2001-01-08 00:00:00 | ****************** UNSAT ************** |
| |
| 1)NOTE:PLEASE SUBMIT A CLEAR RISER DIA- |
| -GRAM SHOWING WORK BEING DONE. |
| |
| 2)NOTE: YOU SHOW AN EXISTING 200A METER |
| PACK AND YOU ARE INCREASING SERVICE BUT |
| NOT METERBANK?? PLEASE SHOW EXISTING |
| RISER CONDUCTORS FOR SERVICE INCREASE. |
| |
| 3)NOTE: PLEASE SEE WHERE IT IS PROPOSED |
| TO INCREASE PANEL TO 200A WITH #1 WIRE. |
| THIS IS NOT PERMITTED PER NEC. |
| |
| 4)NOTE: PLEASE DIVIDE LOAD CALCULATIONS |
| FOR EACH PANEL AND ONE FOR TOTAL SERVICE |
| PLEASE LAYOUT/SHOW PER NEC AND ART215-5. |
| THE TOTAL SQ FT SHOWN IS 2000. IS THIS |
| FOR MAIN HOUSE? GARAGE/APT? OR BOTH? |
| |
| 5)NOTE: PLEASE SHOW ELECTRICAL REWORK |
| IN KITCHEN THAT IS PROPOSED ON APPLICAT- |
| -ION.PLEASE SHOW LAYOUT OF FLOOR PLAN |
| FOR CHANGES. |
| |
| 6)NOTE: PLEASE SEE NEC 310-15. #4 IS NOT |
| RATED FOR 125A SERVICE OR PANEL. |
| |
| PLEASE SUBMIT PLANS WITH MORE DETAIL. |
| PLEASE SEE CITY/COUNTY ADMINISTRATIVE |
| CODE 104.2 AND 104.2.7. |
| PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW. |
| 659-8096 EXT 8372 |