Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-11-03 Cont ID  
Sent By lmartine Date 2000-11-03 Time 12:51 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-12-12 Cont ID  
Sent By jleech Date 2000-12-12 Time 15:16 Rev Time 0.50
Received By jleech Date 2000-12-12 Time 5:16 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
  
 PLUMBING RISER FOR STORM AT PARKING
 GARAGE. HORIZONTAL PIPING MUST BE
 MINIMUM THREE INCHES, PER TABLE 1108.2.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-10-29 Cont ID  
Sent By tlarge Date 2000-10-29 Time 09:52 Rev Time 0.50
Received By tlarge Date 2000-10-29 Time 09:52 Sent To  
Notes
2001-01-08 00:00:00SUBMIT RISER DIAGRAM SHOWING PIPE SIZES,
 SLOPE OF PIPE,SQUARE FOOTAGE DRAINED BY
 EACH DRAIN.COMPLY W/SPC TABLES 1108.1,
 1108.2.,1107.3.
  
 2)STORMWATER DISCHARGE SHALL NOT BE TO
 AN AREA THAT WILL CREATE A NUISANCE.
 CLEARLY SHOW TERMINATION POINT OF DRAINS
 SPC 301.4.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.