Plan Review Details - Permit 00100919
Plan Review Stops For Permit 00100919
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-05-01 Cont ID  
Sent By lmartine Date 2001-05-01 Time 14:36 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-02-27 Cont ID  
Sent By lsmith Date 2001-02-27 Time 08:05 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2001-02-27 00:00:00FAILED: NEED ADDITIONAL INFORMATION
  
 1. HOW MANY STORIES IN BUILDING?
 2. TYPE OF CONSTRUCTION; CEILING RATING?
 3. ENERGY CALCS. MISSING 4TH FLOOR
 4. DOORS @ CONFERENCE ROOM & NEW BATH DO
 NOT MEET FAC CODE.
 5. VALUE OF IMPROVEMENTS ADJUSTED TO
 $30,000.
 5. NEED FIRE SPRINKLER DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-01-30 Cont ID  
Sent By hpiskura Date 2001-01-30 Time 10:19 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-30 00:00:00THE SCOPE OF WORK SHOWN ON THE REVISIONS
 IS REQUIRED TO BE DRAWN BY AN
 ARCHITECT.INCLUDE DIMENSIONS AND
 DETAILS IN ACCORDANCE WITH GOOD
 ARCHITECTURAL PRACTICE.SHOW OR
 PROVIDE NEW RATED DOOR S FOR THE STAIR
 ENCLOSURE, FIRE RATED TENANT SEPARATION
 WHERE APPLICABLE AND PROVISIONS FOR
 HANDICAP ACCESSIBILITY.
  
 SHOW THE METHOD OF FIRE RATED
 PENETRATION PROTECTION FOR THE
 MECHANICAL SERVICES.
  
 SHOW THE FIRE SPRINKLER LAYOUT FOR THE
 CHANGED FLOOR PLAN.
 THE ORIGINAL PERMIT VALUATION OF
 $6000.00 IS FAR TOO LOW FOR THIS WORK.
 THE VALUE EXCEEDS $25,000.00.PLEASE
 PAY ADDITIONAL OR NEW PERMIT FEES AS
 NECESSARY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-11-20 Cont ID  
Sent By drunnels Date 2000-11-20 Time 10:47 Rev Time 1.00
Received By drunnels Date 2000-11-20 Time 10:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2001-04-26 Cont ID  
Sent By dpalmer Date 2001-04-26 Time 20:26 Rev Time 0.00
Received By dpalmer Date 2001-04-26 Time 20:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2001-04-05 Cont ID  
Sent By dpalmer Date 2001-04-05 Time 20:07 Rev Time 0.00
Received By dpalmer Date 2001-04-05 Time 20:07 Sent To  
Notes
2001-04-05 00:00:00**************** UNSAT*****************
  
 1)NOTE: PLEASE PROVIDE BRANCH CIRCUIT
 #`S ON PLANS THAT CORRELATE WITH PANEL
 SCHEDULES.
  
 2)NOTE:PLEASE REMOVE HALL SWITCHING,AS
 HALL/STAIRWAY IS NOW ON SEPARATE PLANS.
  
 3)NOTE: PLEASE NOTE THAT LOADS SHOWN FOR
 TWO PANELS EXCEED OVERCURRENT PROTECTION
 OF DISCONNECT.
  
 4)NOTE: PLEASE NOTE THAT MEANS OF EGRESS
 LIGHTING COMING INTO TENANT#2 IS SHOWN G
 OING TO CEILING J-BOX. PLEASE NOTE THAT
 SOME SORT OF MIN LIGHTING FIXTURES ARE
 REQ`D. 210-70
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE GET WITH ON ANY QUESTIONS
 OR CLARIFICATION THAT IS NEEDED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-02-22 Cont ID  
Sent By dpalmer Date 2001-02-22 Time 11:22 Rev Time 0.00
Received By dpalmer Date 2001-02-22 Time 11:21 Sent To  
Notes
2001-02-22 00:00:00SAME NOTES AS PREVIOUS REVIEWS
 LOAD CLACLS
 BRANCH CIRCUITS
 EQUIPMENT GROUNDING CONDUCTOR
 ETC.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-01-30 Cont ID  
Sent By dpalmer Date 2001-01-30 Time 21:27 Rev Time 0.00
Received By dpalmer Date 2001-01-30 Time 21:27 Sent To  
Notes
2001-01-30 00:00:00****************** UNSAT **************
  
