Plan Review Details - Permit 00100406
Plan Review Stops For Permit 00100406
Review Stop    
Rev No 1 Status P Date 2001-01-22 Cont ID  
Sent By jwitmer Date 2001-08-16 Time 17:52 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-08-16 Cont ID  
Sent By jwitmer Date 2001-08-16 Time 17:52 Rev Time 1.00
Received By jwitmer Date 2001-08-16 Time 17:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-12-06 Cont ID  
Sent By drunnels Date 2000-12-06 Time 16:33 Rev Time 2.00
Received By drunnels Date 2000-12-06 Time 16:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-08-08 Cont ID  
Sent By dpalmer Date 2001-08-08 Time 11:32 Rev Time 0.00
Received By dpalmer Date 2001-08-08 Time 11:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-06-27 Cont ID  
Sent By dpalmer Date 2001-06-27 Time 11:32 Rev Time 0.00
Received By dpalmer Date 2001-06-27 Time 11:28 Sent To  
Notes
2001-08-08 00:00:00SERVICE DISC FOR FIRE PUMP SIZED TOO
 SMALL.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-12-07 Cont ID  
Sent By dpalmer Date 2000-12-07 Time 22:21 Rev Time 0.00
Received By dpalmer Date 2000-12-07 Time 22:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-08-14 Cont ID  
Sent By mcarsill Date 2001-08-14 Time 10:47 Rev Time 0.00
Received By mcarsill Date 2001-08-14 Time 10:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-12-21 Cont ID  
Sent By mcarsill Date 2000-12-21 Time 14:29 Rev Time 0.00
Received By mcarsill Date 2000-12-21 Time 14:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-11-27 Cont ID  
Sent By mcarsill Date 2000-11-27 Time 07:56 Rev Time 0.00
Received By mcarsill Date 2000-11-27 Time 07:56 Sent To  
Notes
2001-01-08 00:00:001) EXISTING FIRE SPRINKLER SYSTEM TO
 REMAIN ACTIVE DURING DEMOLITION,
 ALTERATION, AND CONSTRUCTION ACTIVITIES.
 2) EXISTING FIRE STANDPIPE SYSTEM TO
 REMAIN ACTIVE DURING DEMOLITION,
 ALTERATION AND CONSTRUCTION ACTIVITIES.
 3) PROVIDE MORE DETAILS ON FUTURE GEN
 SETS.
 4) ENTIRE BUILDING TO BE COMPLETELY FIRE
 SPRINKLER PROTECTED. THIS INCLUDES ALL
 MECHANICAL, ELECTRICAL AND SERVICE
 ROOMS. ALSO ALL VERTICAL SHAFTS ARE TO
 BE SPRINKLER PROTECTED. PLEASE EXPLAIN
 NEW 5" STANDPIPE ISOLATION VALVES WITH
 TAMPER SWITCHES. THE PLAN INDICATES THE
 REMOVAL OF EXISTINMG SPRINKLER SYSTEM
 PUMP # 2. PLEASE PROVIDE REVISED
 HYDRAULIC CALCULATIONS.
 5) PLEASE PROVIDE COMPLETE FIRE ALARM
 SYSTEM SHOP DRAWINGS. CUT SHEETS,
 WIRING DIAGRAM, AND FLOOR PLANS TO
 BE SUBMITTED UNDER SEPARATE PERMIT.
  
 APPROVED PROVISO:
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-01-22 Cont ID  
Sent By ndenmark Date 2001-01-22 Time 08:33 Rev Time 0.33
Received By ndenmark Date 2001-01-22 Time 08:33 Sent To  
Notes
2001-01-22 00:00:00PROVISO:
 1. EXHAUST DUCT PENETRATING 1ST FL
 SLABTO BE PROTECTED BY CONTINUOUS SHAFT
 OR FIRE DAMPER AT LOCATION WHERE DUCT
 LEAVES SHAFT IN BASEMENT. FIELD
 INSPECTION TO VERIFY BOTTOM OF SHAFT AT
 BASEMENT CONSTRUCTION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-01-09 Cont ID  
Sent By ndenmark Date 2001-01-09 Time 14:40 Rev Time 0.50
Received By ndenmark Date 2001-01-09 Time 14:40 Sent To  
Notes
2001-01-09 00:00:00****************DENIED******************
 1. RISER DIAGRAM SHOWS FIRE DAMPERS AT
 EACH FLOOR FOR THE EXHAUST DUCT. 1997
 SMC610.4 REQUIRES THAT IN ALL BUILDINGS
 MORE THAN ONE FLOOR IN HEIGHT, DUCTS
 EXTENDING THROUGH MORE THAN ONE FLOOR
 TO BE PROTECTED BY A SHAFT ENCLOSURE
 HAVING A FIRE RESISTANCE RATING OF NOT
 LESS THAN 2 HOURS IN BUILDINGS FOUR
 FLOORS OR MORE IN HEIGHT. PROVIDE SHAFT
 DETAIL AND FIRE DAMPER LOCATION FOR
 DUCTS LEAVING SHAFT AS REQUIRED BY
 610.1.2

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-11-30 Cont ID  
Sent By ndenmark Date 2000-11-30 Time 15:01 Rev Time 0.50
Received By ndenmark Date 2000-11-30 Time 15:01 Sent To  
Notes
2001-01-08 00:00:00***************DENIED*******************
 1. PROVIDE SHAFT DETAIL (INCLUDING RISER
 SHOWING SHAFT CONSTRUCTION AND DUCT
 PENETRATING SHAFT WALL
 2. PROVIDE INFORMATION ON HOW FUTURE
 SPACE IS TO RECEIVE OUTSIDE AIR AS REQ-
 UIRED BY ASHRAE 62-89

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-01-19 Cont ID  
Sent By jleech Date 2001-01-19 Time 10:59 Rev Time 0.75
Received By jleech Date 2001-01-19 Time 10:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-01-10 Cont ID  
Sent By jleech Date 2001-01-10 Time 09:22 Rev Time 1.50
Received By jleech Date 2001-01-10 Time 09:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-11-30 Cont ID  
Sent By jleech Date 2000-11-30 Time 14:06 Rev Time 1.50
Received By jleech Date 2001-01-10 Time 09:21 Sent To  
Notes
2001-01-08 00:00:00NOT ENOUGH INFORMATION;
 1.STATE OCCUPANCY TYPE FOR EACH FLOOR.
  
 2.NUMBER OF EMPLOYEES PER EACH FLOOR.
 SEE 94 SPC. 407.3
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-01-22 Cont ID  
Sent By sgraham Date 2000-10-18 Time 08:35 Rev Time 0.15
Received By ydavis Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS DMP APPROVAL