Plan Review Details - Permit 00100027
Plan Review Stops For Permit 00100027 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2000-11-14 |
|
|
Cont ID |
|
Sent By |
drunnels |
Date |
2000-11-14 |
Time |
11:06 |
Rev Time |
1.00 |
Received By |
drunnels |
Date |
2000-11-14 |
Time |
11:06 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1. THIS PERMIT INCLUDES FOUNDATION FOR | | GAZEBO ONLY. STRUCTURE IS TO BE UNDER | | SEPERATE PERMIT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2000-10-25 |
|
|
Cont ID |
|
Sent By |
drunnels |
Date |
2000-10-25 |
Time |
10:08 |
Rev Time |
1.50 |
Received By |
drunnels |
Date |
2000-10-25 |
Time |
10:08 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1. PROVIDE MANUFACTURER SPECS ON GAZEBO, | | SUNSHELTERS,& PAVILION |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2000-10-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-10-25 |
Time |
01:35 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-10-25 |
Time |
01:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2000-10-24 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-10-24 |
Time |
15:52 |
Rev Time |
0.45 |
Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2000-12-04 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2000-12-04 |
Time |
11:00 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2000-12-04 |
Time |
11:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2000-11-14 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2000-11-14 |
Time |
13:09 |
Rev Time |
1.50 |
Received By |
jleech |
Date |
2000-11-14 |
Time |
13:09 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | DENIED; | | 1.PROVISIONS SHALL BE MADE FOR PEOPLE | | WHO HAVE TROUBLE BENDING OR STOOPING | | FACBC SEC 4.1.2(2) AND 4.3.2(2) | | 2.SHOW LOCATION OF SANITARY FACILITIES | | FOR THE PARK.SPC SEC 407.1.1 407.1.2. | | 3.PVC CANNOT BE USED FOR WATER DIST. | | UNDER SLAB AT PAVILION.611.3 | | 4.SUBMIT SANITARY ISOMETRIC SHOWING | | PIPE SIZE AND CONNECTION POINT TO | | SANITARY COLLECTION. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2000-10-15 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-10-15 |
Time |
10:15 |
Rev Time |
0.75 |
Received By |
tlarge |
Date |
2000-10-15 |
Time |
09:52 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1)PROVIDE DETAILS ON DRINKING FOUNTAIN. | | FOUNTAIN SHALL BE ON AN ACCESSIBLE | | ROUTE AND PROVISIONS SHALL BE MADE FOR | | PEOPLE WHO HAVE TROUBLE BENDING OR | | STOOPING.FACBC SEC.4.1.2(2),4.3.2(2) | | 4.1.3(10)(A),4.3.1. | | | | 2)WATER SUPPLY CONTROL FOR DRINKING | | FOUNTAIN AND HOSE BIBB SHALL COMPLY W/ | | SPC SEC.610.4.1. | | | | 3)SUBMIT SANITARY ISOMETRIC SHOWING | | PIPE SIZE,CONNECTION POINT TO SANITARY | | COLLECTION | | | | 4)PVC CANNOT BE USED FOR WATER DIST. | | PER SPC SEC.611.3. | | | | 5)SHOW LOCATION OF SANITARY FACILITIES | | FOR THE PARK.SPC SEC.407.1.1.407.1.2. | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | QUESTIONS. | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-10-05 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
2000-10-05 |
Time |
10:47 |
Rev Time |
0.10 |
Received By |
nleiva |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|