 1)NOTE: PROVISO FROM FIRST REVIEW STILL
 NOT ADDRESSED.
 ALSO, NEED TO SUBMIT PANEL SCHEDULES
 ANDLOAD CALCULATIONS, SHOWING EXISTING
 PANEL(S) AND SIZES. 215-5
  
 PLEASE SEE ORIG. NOTES ATTACHED AND
 SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-11-07 Cont ID  
Sent By dpalmer Date 2000-11-07 Time 19:40 Rev Time 0.00
Received By dpalmer Date 2000-11-07 Time 19:40 Sent To  
Notes
2001-01-08 00:00:00**************** PROVISO **************
  
 1)NOTE: PLEASE SUBMIT PANEL SCHEDULE
 WITH BRANCH CIRCUITS SHOWN ON PLANS
 THAT CORRELATE WITH PANEL SCHED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW BEFORE FINAL ELECTRICAL
 INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2001-04-26 Cont ID  
Sent By mcarsill Date 2001-04-26 Time 09:44 Rev Time 0.00
Received By mcarsill Date 2001-04-26 Time 09:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-04-11 Cont ID  
Sent By mcarsill Date 2001-04-11 Time 10:47 Rev Time 0.00
Received By mcarsill Date 2001-04-11 Time 10:47 Sent To  
Notes
2001-04-11 00:00:001) PLEASE PROVIDE DETAILS ON REAR
 FIRE ESCAPE STAIR. WHERE DOES IT
 TERMINATE, HOW IS IT SUPPORTED,
 RISE AND RUN CRITERIA.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-03-02 Cont ID  
Sent By mcarsill Date 2001-03-02 Time 08:39 Rev Time 0.00
Received By mcarsill Date 2001-03-02 Time 08:35 Sent To  
Notes
2001-03-02 00:00:001) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 2) NO FIRE ALARM EQUIPMENT SHOWN ON THE
 FOURTH FLOOR.
 3) EMERGENCY LIGHTING REQUIRED IN
 EXISTING STAIR.
 4) NO FIRE SPRINKLER DRAWINGS INCLUDED
 WITH PLANS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-02-05 Cont ID  
Sent By mcarsill Date 2001-02-05 Time 12:07 Rev Time 0.00
Received By mcarsill Date 2001-02-05 Time 12:06 Sent To  
Notes
2001-02-05 00:00:001) NO DOOR SCHEDULE PROVIDED WITH PLANS.
 2) NO EMERGENCY LIGHTS OR EXIT
 SIGNS SHOWN ON PLANS.
 3) HOW IS THE STAIR RATED. WHAT IS THE
 RATING FOR THE STAIR SHAFT.
 4) NO MECHANICAL EQUIPMENT SHOWN ON
 PLANS.
 5) NO FIRE SPRINKLER SYSTEM INFORMATION
 PROVIDED WITH PLANS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-11-01 Cont ID  
Sent By mcarsill Date 2000-11-01 Time 11:45 Rev Time 0.00
Received By mcarsill Date 2000-11-01 Time 11:45 Sent To  
Notes
2001-01-08 00:00:00ON 11-1-00, THIS WRITER CONTACTED MR.
 NORDINE BY TELEPHONE. ACCORDING TO MR.
 NORDINE, THE PERMITTED WORK IS FOR
 THE 4TH FLOOR ONLY. MR. NORDINE
 EXPLAINED THAT 1/2" SHEETROCK IS
 TO BE INSTALLED ON THE METAL STUDS.
 HE FURTHER ADVISED THAT THE BUILDING
 HAS FIRE SPRINKLER PROTECTION.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2001-04-27 Cont ID  
Sent By pkrauss Date 2001-04-27 Time 09:30 Rev Time 0.30
Received By pkrauss Date 2001-04-27 Time 09:29 Sent To  
Notes
2001-04-27 00:00:00NOTE ON PLAN - FAN SHUTDOWN WITH
 NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-03-26 Cont ID  
Sent By pkrauss Date 2001-03-26 Time 14:46 Rev Time 0.35
Received By pkrauss Date 2001-03-23 Time 08:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2001-03-21 Cont ID  
Sent By pkrauss Date 2001-03-21 Time 12:17 Rev Time 0.45
Received By pkrauss Date 2001-03-21 Time 12:17 Sent To  
Notes
2001-03-21 00:00:00NOTES ON PERMIT 01020715.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-02-27 Cont ID  
Sent By pkrauss Date 2001-02-27 Time 15:56 Rev Time 0.40
Received By pkrauss Date 2001-02-27 Time 16:13 Sent To  
Notes
2001-02-27 00:00:00NOTES:
  
