Plan Review Stops For Permit 00100406 |
Review Stop |
|
|
Rev No |
1 |
Status |
P |
Date |
2001-01-22 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-08-16 |
Time |
17:52 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2001-08-16 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-08-16 |
Time |
17:52 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
2001-08-16 |
Time |
17:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2000-12-06 |
|
|
Cont ID |
|
Sent By |
drunnels |
Date |
2000-12-06 |
Time |
16:33 |
Rev Time |
2.00 |
Received By |
drunnels |
Date |
2000-12-06 |
Time |
16:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2001-08-08 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-08-08 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-08-08 |
Time |
11:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2001-06-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-06-27 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-06-27 |
Time |
11:28 |
Sent To |
|
|
Notes |
2001-08-08 00:00:00 | SERVICE DISC FOR FIRE PUMP SIZED TOO | | SMALL. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2000-12-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-12-07 |
Time |
22:21 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-12-07 |
Time |
22:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2001-08-14 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-08-14 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-08-14 |
Time |
10:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2000-12-21 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-12-21 |
Time |
14:29 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-12-21 |
Time |
14:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2000-11-27 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-11-27 |
Time |
07:56 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-11-27 |
Time |
07:56 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) EXISTING FIRE SPRINKLER SYSTEM TO | | REMAIN ACTIVE DURING DEMOLITION, | | ALTERATION, AND CONSTRUCTION ACTIVITIES. | | 2) EXISTING FIRE STANDPIPE SYSTEM TO | | REMAIN ACTIVE DURING DEMOLITION, | | ALTERATION AND CONSTRUCTION ACTIVITIES. | | 3) PROVIDE MORE DETAILS ON FUTURE GEN | | SETS. | | 4) ENTIRE BUILDING TO BE COMPLETELY FIRE | | SPRINKLER PROTECTED. THIS INCLUDES ALL | | MECHANICAL, ELECTRICAL AND SERVICE | | ROOMS. ALSO ALL VERTICAL SHAFTS ARE TO | | BE SPRINKLER PROTECTED. PLEASE EXPLAIN | | NEW 5" STANDPIPE ISOLATION VALVES WITH | | TAMPER SWITCHES. THE PLAN INDICATES THE | | REMOVAL OF EXISTINMG SPRINKLER SYSTEM | | PUMP # 2. PLEASE PROVIDE REVISED | | HYDRAULIC CALCULATIONS. | | 5) PLEASE PROVIDE COMPLETE FIRE ALARM | | SYSTEM SHOP DRAWINGS. CUT SHEETS, | | WIRING DIAGRAM, AND FLOOR PLANS TO | | BE SUBMITTED UNDER SEPARATE PERMIT. | | | | APPROVED PROVISO: | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2001-01-22 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2001-01-22 |
Time |
08:33 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2001-01-22 |
Time |
08:33 |
Sent To |
|
|
Notes |
2001-01-22 00:00:00 | PROVISO: | | 1. EXHAUST DUCT PENETRATING 1ST FL | | SLABTO BE PROTECTED BY CONTINUOUS SHAFT | | OR FIRE DAMPER AT LOCATION WHERE DUCT | | LEAVES SHAFT IN BASEMENT. FIELD | | INSPECTION TO VERIFY BOTTOM OF SHAFT AT | | BASEMENT CONSTRUCTION. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2001-01-09 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2001-01-09 |
Time |
14:40 |
Rev Time |
0.50 |
Received By |
ndenmark |
Date |
2001-01-09 |
Time |
14:40 |
Sent To |
|
|
Notes |
2001-01-09 00:00:00 | ****************DENIED****************** | | 1. RISER DIAGRAM SHOWS FIRE DAMPERS AT | | EACH FLOOR FOR THE EXHAUST DUCT. 1997 | | SMC610.4 REQUIRES THAT IN ALL BUILDINGS | | MORE THAN ONE FLOOR IN HEIGHT, DUCTS | | EXTENDING THROUGH MORE THAN ONE FLOOR | | TO BE PROTECTED BY A SHAFT ENCLOSURE | | HAVING A FIRE RESISTANCE RATING OF NOT | | LESS THAN 2 HOURS IN BUILDINGS FOUR | | FLOORS OR MORE IN HEIGHT. PROVIDE SHAFT | | DETAIL AND FIRE DAMPER LOCATION FOR | | DUCTS LEAVING SHAFT AS REQUIRED BY | | 610.1.2 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2000-11-30 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-11-30 |
Time |
15:01 |
Rev Time |
0.50 |
Received By |
ndenmark |
Date |
2000-11-30 |
Time |
15:01 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ***************DENIED******************* | | 1. PROVIDE SHAFT DETAIL (INCLUDING RISER | | SHOWING SHAFT CONSTRUCTION AND DUCT | | PENETRATING SHAFT WALL | | 2. PROVIDE INFORMATION ON HOW FUTURE | | SPACE IS TO RECEIVE OUTSIDE AIR AS REQ- | | UIRED BY ASHRAE 62-89 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2001-01-19 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-01-19 |
Time |
10:59 |
Rev Time |
0.75 |
Received By |
jleech |
Date |
2001-01-19 |
Time |
10:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2001-01-10 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-01-10 |
Time |
09:22 |
Rev Time |
1.50 |
Received By |
jleech |
Date |
2001-01-10 |
Time |
09:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2000-11-30 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2000-11-30 |
Time |
14:06 |
Rev Time |
1.50 |
Received By |
jleech |
Date |
2001-01-10 |
Time |
09:21 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | NOT ENOUGH INFORMATION; | | 1.STATE OCCUPANCY TYPE FOR EACH FLOOR. | | | | 2.NUMBER OF EMPLOYEES PER EACH FLOOR. | | SEE 94 SPC. 407.3 | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2001-01-22 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2000-10-18 |
Time |
08:35 |
Rev Time |
0.15 |
Received By |
ydavis |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | NEEDS DMP APPROVAL |
|
|