Plan Review Stops For Permit 00100036 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2000-11-02 |
|
|
Cont ID |
|
Sent By |
drunnels |
Date |
2000-11-02 |
Time |
08:26 |
Rev Time |
1.00 |
Received By |
drunnels |
Date |
2000-11-02 |
Time |
08:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2000-10-30 |
|
|
Cont ID |
|
Sent By |
drunnels |
Date |
2000-10-30 |
Time |
09:05 |
Rev Time |
2.00 |
Received By |
drunnels |
Date |
2000-10-27 |
Time |
15:01 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1.SHEET A1.1 DETAIL 2 RECEPTION COUNTER | | DOES NOT COMPLY TO SECTION 7.2 OF THE | | 1997 EDITION FLORIDA ACCESSIBILITY CODE | | FOR BUILDING CONSTRUCTION. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2001-02-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-02-14 |
Time |
10:57 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-02-14 |
Time |
10:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2000-12-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-12-27 |
Time |
17:26 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-12-27 |
Time |
17:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2000-10-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-10-25 |
Time |
01:51 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-10-25 |
Time |
01:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2000-12-14 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-12-14 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-12-14 |
Time |
15:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2000-11-02 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-11-02 |
Time |
10:58 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-11-02 |
Time |
10:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2000-10-04 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-10-04 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-10-04 |
Time |
16:13 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) PLEASE INDICATE EXIT SIGN LOCATIONS | | ON PLANS. THEY COULD NOT BE LOCATED | | WITHIN THE DRAWINGS. | | 2) NO INTERIOR FINISH NOTES ON PLANS. | | INTERIOR FINISH IN EXITS TO BE CLASS | | A OR B. INTERIOR FINISH IN OFFICES TO | | BE CLASS A,B, OR C. | | 3) FIRE ALARM NOTES, PAGE FAO.1, | | INDICATES CLASS B, STYLE C FIRE ALARM | | CIRCUITS. CLASS A, STYLE D FIRE ALARM | | CIRCUITS IS ONLY PERMITTED. | | 4) PROVIDE FIRE ALARM SYSTEM SHOP | | DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN | | ON PLANS. CUT SHEETS ON ALL DEVICES | | PLANNED FOR USE ARE TO BE SUBMITTED. | | A SEPARATE PLAN AND PERMIT IS REQUIRED. | | 5) LOCKS ON EXIT DOORS TO COMPLY WITH | | SPECIAL LOCKING ARRANGEMENTS, SECTION | | 5-2.1.6, 1985 EDITION OF THE LIFE | | SAFETY CODE. | | 6) NO FIRE SPRINKLER DRAWINGS INCLUDED | | WITH PLANS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2001-02-26 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-02-26 |
Time |
16:43 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2001-02-26 |
Time |
16:42 |
Sent To |
|
|
Notes |
2001-02-26 00:00:00 | NOTE:VAV 10-7, DRAWING M5.1 VAV | | SCHEDULE INDICATES REQUIRED CFM IS 500 | | - DRAWING M2.1 ONLY REFLECTS 350 CFM | | FOR VAV 10-7. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-01-09 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2001-01-09 |
Time |
13:33 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2001-01-09 |
Time |
13:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2000-10-31 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-10-30 |
Time |
16:26 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2000-10-30 |
Time |
16:26 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ***********DENIED*********************** | | 1. 1997 SMC 610 REQUIRES THE LOCATION | | AND INSTALLATION INSTRUCTIONS FOR EACH | | REQUIRED FIRE OR FIRE SMOKE DAMPER BE | | SHOWN AND PROPERLY IDENTIFIED ON THE | | BUILDING PLANS BY THE DESIGNER. | | FIRE DAMPERS ARE NOT SHOWN AT THE RATED | | WALLS FOR THE BATHROOM (159) | | ARE THE WALL TO THE ELECTRICAL ROOM | | RATED? | | ARE THE ELEVATOR LOBBY WALLS FIRE OR | | SMOKE RATED? | | INCLUDE ABOVE INFORMATION FOR REVIEW. | | | | REVISED PLAN SHOWING LOCATION AND DETAIL | | OF ABOVE DAMPERS TO BE SUBMITTED AND | | REVIEWED PRIOR TO THE MECH PERMIT BEING | | ISSUED |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2001-02-26 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-02-26 |
Time |
08:35 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2001-02-26 |
Time |
08:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-01-13 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-01-13 |
Time |
11:23 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2001-01-13 |
Time |
11:22 |
Sent To |
|
|
Notes |
2001-01-13 00:00:00 | PROVISO; | | 1.DELETE FLOOR DRAIN DETAIL PO.1 | | 2.DELETE HANDICAP W/C AND LAV. FROM | | SANITARY ISOMETRIC P5.1 | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2000-10-15 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2000-10-15 |
Time |
11:57 |
Rev Time |
1.50 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PLUMBING PLAN REVIEW PROVISO | | (1) SHT P-2.1 TOILET RM 104-B TO COMPLY | | W/ FACBC SEC 4.1.3 (11) TO BE ADAPTABLE. | | (2) SHT P-5.1 AIR CHAMBERS TO COMPLY | | W/ SPC 94 SEC 607.8.3 TO BE ACCESSIBLE | | AND RECHARGEABLE. | | END OF COMMENTS. |
|
|