 1.NO AIR BALANCE OR OUTSIDE AIR CALCS.
 ASHRAE 62-89.
  
 2.NO DUCT SMOKE DETECTORS INDICATED.
 97 SMC 609.1 & 406.4 & NFPA 90A
 4-4.4.3
  
 3.DO WINDOWS IN BATHROOMS WORK?NO
 EXHAUST FANS INDICATED IN BATHROOMS.
 97 SMC 503.3.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-11-17 Cont ID  
Sent By ndenmark Date 2000-11-17 Time 07:24 Rev Time 0.25
Received By ndenmark Date 2000-11-17 Time 07:24 Sent To  
Notes
2001-01-08 00:00:00NO MECHANICAL INFORMATION PROVIDED FOR
 REVIEW. PROVIDE PLANS FOR MECH WORK AT
 TIME OF MECH PERMIT APPLICATION PRIOR TO
 ANY MECH WORK BEING STARTED.

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-05-01 Cont ID  
Sent By kstevens Date 2001-05-01 Time 14:27 Rev Time 0.25
Received By kstevens Date 2001-05-01 Time 14:27 Sent To  
Notes
2001-05-01 00:00:00SHOWER DELETED - SINK DELETED BY
 L. MARTINEZ-KSTEVENS

Review Stop P PLUMBING
Rev No 4 Status F Date 2001-04-30 Cont ID  
Sent By kstevens Date 2001-04-30 Time 10:28 Rev Time 1.25
Received By kstevens Date 2001-04-30 Time 10:58 Sent To  
Notes
2001-04-30 00:00:00REVIEW NOTES: DENIED;
  
 (1) BATHROOM ADDITION SHALL MEET 97
 FACBC REQUIREMENTS. 5' TURNING RADIUS,
 AND SHOWER.
  
 (2) KITCHEN SINK SHALL MEET FACBC SEC.
 4.24.2 THRU 4.24.7.
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-04-11 Cont ID  
Sent By jleech Date 2001-04-11 Time 08:38 Rev Time 0.75
Received By jleech Date 2001-04-11 Time 08:38 Sent To  
Notes
2001-04-11 00:00:00DENIED;
  
 1.BATHROOM ADDITION SHALL MEET 97 FACBC
 REQUIREMENTS. DOOR SWING, 5' TURNING
 RADIUS,AND SHOWER.
  
 2.KITCHEN SINK SHALL MEET FACBC SEC.
 4.24.2 THRU 4.24.7.
  
 3.SANITARY RISER NOT TO CODE. WATER
 CLOSET UNVENTED.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-03-04 Cont ID  
Sent By pschmitz Date 2001-03-04 Time 14:30 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-03-04 00:00:00PLUMBING PLAN REVIEW # 401 PASS. PES

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-02-01 Cont ID  
Sent By jleech Date 2001-02-01 Time 14:49 Rev Time 0.75
Received By pschmitz Date 2001-02-01 Time 14:49 Sent To  
Notes
2001-02-01 00:00:00NO PLUMBING PLAN REVIEW;
  
 1.NOT ENOUGH INFORMATION TO DO A
 PLUMBING PLAN REVIEW.
  
 2.PLANS TO BE SUBMITED WITH PLUMBING
 APPLICATION.
  
 ANY QUESTIONS CALL
 JOHN LEECH
 659-8096 EXT. 8377