Plan Review Details - Permit 00100247
Plan Review Stops For Permit 00100247
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-03-05 Cont ID  
Sent By hpiskura Date 2001-03-05 Time 14:01 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-11-06 Cont ID  
Sent By drunnels Date 2000-11-06 Time 11:11 Rev Time 2.00
Received By drunnels Date 2000-11-06 Time 11:11 Sent To  
Notes
2001-01-08 00:00:001.PROVIDE PRODUCT APPROVALS FOR WINDOWS,
 DOORS AND ROOF COVERINGS ON ALL
 STRUCTURES
 2.PROVIDE DETAILS SHOWING CONCESSION
 BUILDING COMPLYING WITH THE FLORIDA
 ACCESSIBILITY CONE FOR BUILDING CONSTRU-
 CTION 1997 EDITION
 3. PROVIDE ENGINEERING SHOWING DUG OUT,
 AND SCOREBOARD COMPLYING WITH CHAPTER 16
 1997 EDITION SBC
 4.PROVIDE FOOTING DETAILS FOR THE
 CONCESSION BUILDING
 5.IF THE FOOTING AND FOUNDATION FOR
 PAVILION IS IN THIS CONTRACT PLEASE
 PROVIDE PLANS AND DETAILS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-04-02 Cont ID  
Sent By dpalmer Date 2001-04-02 Time 08:57 Rev Time 0.00
Received By dpalmer Date 2001-04-02 Time 08:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-02-28 Cont ID  
Sent By dpalmer Date 2001-02-28 Time 10:12 Rev Time 0.00
Received By dpalmer Date 2001-02-28 Time 10:12 Sent To  
Notes
2001-02-28 00:00:00************* UNSAT ************
  
 1)NOTE: PLEASE SEE SHEET 2 OF 4 THIS IS
 SHOWING A NEW ELECTRICAL SERVICE AND
 3 OF 4 SAYS EXISTING?
  
 2)NOTE: PLEASE NOTE LOAD CALCULATIONS
 FOR MAIN SERVICE WAS NOT SUBMITTED SHOW-
 ING ALL CONTINUOUS LOADS AT 125%.
  
 3)NOTE: PLEASE SEE 3 OF 4 "PLAN NOTES"
 #3 SHOWS 4-1/0`S AND #6G. THIS IS SHOWN
 AS A 1PHASE SERVICE. PLEASE CLARIFY.
  
 4)NOTE:PLEASE NOTE THAT ALL ELECTRICAL
 POWER FEEDING PAVILLIONS REQ MEANS OF
 DISCONNECT PER 225-31.
  
 PLEASE SUBMIT THE ABOVE CLARIFICATION
 AND INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS OR IF CORRECTIONS CAN BE
 TAKEN CARE OF IN PERSON, PLEASE CALL
 TO SSET UP A TIME FOR A MEETING.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-10-31 Cont ID  
Sent By dpalmer Date 2000-10-31 Time 19:15 Rev Time 0.00
Received By dpalmer Date 2000-10-31 Time 19:15 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 SHOWING ALL CONTINUOUS LOADS AT 125%
 LIGHTING ETC.SHEET E-3 OF 4 SHOWS CON-
 -CESSION PANEL AS BEING BY OTHERS??
 PLEASE SUBMIT CLARIFICATION?
 PANEL FOR CONCESSION BLDG IS ON 4 OF 4?
 CONTINUOUS LOADS FOR PANEL "L" ALSO.
  
 2)NOTE: PLEASE SEE NOTE #3 NOTE DESCRIBE
 -S 4-1/0`S FOR FEED TO PANEL"L". SHOWS
 MAIN BREAKER AT 60AMPS. PLEASE CALRIFY
 1/0 WIRE SIZE INTO 60A BRKR.
  
 3)NOTE: PLEASE SEE 110-26 AND 384-7 FOR
 PANEL REQ`MENTS IN A "STORAGE ROOM".
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-11-08 Cont ID  
Sent By mgonzale Date 2000-11-08 Time 14:38 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-10-25 Cont ID  
Sent By rturnque Date 2000-10-25 Time 10:23 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-10-30 Cont ID  
Sent By ndenmark Date 2000-10-30 Time 17:07 Rev Time 0.25
Received By ndenmark Date 2000-10-30 Time 17:07 Sent To  
Notes
2001-01-08 00:00:00MECHANICAL PERMIT REQUIRED FOR MECHANICA
 WORK

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-11-08 Cont ID  
Sent By pschmitz Date 2000-11-08 Time 10:58 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO FOR PLUMBING
 (1) FLR DRAINS ARE REQUIRED IN PUBLIC
 REST RM'S SEC 409.4.1.1
 (2) AIR CHAMBERS TO COMPLY WITH
 SEC 607.8.2 TO BE ACCESIBLE, RECHARGEABL
 END OF COMMENTS QUESTIONS CALL
 PAUL SCHMITZ 561-659-8096 X 8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-10-21 Cont ID  
Sent By tlarge Date 2000-10-21 Time 10:21 Rev Time 2.25
Received By tlarge Date 2000-10-21 Time 10:21 Sent To  
Notes
2001-01-08 00:00:001)A WATER USE PERMIT IS REQD.FROM SO.FLA
 WATER MNGMT.DIV.FOR THE IRRIGATION
 SYSTEM PER F.S.373.219.SUBMIT COPY OF
 PERMIT.
  
 2)A WELL DRILLING PERMIT WILL ALSO BE
 REQD.FROM SFWMD AND P.B.COUNTY HEALTH
 DEPT.COUNTYWIDE AMENDMENTS TO SPC SEC.
 101.4.7.
  
 3)FLOOR DRAINS ARE REQD.IN THE TOILET
 ROOMS PER SPC SEC.409.4.1.1.
  
 4)DOOR SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQD.FOR THE DRINKING
 FOUNTAINS.(A MIN.30"X48"CLEAR SPACE IS
 REQD.FACBC SEC.4.15.5.
  
 5)SHT.P-1-NOTE #5-CALCULATED AIR CHAMBER
 SHALL COMPLY W/STANDARD PDI-WH201.SPC
 SEC.607.8.2.
  
 6)SHOW SINK AND DRINKING FOUNTAIN ON
 WATER RISER ON SHT.P-1.COUNTYWIDE AMEND-
 MENT TO SPC SEC.104.2.1.
  
 CALL IF YOU HAVE QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-10-19 Cont ID  
Sent By gjoyce Date 2000-10-19 Time 13:28 Rev Time 0.15
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***