIGNER. | | RATED WALL AT BATTERY ROOM HAVE OPENINGS | | IN WALLS AND NO PROTECTION SHAOWN AS | | REQUIRED BY 610.1.2 | | 2. CONDENSATE DRAIN LINE SHOWS TERMINATE | | TO MOP SINK. LOCAL ORDINANCE DOES NOT | | PERMIT CONDENSATE TO FLOW INTO SANITARY | | SEWER. | | 3. LOCAL CODE REQUIRES MINIMUM 18" | | CLEARANCE BETWEEN ROOF SURFACE AND | | BOTTOM OF EQUIPMENT SUPPORT FOR ACCESS | | BELOW EQUIPMENT TO REROOF. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2000-11-04 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-11-04 |
Time |
09:00 |
Rev Time |
1.00 |
Received By |
tlarge |
Date |
2000-11-04 |
Time |
08:18 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1)THE NUMBER OF REQD.SANITARY FACILITIES | | SHALL BE BASED UPON HABITABLE FLOOR | | SPACE PER SPC 407.1.3.AND TABLE 407. | | REVIEW,REVISE AND COMPLY. | | | | 2)SUBMIT SANITARY AND WATER RISER | | DIAGRAMS FOR ALL PLUMBING WORK.(ADD'L. | | FIXTURES,MOP SINK,DRINKING FOUNTAIN,ETC. | | | | 3)SUBMIT OCCUPANT LOAD FOR COMPLIANCE W/ | | SPC TABLE 407. | | | | 4)SHOW CLEAR INSIDE DIMENSIONS OF TOILET | | ROOM AND REQD.WHEELCHAIR TURNING SPACE | | PER COUNTYWIDE AMENDMENTS TO SPC SEC. | | 104.2.1.,FACBC SEC.4.2.3. | | | | CALL IF YOU HAVE QUESTIONS. | | 561-659-8096,EXT.8377. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |