Plan Review Details - Permit 00100505
Plan Review Stops For Permit 00100505
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-12-13 Cont ID  
Sent By lmartine Date 2002-12-13 Time 18:41 Rev Time 0.00
Received By lmartine Date 2002-12-13 Time 18:42 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-04-04 Cont ID  
Sent By lmartine Date 2002-04-04 Time 16:07 Rev Time 6.00
Received By lmartine Date   Time   Sent To  
Notes
2002-04-04 00:00:00APPROV SHOP DRAWINGS FOR ROOF JOIST AND
 EXTERIOR GLAZING.
  
 L.MARTINEZ
 659-8096
 #8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-01-09 Cont ID  
Sent By lmartine Date 2002-01-09 Time 13:25 Rev Time 2.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-01-31 Cont ID  
Sent By jwitmer Date 2001-01-31 Time 16:16 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-31 00:00:00PROVISO: NEEDS TO PAY COUNTY IMPACT
 FEES BEFORE ISSUANCE.01/31/01 JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-11-20 Cont ID  
Sent By drunnels Date 2000-11-20 Time 12:13 Rev Time 2.00
Received By drunnels Date 2000-11-20 Time 12:13 Sent To  
Notes
2001-01-08 00:00:001] FLORIDA ENERGE SHEETS MUST BE SIGNED
 BY OWNER/AGENT.
 2] SUBMIT PRODUCT APPROVAL FOR INPACT
 RESISTANT GLAZING FOR STOREFRONT AND
 DOORS / METRO DADE COUNTY OR SBCCI
 3] SUBMIT PRODUCT APPROVAL FOR ROOF
 COVERINGS.
 4. SUBMIT PLANS TO COUNTY AND PAY IMPACT
 FEES.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2002-12-04 Cont ID  
Sent By dpalmer Date 2002-12-04 Time 15:05 Rev Time 0.25
Received By dpalmer Date 2002-12-04 Time 15:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2002-12-03 Cont ID  
Sent By dpalmer Date 2002-12-03 Time 14:43 Rev Time 0.25
Received By dpalmer Date 2002-12-03 Time 14:43 Sent To  
Notes
2002-12-03 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE, PANEL SCHEDULES
 SHOW FEEDERS AS 3/0`S AND RISER SHOWS
 4/0`S FOR PANELS "L" AND "A/C". PLEASE
 VERIFY AND CORRELATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVEIW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-03-28 Cont ID  
Sent By btrobaug Date 2002-11-19 Time 18:23 Rev Time 0.00
Received By dpalmer Date 2002-03-28 Time 13:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-01-18 Cont ID  
Sent By lmartine Date 2002-01-18 Time 11:45 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2002-01-18 00:00:00SEE PROVISO APPROVED BY BILL
 TROBAUGH ON #01100725
  
 L MARTINEZ

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-11-21 Cont ID  
Sent By dpalmer Date 2001-11-21 Time 07:53 Rev Time 0.00
Received By dpalmer Date 2001-11-21 Time 07:53 Sent To  
Notes
2001-11-21 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT PROVISO FROM
 LAST REVIEW WAS NOT ADDRESSED.
 PLEASE NOTE/CLARIFY 225A OCP SHOWN FOR
 PANELS "L" AND "AC" AND 3/0`S AS THE
 CONDUCTORS. PLEASE NOTE THAT PROVISO
 NEEDED THESE TO BE CHANGED BEFORE
 NEXT PLAN REVIEW/FINAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-14 Cont ID  
Sent By dpalmer Date 2001-02-14 Time 17:47 Rev Time 0.00
Received By dpalmer Date 2001-02-14 Time 17:47 Sent To  
Notes
2001-02-14 00:00:00RISER DIAGRAM TO BE REVISED BEFORE FINAL
 .
 3/0`S TO 4/0`S

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-11-14 Cont ID  
Sent By dpalmer Date 2000-11-14 Time 21:37 Rev Time 0.00
Received By dpalmer Date 2000-11-14 Time 21:37 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2000-11-27 Cont ID  
Sent By mgonzale Date 2000-11-27 Time 09:34 Rev Time 0.15
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00NO UTILITIES

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2002-04-04 Cont ID  
Sent By mcarsill Date 2002-04-04 Time 08:43 Rev Time 0.00
Received By mcarsill Date 2002-04-04 Time 08:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-01-09 Cont ID  
Sent By mcarsill Date 2002-01-09 Time 14:02 Rev Time 0.00
Received By mcarsill Date 2002-01-09 Time 14:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-11-29 Cont ID  
Sent By mcarsill Date 2001-11-29 Time 08:10 Rev Time 0.00
Received By mcarsill Date 2001-11-29 Time 08:10 Sent To  
Notes
2001-11-29 00:00:00A LETTER WAS SUBMITTED BY THE ARCHITECT
 FOR THE REMOVAL OF THE FIRE SPRINKLER
 SYSTEM THAT WAS PLANNED FOR THE SAAB
 PORTION OF THE BUILDING. THE ARCHITECT
 ALSO PROVIDED SOME CODE INFORMATION TO
 SUUPORT THE PREMISE THAT THE FIRE
 SPRINKLER SYSTEM COULD BE REMOVED.
 THIS OFFICE NEEDS TO KNOW WHAT PORTIONS
 IF ANY ON THE SITE ARE FIRE SPRINKLER
 PROTECTED AS IT RELATES TO THE SAAB
 PORTION OF THE SITE. IT IS BELIEVED THAT
 SOME PORTIONS OF THE BUILDING ALREADY
 ARE PROTECTED BY FIRE SPRINKLER SYSTEMS.
 THE BUILDING BELIEVED FORMERLY LEVITZ
 HAD SOME FIRE SPRINKLER PROTECTION
 PROVIDED TO IT. IS THAT NOT STILL THE
 CASE. A TWO HOUR FIRE WALL WAS OBSERVED
 BETWEEN THE DISPLAY AREA, PARTS, AND
 SERVICE AREA. A TWO HOUR SEPARATION DOES
 NOT MAKE THIS AREA SEPARATE BUILDING
 BUT PROVIDES FOR TENANT SEPARATION.
 A REVIEW OF FIRE RESCUE RECORDS WILL
 OCCUR WITH REGARDS TO EXISTING FIRE
 PROTECTION SYSTEMS THAT MAY HAVE BEEN
 PRESENT. PLEASE PROVIDE FURTHER DETAILS
 REGARDING THIS MATTER. THANK YOU
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-02-15 Cont ID  
Sent By mcarsill Date 2001-02-15 Time 11:46 Rev Time 0.00
Received By mcarsill Date 2001-02-15 Time 11:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-11-14 Cont ID  
Sent By mcarsill Date 2000-11-14 Time 14:02 Rev Time 0.00
Received By mcarsill Date 2000-11-14 Time 14:01 Sent To  
Notes
2001-01-08 00:00:001) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
 2) PLEASE EXPLAIN EXITING. IT APPEARS
 THAT ALL DESIGNATED EXITS ARE ON ONE
 SIDE OF THE BUILDING. WHEN EXITS ARE
 REQUIRED THEY ARE TO BE SEPARATED FROM
 ONE ANOTHER SO A SINGLE FIRE CANNOT
 BLOCK BOTH EXITS.
 3) PLEASE SHOW FIRE HYDRANT LOCATIONS.
 4) PLEASE INDICATE HOW VEHICLES WILL
 BE DISPLAYED WITHIN BUILDING.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-19 Cont ID  
Sent By btrobaug Date 2002-11-19 Time 18:23 Rev Time 0.00
Received By btrobaug Date 2002-11-19 Time 18:23 Sent To E
Notes
2002-11-19 00:00:00TO DVP./WRT

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-04-01 Cont ID  
Sent By pkrauss Date 2002-04-01 Time 08:50 Rev Time 0.45
Received By pkrauss Date 2002-04-01 Time 08:45 Sent To  
Notes
2002-04-01 00:00:00MECHANICAL PERMIT 01100723

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-12-06 Cont ID  
Sent By pkrauss Date 2001-12-01 Time 10:37 Rev Time 0.45
Received By pkrauss Date 2001-12-01 Time 10:36 Sent To  
Notes
2001-12-01 00:00:00CANNOT FIND ORIGINAL PLANS TO SEE WHAT
 WAS ELMINATED FROM THE ORIGINAL PLANS.
 PLANS INDICATE A CHANGE IN O.A. CALCS
 IN THE AUTO DISPLAY AREA.. NEED
 ORIGINAL PLANS...
  
 PLANS LOCATED REVISIONS APPROVED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-02-14 Cont ID  
Sent By pkrauss Date 2001-02-14 Time 12:00 Rev Time 0.50
Received By pkrauss Date 2001-02-14 Time 11:58 Sent To  
Notes
2001-02-14 00:00:00MECHANICAL REVISION REQUIRED WERE LEFT
 OUT OF THIS RESUB./ DAVE ROMKE
 (ENGINEER) WAS NOTIFIED AND WILL
 CONTACT THE ARCHITECT TO HAVE CORRECT
 PAGES SUBMITTED
 PLANS WERE INSERTED INTO SET AND ALL
 PRIOR COMMENTS WERE ADDRESS ON RESUB

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-11-16 Cont ID  
Sent By ndenmark Date 2000-11-16 Time 12:47 Rev Time 0.33
Received By ndenmark Date 2000-11-16 Time 12:46 Sent To  
Notes
2001-01-08 00:00:00**************DENIED********************
 1. PROVIDE INFORMATION ON DROPS FOR NEW
 VEHICLE DISPLAY AREA AND NEW VEHICLE
 DELIVERY AREA.
 2. PROVIDE OUTSIDE AIR SCHEDULE PER
 ASHRAE 62-89.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-12-20 Cont ID  
Sent By kstevens Date 2002-12-20 Time 18:37 Rev Time 0.50
Received By kstevens Date 2002-12-20 Time 18:36 Sent To  
Notes
2002-12-20 00:00:00REVISION OK - ADDED 2 ROOF DRAINS AND
 2 SECONDARY DRAINS - PROVISO SHALL TIE
 INTO APPROVED STORM LINE OR CATCH BASIN.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-02-23 Cont ID  
Sent By lmartine Date 2002-12-13 Time 18:43 Rev Time 1.33
Received By jleech Date 2001-02-23 Time 16:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-10-27 Cont ID  
Sent By tlarge Date 2000-10-27 Time 15:26 Rev Time 1.25
Received By tlarge Date 2000-10-27 Time 15:26 Sent To  
Notes
2001-01-08 00:00:00 
 SUBMIT UL ASSEMBLY NUMBER AND DETAIL FOR
 FIRESAFING OF METALLIC AND NON- METALLIC
 PIPE PENETRATIONS.COUNTYWIDE AMENDMENTS
 TO SPC SEC.104.2.4.
  
 2)SHT.A115-DELETE REFERENCE TO SO.FLA.
 BLDG.CODE.THE CODES IN EFFECT IN THE
 CITY OF WPB ARE THEW STANDARD CODES.
 COUNTYWIDE AMENDMENTS TO SPC SEC.101.
  
 3)FLUSH CONTROLS ON WATER CLOSETS IN
 HANDICAP TOILET ROOMS SHALL BE LOCATED
 ON THE WIDE SIDE PER FACBC SEC.4.16.5.
  
 4)SUBMIT ISOMETRIC FOR THE REVISED STORM
 WATER DRAINAGE SYSTEM.SHOW SQ.FOOT AREA
 DRAINED BY EACH ROOF DRAIN.COMPLY W/SPC
 SEC.1108.1,1108.2.
  
 5)PROVIDE INFORMATION ON SECONDARY
 DRAINAGE.COMPLY W/SPC SEC.1109.
  
 CALL IF YOU HAVE QUESTIONS
 561-659-8096,EXT.8377.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop Z ZONING
Rev No 2 Status P Date 2001-10-02 Cont ID  
Sent By sgraham Date 2001-10-02 Time 11:53 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2001-08-15 Cont ID  
Sent By sgraham Date 2001-08-15 Time 11:38 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-08-15 00:00:00CPD MUST BE APPROVED BEFORE PERMIT CAN
 BE ISSUED


Account Summary | Usage Policy | Privacy Policy