Plan Review Details - Permit 00100036
Plan Review Stops For Permit 00100036
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-11-02 Cont ID  
Sent By drunnels Date 2000-11-02 Time 08:26 Rev Time 1.00
Received By drunnels Date 2000-11-02 Time 08:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-10-30 Cont ID  
Sent By drunnels Date 2000-10-30 Time 09:05 Rev Time 2.00
Received By drunnels Date 2000-10-27 Time 15:01 Sent To  
Notes
2001-01-08 00:00:001.SHEET A1.1 DETAIL 2 RECEPTION COUNTER
 DOES NOT COMPLY TO SECTION 7.2 OF THE
 1997 EDITION FLORIDA ACCESSIBILITY CODE
 FOR BUILDING CONSTRUCTION.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-02-14 Cont ID  
Sent By dpalmer Date 2001-02-14 Time 10:57 Rev Time 0.00
Received By dpalmer Date 2001-02-14 Time 10:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-12-27 Cont ID  
Sent By dpalmer Date 2000-12-27 Time 17:26 Rev Time 0.00
Received By dpalmer Date 2000-12-27 Time 17:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-10-25 Cont ID  
Sent By dpalmer Date 2000-10-25 Time 01:51 Rev Time 0.00
Received By dpalmer Date 2000-10-25 Time 01:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-12-14 Cont ID  
Sent By mcarsill Date 2000-12-14 Time 15:45 Rev Time 0.00
Received By mcarsill Date 2000-12-14 Time 15:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-11-02 Cont ID  
Sent By mcarsill Date 2000-11-02 Time 10:58 Rev Time 0.00
Received By mcarsill Date 2000-11-02 Time 10:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-10-04 Cont ID  
Sent By mcarsill Date 2000-10-04 Time 16:13 Rev Time 0.00
Received By mcarsill Date 2000-10-04 Time 16:13 Sent To  
Notes
2001-01-08 00:00:001) PLEASE INDICATE EXIT SIGN LOCATIONS
 ON PLANS. THEY COULD NOT BE LOCATED
 WITHIN THE DRAWINGS.
 2) NO INTERIOR FINISH NOTES ON PLANS.
 INTERIOR FINISH IN EXITS TO BE CLASS
 A OR B. INTERIOR FINISH IN OFFICES TO
 BE CLASS A,B, OR C.
 3) FIRE ALARM NOTES, PAGE FAO.1,
 INDICATES CLASS B, STYLE C FIRE ALARM
 CIRCUITS. CLASS A, STYLE D FIRE ALARM
 CIRCUITS IS ONLY PERMITTED.
 4) PROVIDE FIRE ALARM SYSTEM SHOP
 DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN
 ON PLANS. CUT SHEETS ON ALL DEVICES
 PLANNED FOR USE ARE TO BE SUBMITTED.
 A SEPARATE PLAN AND PERMIT IS REQUIRED.
 5) LOCKS ON EXIT DOORS TO COMPLY WITH
 SPECIAL LOCKING ARRANGEMENTS, SECTION
 5-2.1.6, 1985 EDITION OF THE LIFE
 SAFETY CODE.
 6) NO FIRE SPRINKLER DRAWINGS INCLUDED
 WITH PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-02-26 Cont ID  
Sent By pkrauss Date 2001-02-26 Time 16:43 Rev Time 0.35
Received By pkrauss Date 2001-02-26 Time 16:42 Sent To  
Notes
2001-02-26 00:00:00NOTE:VAV 10-7, DRAWING M5.1 VAV
 SCHEDULE INDICATES REQUIRED CFM IS 500
 - DRAWING M2.1 ONLY REFLECTS 350 CFM
 FOR VAV 10-7.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-01-09 Cont ID  
Sent By ndenmark Date 2001-01-09 Time 13:33 Rev Time 0.33
Received By ndenmark Date 2001-01-09 Time 13:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-10-31 Cont ID  
Sent By ndenmark Date 2000-10-30 Time 16:26 Rev Time 0.33
Received By ndenmark Date 2000-10-30 Time 16:26 Sent To  
Notes
2001-01-08 00:00:00***********DENIED***********************
 1. 1997 SMC 610 REQUIRES THE LOCATION
 AND INSTALLATION INSTRUCTIONS FOR EACH
 REQUIRED FIRE OR FIRE SMOKE DAMPER BE
 SHOWN AND PROPERLY IDENTIFIED ON THE
 BUILDING PLANS BY THE DESIGNER.
 FIRE DAMPERS ARE NOT SHOWN AT THE RATED
 WALLS FOR THE BATHROOM (159)
 ARE THE WALL TO THE ELECTRICAL ROOM
 RATED?
 ARE THE ELEVATOR LOBBY WALLS FIRE OR
 SMOKE RATED?
 INCLUDE ABOVE INFORMATION FOR REVIEW.
  
 REVISED PLAN SHOWING LOCATION AND DETAIL
 OF ABOVE DAMPERS TO BE SUBMITTED AND
 REVIEWED PRIOR TO THE MECH PERMIT BEING
 ISSUED

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-02-26 Cont ID  
Sent By jleech Date 2001-02-26 Time 08:35 Rev Time 0.50
Received By jleech Date 2001-02-26 Time 08:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-01-13 Cont ID  
Sent By jleech Date 2001-01-13 Time 11:23 Rev Time 0.50
Received By jleech Date 2001-01-13 Time 11:22 Sent To  
Notes
2001-01-13 00:00:00PROVISO;
 1.DELETE FLOOR DRAIN DETAIL PO.1
 2.DELETE HANDICAP W/C AND LAV. FROM
 SANITARY ISOMETRIC P5.1
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-10-15 Cont ID  
Sent By pschmitz Date 2000-10-15 Time 11:57 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW PROVISO
 (1) SHT P-2.1 TOILET RM 104-B TO COMPLY
 W/ FACBC SEC 4.1.3 (11) TO BE ADAPTABLE.
 (2) SHT P-5.1 AIR CHAMBERS TO COMPLY
 W/ SPC 94 SEC 607.8.3 TO BE ACCESSIBLE
 AND RECHARGEABLE.
 END OF COMMENTS.